R-407C

R-407C was built to replace R-22: similar pressures, POE oil, and a straightforward changeout. In commercial refrigeration it appears mostly in medium-temperature equipment, and manufacturer selection tables often rate it alongside R-407A[1].

Its GWP of 1,774 puts it over the 1,400 interim limit from the May 2026 rule, so new installs in the GWP-limited subsectors cannot use it (91 FR 31284)[2]. Existing systems stay legal to run and service.

R-407C quick facts
TypeHFC blend: 23% R-32, 25% R-125, 52% R-134a
ASHRAE safety classA1 (no flame propagation)
GWP (AIM Act exchange values)1,774 (computed per 40 CFR 84.64)
Temperature glideAbout 8 to 10 °F. Bubble for charging, dew for superheat
LubricantPOE
Common useR-22 replacement in AC and medium-temperature refrigeration

Regulatory status

Running and servicing existing equipmentAllowed[2]
Buying bulk cylindersSection 608-certified buyers only[3]
New remote condensing unitsNot allowed since Jul 27, 2026 (over the 1,400 interim limit)[2]
New supermarket systemsNot allowed from Jan 1, 2027[2]
New cold storage systemsNot allowed since Jul 27, 2026[2]

Rules

Federal

R-407C's GWP of 1,774 is over the interim limits for every restricted refrigeration subsector, so the interim dates end new R-407C installs there (91 FR 31284)[2]. The rule restricts new systems. It does not ban running or servicing existing equipment[2].

SubsectorLimitDateR-407C outcome
Remote condensing units (retail food)GWP 1,400 interimJul 27, 2026[2]GWP 150/300 on Jan 1, 2032
Supermarket systemsGWP 1,400 interimJan 1, 2027[2]GWP 150/300 on Jan 1, 2032
Cold storage warehousesGWP 700 interimJul 27, 2026[2]GWP 150/300 on Jan 1, 2032
Current federal GWP limits for new installs in each subsector, after the May 2026 reconsideration.

Five consolidated petitions challenge the May 2026 rule in the D.C. Circuit (lead case HARDI v. EPA, No. 26-1168)[2]. The dates above are current law while the litigation runs.

State

Each row below is checked against the state's own regulation text:

StateRuleEffective
WashingtonRetail food refrigeration over 50 lb charge (new): GWP over 150 prohibited, which covers R-407CJan 1, 2025
States verified against the state's own regulation text. State coverage grows as verification completes.

Vermont (10 V.S.A. § 586), Maryland, and Rhode Island restrict listed substances in supermarket and condensing-unit subsectors. Their legacy lists target R-404A-class blends rather than R-407C. California's SB 1206 bulk-sale threshold reaches GWP 1,500 in 2030, which does not cover R-407C, and 750 in 2033, which does. Verify with your local authority having jurisdiction before an install decision.

Buying R-407C

Bulk R-407C can only be sold to Section 608-certified technicians and related buyers under 40 CFR 82.154[3].

Replacements

For new equipment in the restricted subsectors, R-448A and R-449A carry the interim window through 2031, and CO2, R-290, R-454C, and R-455A carry the 2032 limits[2]. Existing R-407C systems keep running. The AIM Act phasedown (40 CFR 84.7) will push service prices up over time[7].

R-407C PT chart

Saturation pressures for R-407C from -40 °F upward, computed from reference equations of state[6]. R-407C has one of the larger glides in common use, about 8 to 10 °F, so the bubble and dew columns differ by roughly 13 psi at box temperatures. Charging and subcooling use bubble, and superheat uses dew.

Full-page R-407CPT chart →

Temp (°F)Liquid / bubble (psig)Vapor / dew (psig)
-402.7-2.3
-355.1-0.4
-307.71.6
-2510.63.9
-2013.76.5
-1517.29.3
-1020.912.3
-525.015.7
029.519.4
534.323.5
1039.527.9
1545.232.7
2051.237.9
2557.743.5
3064.749.6
3572.256.1
4080.263.2
4588.870.7
5097.978.8
55107.687.5
60117.996.8
65128.9106.7
70140.5117.3
75152.8128.5
80165.8140.5
85179.6153.2
90194.1166.7
95209.4181.0
100225.5196.1
105242.4212.1
110260.3229.0
115279.0246.9
120298.6265.8
125319.2285.7
130340.7306.6

Use the vapor (dew) column to check superheat at the suction line. Use the liquid (bubble) column to check subcooling at the liquid line and for charging. R-407C glide is about 8 to 10 °F. Using the wrong column misstates superheat by several degrees. R-407C values are computed, not transcribed; see Sources.

Equipment rated for R-407C

Walk-in unit cooler models whose maker publishes R-407C ratings, usually in a shared column with R-407A. Each page shows the full specifications with the page each value comes from.

939 models in the database carry R-407C ratings. A sample:

Browse all 939models →

Questions

Is R-407C being phased out?

New installs in the GWP-limited refrigeration subsectors ended with the interim limits (July 27, 2026 for remote condensing units, January 1, 2027 for supermarkets, per 91 FR 31284). Existing systems stay legal to run and service, and R-407C remains common in AC applications not covered by those limits.

Can R-407C replace R-22?

That is what it was designed for. The changeout needs POE oil and attention to the glide when setting superheat. Check the equipment manufacturer's retrofit guidance for TXV and charge adjustments.

Why do my gauges disagree with the box temperature on R-407C?

Glide. R-407C evaporates across a temperature range of roughly 8 to 10 degrees F, so a single saturation temperature does not exist at a given pressure. Use the dew column for superheat and the bubble column for subcooling.

Updated