TEP025LE-S4E
Trenton Refrigeration TEP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 1 count | TEP + TEP-GEN-E p.5 ✓ | |
| capacity | 26600 btu_h | evap temp f: 0; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.5 ✓ |
| 25900 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.5 ✓ | |
| 25100 btu_h | evap temp f: 20; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.5 ✓ | |
| 22800 btu_h | evap temp f: 30; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.5 ✓ | |
| 21300 btu_h | evap temp f: 40; refrigerant: R407A/R407C/R448A/R449A | TEP + TEP-GEN-E p.5 ✓ | |
| 21600 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.5 | |
| 21000 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.5 | |
| 20400 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.5 | |
| 18800 btu_h | evap temp f: 30; refrigerant: R404A/R507 | p.5 ✓ | |
| 17300 btu_h | evap temp f: 40; refrigerant: R404A/R507 | p.5 | |
| 26600 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.5 ✓ | |
| 25900 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.5 ✓ | |
| 25100 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.5 ✓ | |
| 22800 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.5 ✓ | |
| 21300 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.5 ✓ | |
| 21600 btu_h | evap temp f: 0; refrigerant: R404A | p.8 | |
| 21000 btu_h | evap temp f: 10; refrigerant: R404A | p.8 | |
| 20400 btu_h | evap temp f: 20; refrigerant: R404A | p.8 | |
| 18800 btu_h | evap temp f: 30; refrigerant: R404A | p.8 | |
| 17300 btu_h | evap temp f: 40; refrigerant: R404A | p.8 | |
| airflow | 3700 cfm | TEP + TEP-GEN-E p.5 ✓ | |
| 1750 l_s | TEP + TEP-GEN-E p.5 ✓ | ||
| refrigerant charge | 5.2 lb | refrigerant: R407A/R407C | TEP + TEP-GEN-E p.5 ✓ |
| 2.4 kg | refrigerant: R407A/R407C | TEP + TEP-GEN-E p.5 ✓ | |
| 4.8 lb | refrigerant: R404A/R507 | p.5 | |
| 2.2 kg | refrigerant: R404A/R507 | p.5 | |
| 4.7 lb | refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.5 ✓ | |
| 2.1 kg | refrigerant: R454A/R454C/R455A | TEP + TEP-GEN-E p.5 ✓ | |
| 5 lb | refrigerant: R448A/R449A | TEP + TEP-GEN-E p.5 ✓ | |
| 2.3 kg | refrigerant: R448A/R449A | TEP + TEP-GEN-E p.5 ✓ | |
| 4.8 lb | refrigerant: R404A | p.8 | |
| 2.2 kg | refrigerant: R404A | p.8 | |
| awef rating | 4.15 ratio | refrigerant: R404A/R507 | p.35 ✓ |
| 4.15 ratio | refrigerant: R407A/R407C | p.35 | |
| 4.15 ratio | refrigerant: R448A/R449A | p.35 | |
| 4.15 ratio | refrigerant: R454A | p.35 | |
| 4.15 ratio | refrigerant: R454C | p.35 | |
| 4.15 ratio | refrigerant: R455A | p.35 | |
| 4.15 ratio | p.33 | ||
| suction od | 1 3/8 inches | TEP + TEP-GEN-E p.37 ✓ | |
| distributor inlet | 0.875 inches | defrost piping: reverse_cycle_3_pipe | p.37 |
| 0.875 inches | TEP + TEP-GEN-E p.37 ✓ | ||
| side port connection | 0.5 inches | defrost piping: reverse_cycle_3_pipe | p.37 |
| 0.5 inches | p.36 | ||
| hot gas connection | 0.875 inches | p.37 | |
| shipping weight | 215 lb | TEP + TEP-GEN-E p.38 ✓ | |
| 98 kg | TEP + TEP-GEN-E p.38 ✓ | ||
| fpi | 6 | TEP + TEP-GEN-E p.13 ✓ | |
| mca | 12.8 ampssources differ | TEP p.13 | |
| 15 ampssources differ | TEP-GEN-E p.13 | ||
| 12.8 ampssources differ | TEP-GEN-E p.13 | ||
| esp circuit 460 1 60 mop a | 15 | TEP + TEP-GEN-E p.13 ✓ | |
| voltage | 460 V | TEP + TEP-GEN-E p.? ✓ | |
| phase | 1 ph | TEP + TEP-GEN-E p.? ✓ | |
| frequency | 60 Hz | TEP + TEP-GEN-E p.? ✓ | |
| liquid line od | 9.5 mm | p.51 | |
| suction line od | 22.2 mm | p.51 | |
| maximum line length 3m minimum room area m2 | 7 | p.51 | |
| maximum line length 7 6m | 9 | p.51 | |
| maximum line length 15 2m | 13 | p.51 | |
| maximum line length 30 5m | 20 | p.51 | |
| motor hp | 1 hp | p.13 | |
| motor fla | 2.5 amps | p.13 | |
| motor watts | 350 watts | p.13 | |
| mop | 15 amps | p.13 | |
| total watts | 4728 watts | p.13 | |
| total amps | 10.3 amps | p.13 | |
| defrost heaters 460 1 60 mop a | 15 | p.13 | |
| esp circuit mca | 12.8 amps | p.18 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TEP025LE-S4E | 460/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 025 |
| capacity mbh | 25 |
| defrost | E |
| generation suffix | E |
| temp class | L |
| voltage | S4 |
Parts
12 factory parts for this unit: 12from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | G4✓ | Distributor nozzle; Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E2V24order as E2V24FWBC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV11order as CSOV-11S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV10✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B6order as B6S1✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| TXV | EBSSE-6-ZP✓ | evap temp f: -20; Thermostatic expansion valve (TXV) — evap temp f: -30; Thermostatic expansion valve (TXV) — evap temp f: -40 | - | - | Check availability |
| TXV | ERSE-3-C✓ | evap temp f: 0 | - | - | Check availability |
| TXV | ERSE-6-ZPorder as ERSE-6-ZP40✓ | evap temp f: -10 | - | - | Check availability |
| TXV | ERVE-3-C✓ | evap temp f: 0, refrigerant: R407A/R448A/R449A | - | - | Check availability |
| TXV | ERVE-4-ZPorder as ERVE-4-ZP40✓ | evap temp f: -10, refrigerant: R407A/R448A/R449A | - | - | Check availability |
| TXV | ERVE-5-ZPorder as ERVE-5-ZP40✓ | evap temp f: -20, refrigerant: R407A/R448A/R449A | - | - | Check availability |
| TXV | ERVE-8-ZPorder as ERVE-8-ZP40✓ | evap temp f: -30, refrigerant: R407A/R448A/R449A; Thermostatic expansion valve (TXV) — evap temp f: -40, refrigerant: R407A/R448A/R449A | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KEP025LE-S4E | shared catalog stem ✓ |
| Bally | BEP025LE-S4E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TEP025LE-S4E?
TEP025LE-S4E has a rated capacity of 26600 btu_h. See the specifications table for rating conditions.
What voltage does TEP025LE-S4E require?
TEP025LE-S4E runs on 460 V supply power.
Related models in TEP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.