R-454B

R-454B is an A2L refrigerant blend with a GWP of 466 under the AIM Act exchange values[1]. It is the main replacement for R-410A in new residential and light-commercial air conditioners and heat pumps, sold under trade names including Opteon XL41 and Puron Advance.

It sits under the 700 GWP limit for new AC systems (88 FR 73098)[2]. It is mildly flammable (ASHRAE class A2L), which changes handling, tools, and equipment listings compared with R-410A[5].

R-454B quick facts
TypeA2L blend: 68.9% R-32, 31.1% R-1234yf
ASHRAE safety classA2L (lower flammability)
GWP (AIM Act exchange values)466
Temperature glideAbout 1 to 1.5 °F
LubricantPOE
Trade namesOpteon XL41, Puron Advance
Common useNew residential and light-commercial AC and heat pumps (R-410A replacement)

Regulatory status

New AC and heat pump equipmentAllowed (GWP 466, under the 700 limit)[2]
Buying bulk cylindersSection 608-certified buyers only[4]
Flammability classA2L (lower flammability)[5]
Drop-in for R-410A systemsNo. A2L-listed equipment only[5]

Rules

Federal

The Technology Transitions rule set a 700 GWP limit for new residential and light-commercial AC and heat pump systems, applying to products manufactured from January 1, 2025 (88 FR 73098)[2]. R-410A (GWP 2,088) fails that limit. R-454B and R-32 pass it.

EPA's May 2026 rule (91 FR 31284) removed the installation deadline for systems whose components were manufactured before 2025, so R-410A equipment already built can still be installed[3]. New manufacture belongs to R-454B and R-32.

SubsectorLimitDateR-454B outcome
Residential and light-commercial AC/HP (products)GWP 700Jan 1, 2025 (manufacture)[2]R-454B compliant
Residential and light-commercial AC/HP (installs of pre-2025 components)install deadline removedJul 27, 2026[3]pre-2025 R-410A equipment installable
Current federal GWP limits for new installs in each subsector, after the May 2026 reconsideration.

State

California applies a GWP 750 limit to new residential and nonresidential AC from January 1, 2025 under CARB's HFC regulation, and R-454B passes it[6]. Verify with your local authority having jurisdiction. A2L adoption also depends on state building and mechanical codes.

Buying R-454B

Bulk R-454B can only be sold to Section 608-certified technicians and related buyers under 40 CFR 82.154[4]. A2L blends fall under the same sales restriction as the HFCs they replace.

Safety and handling

A2L means lower flammability under ASHRAE Standard 34: harder to ignite and slower-burning than propane-class A3 refrigerants, and not nonflammable like R-410A[5]. Equipment must be designed and listed for A2L use. Use A2L-rated recovery machines and tools. Do not charge R-454B into a system designed for R-410A.

R-454B PT chart

Saturation pressures for R-454B from -40 °F to 130 °F (-40 °C to 54.4 °C), computed from reference equations of state[7]. Operating pressures run close to R-410A, slightly lower. The glide is small (about 1 to 1.5 °F): read the vapor column for superheat and the liquid column for subcooling.

Full-page R-454BPT chart →

Temp (°F)Liquid / bubble (psig)Vapor / dew (psig)
-409.88.5
-3513.011.5
-3016.614.9
-2520.518.6
-2024.722.7
-1529.427.1
-1034.532.0
-540.037.2
045.942.9
552.449.1
1059.355.7
1566.862.9
2074.870.6
2583.578.9
3092.787.8
35102.697.3
40113.2107.5
45124.5118.3
50136.4129.9
55149.2142.2
60162.7155.3
65177.1169.2
70192.3183.9
75208.4199.5
80225.4216.0
85243.4233.5
90262.3251.9
95282.3271.4
100303.3291.9
105325.4313.5
110348.6336.3
115373.0360.3
120398.6385.5
125425.5412.1
130453.6440.0

Use the vapor (dew) column to check superheat at the suction line. Use the liquid (bubble) column to check subcooling at the liquid line and for charging. R-454B has a small glide. Use dew for superheat and bubble for subcooling. R-454B values are computed, not transcribed; see Sources.

Equipment rated for R-454B

R-454B is an air conditioning refrigerant, and no walk-in unit cooler or condensing unit rates it today. The refrigeration A2Ls in the walk-in lines are R-454A, R-454C, and R-455A.

Questions

Is R-454B flammable?

Mildly. ASHRAE Standard 34 classes it A2L: lower flammability, harder to ignite than A3 refrigerants like propane. Equipment, sensors, and service tools must be rated for A2L use.

Is R-454B being phased out?

No rule restricts R-454B. It is the replacement refrigerant under the current 700 GWP limit for new AC systems (88 FR 73098). Overall HFC supply follows the AIM Act phasedown, and low-GWP blends consume the fewest allowances per pound.

What is the difference between R-454B and R-410A?

GWP 466 versus 2,088, and A2L versus A1. Operating pressures are similar, slightly lower for R-454B. The two are not interchangeable: R-454B belongs only in equipment designed and listed for it.

Can I retrofit an R-410A system to R-454B?

No. R-454B is not approved as a retrofit for R-410A equipment. Flammability listing, sensors, and component ratings differ. Pre-2025 R-410A equipment can still be installed and serviced (91 FR 31284).

Updated