R-290

R-290 is refrigerant-grade propane. With a GWP of 3.3 it passes every federal GWP limit, including the 150 limits that arrive for large systems on January 1, 2032 (91 FR 31284)[2]. It is one of the three long-term paths for commercial refrigeration, next to CO2 and the A2L blends.

The tradeoff is flammability. R-290 is ASHRAE class A3, so it appears in self-contained, charge-limited equipment rather than large field-piped systems. Charge limits come from EPA SNAP use conditions and the equipment safety standard[4].

R-290 quick facts
TypeNatural refrigerant: refrigerant-grade propane, single compound
ASHRAE safety classA3 (higher flammability)
GWP (AIM Act exchange values)3.3
Temperature glideNone (single compound)
LubricantMineral oil or POE per equipment listing
Common useSelf-contained commercial refrigeration: reach-ins, display cases, small monoblocks

Regulatory status

Buying R-290No Section 608 restriction, as an exempt substitute in its listed end-uses[3]
New equipment, any GWP-limited subsectorQualifies (GWP 3.3 is under every limit)[2]
Charge per circuitCapped by SNAP use conditions and UL 60335-2-89 listing[4]
VentingExempt from the venting prohibition in listed end-uses[4]

Rules

Federal

R-290 is under every GWP limit in the Technology Transitions rule, so the compliance dates that end high-GWP installs are entry points for R-290 equipment[2]. The binding federal constraints are the SNAP use conditions instead: listed end-uses, charge limits, and marking requirements (89 FR 50410)[4].

SubsectorLimitDateR-290 outcome
Retail food refrigeration (self-contained)SNAP-listed end-useCurrent[4]Charge cap per SNAP use conditions and UL 60335-2-89
Supermarket systems, remote condensing units, cold storageGWP 150/300 from Jan 1, 2032Jan 1, 2032[2]R-290 qualifies, and the equipment listing governs where it can be used
Current federal GWP limits for new installs in each subsector, after the May 2026 reconsideration.

State

No state HFC rule restricts R-290, since state HFC programs target high-GWP substances. Building and mechanical codes govern flammable refrigerants, and adoption varies by jurisdiction. Verify with your local authority having jurisdiction before an install decision.

Buying R-290

R-290 is an exempt substitute under 40 CFR 82.154 in its listed end-uses, so the Section 608 sales restriction does not apply to it[3]. Sellers may still require credentials as store policy. Refrigerant-grade propane (higher purity, moisture-controlled) is not the same product as grill propane. Equipment warranties and listings specify refrigerant grade.

Safety and handling

A3 means higher flammability. R-290 belongs only in equipment designed and listed for it, with charge limits, spark-free components, and marked circuits. Never charge R-290 into a system built for an A1 refrigerant. Service work follows the manufacturer's procedures for flammable refrigerants, including ventilation and leak checks with tools rated for A3 service.

Replacements

R-290 is a destination, not a refrigerant that gets replaced. For loads too large for its charge limits, the low-GWP paths are CO2 for racks and large systems, and A2L blends such as R-454C and R-455A for field-piped equipment under the 2032 limits[2].

R-290 PT chart

Saturation pressures for R-290 from -40 °F to 150 °F, computed from reference equations of state[5]. Propane is a single compound, so liquid and vapor pressures are equal at a given temperature and there is no glide.

Full-page R-290PT chart →

Temp (°F)Liquid / bubble (psig)Vapor / dew (psig)
-401.41.4
-353.43.4
-305.75.7
-258.18.1
-2010.710.7
-1513.613.6
-1016.716.7
-520.120.1
023.723.7
527.627.6
1031.831.8
1536.336.3
2041.141.1
2546.346.3
3051.851.8
3557.757.7
4063.963.9
4570.670.6
5077.677.6
5585.185.1
6093.093.0
65101.4101.4
70110.2110.2
75119.5119.5
80129.3129.3
85139.7139.7
90150.5150.5
95161.9161.9
100173.9173.9
105186.5186.5
110199.6199.6
115213.4213.4
120227.8227.8
125242.9242.9
130258.7258.7
135275.1275.1
140292.3292.3
145310.2310.2
150328.9328.9

Use the vapor (dew) column to check superheat at the suction line. Use the liquid (bubble) column to check subcooling at the liquid line and for charging. R-290 has no glide, so one pressure column serves both charging and superheat checks. R-290 values are computed, not transcribed; see Sources.

Equipment rated for R-290

No walk-in unit cooler rates R-290 today, because the walk-in lines use A2L blends and CO2 for their low-GWP options. R-290 equipment in this market is mostly self-contained, and those models will be listed as their documentation is added.

Questions

Do I need a 608 certification to buy R-290?

No federal certification is required, because R-290 is an exempt substitute under 40 CFR 82.154 in its listed end-uses. Sellers may set their own policies. Handling it still requires training for flammable refrigerants.

Can I retrofit an R-404A system to R-290?

No. R-290 is A3 flammable and belongs only in equipment designed, listed, and marked for it. Retrofitting a non-listed system with propane violates the equipment listing and creates a fire hazard.

Is R-290 legal in walk-in coolers?

Federal GWP limits do not restrict it, and SNAP lists R-290 for specified end-uses with charge caps (89 FR 50410). Whether a given walk-in can use it depends on the equipment listing and local codes. Most walk-in unit cooler lines use A2L blends or CO2 instead.

Why is the R-290 charge limited?

Flammability. SNAP use conditions and UL 60335-2-89 cap the charge per circuit so a leak cannot form an ignitable volume in the space. Larger loads use multiple circuits or a different refrigerant.