Trenton TMP medium profile evaporators
TMP is Trenton Refrigeration's medium profile unit cooler line for walk-in coolers and freezers. Models span medium temperature (10 to 35 F evaporator temperature) and low temperature (-40 to 0 F) applications, with electric, air, hot gas, and reverse cycle defrost options, and EC fan motors with SmartSpeed technology.
Search TMP models
Image: Trenton Refrigeration
Nomenclature
Family
Medium profile evaporator
Fans
1 to 4
Nominal capacity x 1000
13 to 95 MBH (x 1000 BTU/h)
Temperature class
- MMedium Temp 6 FPI (10°F to 35°F Evap Temp)
- LLow Temp 6 FPI (-40°F to 0°F Evap Temp)
- VLow Temp 4 FPI (-40°F to 0°F Evap Temp)
Generation
- EA2L and A1 refrigerant compatible, AWEF Compliant†
Voltage
- S4460/1/60
- T3208-230/3/60
- T4460/3/60
- S2208-230/1/60*
Defrost
- AAir
- EElectric
- T3 pipe hot gas w/ electric heater pan†
- H3 pipe hot gas w/ hot gas loop pan
- GReverse Cycle w/ Electric Heater Pan
- RReverse Cycle w/ Hot Gas Loop Pan
† marks an option the other bulletin lists differently or not at all. * marks one this bulletin prints in its tables but leaves out of its legend.
Documentation history (2025 to 2026)
Generations D and E
The line is documented in two active generations. Generation D covers A1 refrigerants (R-404A, R-448A, R-449A, R-507, and related blends) and transcritical CO2, and is AWEF compliant. Generation E is the A2L generation: it adds the mildly flammable low-GWP refrigerants R-454A, R-454C, and R-455A that new refrigeration equipment is moving to in the U.S. low-GWP transition.
Generation E equipment carries the A2L safety package alongside the refrigerant change. The GEN E bulletin lists an A2L Refrigerant Detection System (RDS), a leak mitigation system built on safety shut off valves (SSOV) and check shut off valves (CSOV), and the ESP+ evaporator control as factory options. It also narrows the SmartSpeed EC motor statement to 230 V and 460 V models, a caveat the combined bulletin does not carry.
CO2 sits only on the generation D side of the documentation. The combined bulletin defines three CO2 application classes (C, D, and F) and two 575 V CO2 voltage codes (S5 and T5); the GEN E bulletin does not mention CO2 at all. Whether CO2 models continue past generation D is not something the current documentation answers.
TMP models
457 documented configurations, 13 to 95 MBH (x 1000 BTU/h).
Search TMP modelsBy capacity
Rated at 10 F TD on R-448A, the maker's leading condition.
By temperature class
Sources
- [1]
- [2]
Updated