TTM105LE-S2E
Trenton Refrigeration TTM evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 1 count | p.7 | |
| motor fla | 1 amps | p.7 | |
| motor watts | 60 watts | p.7 | |
| mca | 1.3 ampssources differ | TTM-GEN-E p.7 | |
| 8.4 ampssources differ | TTM-GEN-E p.7 | ||
| mop | 15 amps | p.7 | |
| total watts | 1540 watts | p.7 | |
| total amps | 6.7 amps | p.7 | |
| unclassified field | 15 | p.7 | |
| capacity | 5330 btu_h | td f: 10; evap temp f: 0; refrigerant: R454A/R454C/R455A | p.3 |
| 5170 btu_h | td f: 10; evap temp f: -10; refrigerant: R454A/R454C/R455A | p.3 | |
| 5040 btu_h | td f: 10; evap temp f: -20; refrigerant: R454A/R454C/R455A | p.3 | |
| 5330 btu_h | td f: 10; evap temp f: 0; refrigerant: R407A/R448A/R449A | p.5 | |
| 5170 btu_h | td f: 10; evap temp f: -10; refrigerant: R407A/R448A/R449A | p.5 | |
| 5040 btu_h | td f: 10; evap temp f: -20; refrigerant: R407A/R448A/R449A | p.5 | |
| 4340 btu_h | td f: 10; evap temp f: 0; refrigerant: R404A | p.5 | |
| 4200 btu_h | td f: 10; evap temp f: -10; refrigerant: R404A | p.5 | |
| 4100 btu_h | td f: 10; evap temp f: -20; refrigerant: R404A | p.5 | |
| airflow | 1070 cfm | p.3 | |
| 505 l_s | p.3 | ||
| refrigerant charge | 1.4 lb | refrigerant: R454A/R454C/R455A | p.3 |
| 0.6 kg | refrigerant: R454A/R454C/R455A | p.3 | |
| 1.4 lb | refrigerant: R407A/R448A/R449A | p.5 | |
| 0.6 kg | refrigerant: R407A/R448A/R449A | p.5 | |
| 1.3 lb | refrigerant: R404A | p.5 | |
| 0.6 kg | refrigerant: R404A | p.5 | |
| awef rating | 3.97 ratio | fpi: 6 | p.18 |
| dimension A | 45.5 inches | p.19 | |
| 1156 mm | p.19 | ||
| dimension B | 33 inches | p.19 | |
| 838 838 mm | p.19 | ||
| dimension unparsed | - - | p.19 | |
| dimension D | - inches | p.19 | |
| - mm | p.19 | ||
| dimension E | - inches | p.19 | |
| - mm | p.19 | ||
| suction od | 0.625 inches | p.20 | |
| 16 mm | p.20 | ||
| distributor inlet | 0.5 inches | p.20 | |
| 13 mm | p.20 | ||
| hot gas connection | 0.5 inches | p.20 | |
| 13 mm | p.20 | ||
| shipping weight | 54 lb | p.20 | |
| 24 kg | p.20 | ||
| liquid line od | 0.5 inches | p.30 | |
| 13 mm | p.30 | ||
| suction line od | 0.625 inches | p.30 | |
| 16 mm | p.30 | ||
| min room area | 23 ft2 | line length ft: 10 | p.30 |
| 38 ft2 | line length ft: 25 | p.30 | |
| 62 ft2 | line length ft: 50 | p.30 | |
| 112 ft2 | line length ft: 100 | p.30 | |
| 2 m2 | line length m: 3 | p.30 | |
| 4 m2 | line length m: 7.6 | p.30 | |
| 6 m2 | line length m: 15.2 | p.30 | |
| 10 m2 | line length m: 30.5 | p.30 | |
| voltage | 208 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TTM105LE-S2E | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 05 |
| capacity mbh | 5 |
| defrost | E |
| fan count | 1 |
| generation suffix | E |
| temp class | L |
| voltage | S2 |
Parts
9 factory parts for this unit: 9from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | L1✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E2V11order as E2V11FWBC0✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Solenoid valve | 3✓ | Solenoid valve | - | - | Check availability |
| TXV | SBQSE-A-ZPorder as SBQSE-A-ZP40✓ | evap temp f: -20, refrigerant: <as printed> | - | - | Check availability |
| TXV | SBQSE-AA-C✓ | evap temp f: 0, refrigerant: <as printed> | - | - | Check availability |
| TXV | SBQSE-AA-ZP✓ | evap temp f: -10, refrigerant: <as printed> | - | - | Check availability |
| TXV | SBQVE-A-ZPorder as SBQVE-A-ZP40✓ | evap temp f: -20, refrigerant: <as printed> | - | - | Check availability |
| TXV | SBQVE-AA-C✓ | evap temp f: 0, refrigerant: <as printed> | - | - | Check availability |
| TXV | SBQVE-AA-ZP✓ | evap temp f: -10, refrigerant: <as printed> | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KTM105LE-S2E | shared catalog stem ✓ |
| Bally | BTM105LE-S2E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TTM105LE-S2E?
TTM105LE-S2E has a rated capacity of 5330 btu_h. See the specifications table for rating conditions.
What voltage does TTM105LE-S2E require?
TTM105LE-S2E runs on 208 V supply power.