TMP495ME-S4E
Trenton Refrigeration TMP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 4 count | TMP + TMP-GEN-E p.3 ✓ | |
| capacity | 94800 btu_h | evap temp f: 25; refrigerant: R407A/R448A | p.3 |
| 93900 btu_h | evap temp f: 15; refrigerant: R407A/R448A | p.3 | |
| 92900 btu_h | evap temp f: 10; refrigerant: R407A/R448A | p.3 | |
| 77100 btu_h | evap temp f: 25; refrigerant: R404A | p.3 | |
| 76330 btu_h | evap temp f: 15; refrigerant: R404A | p.3 | |
| 75560 btu_h | evap temp f: 10; refrigerant: R404A | p.3 | |
| 94800 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.3 ✓ | |
| 93900 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.3 ✓ | |
| 92900 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.3 ✓ | |
| 94800 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 93900 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 92900 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 77100 btu_h | evap temp f: 25; refrigerant: R404A/R507 | p.6 | |
| 76330 btu_h | evap temp f: 15; refrigerant: R404A/R507 | p.6 | |
| 75560 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.6 | |
| airflow | 10780 cfm | refrigerant: R407A/R448A | p.3 |
| 5090 l_s | refrigerant: R407A/R448A | p.3 | |
| 10780 cfm | refrigerant: R404A | p.3 | |
| 5088 l_s | refrigerant: R404A | p.3 | |
| 10780 cfm | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.3 ✓ | |
| 5090 l_s | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.3 ✓ | |
| 10780 cfm | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 5090 l_s | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 10780 cfm | refrigerant: R404A/R507 | p.6 | |
| 5088 l_s | refrigerant: R404A/R507 | p.6 | |
| refrigerant charge | 9.1 lb | refrigerant: R407A | p.3 |
| 4.1 kg | refrigerant: R407A | p.3 | |
| 8.6 lb | refrigerant: R404A | p.3 | |
| 3.9 kg | refrigerant: R404A | p.3 | |
| 3.7 lbsources differ | refrigerant: R454A/R454C/R455A | TMP p.3 | |
| 8.2 lbsources differ | refrigerant: R454A/R454C/R455A | TMP-GEN-E p.3 | |
| 1.7 kgsources differ | refrigerant: R454A/R454C/R455A | TMP p.3 | |
| 3.7 kgsources differ | refrigerant: R454A/R454C/R455A | TMP-GEN-E p.3 | |
| 8.7 lb | refrigerant: R448A | p.3 | |
| 3.9 kg | refrigerant: R448A | p.3 | |
| 9.1 lb | refrigerant: R407A/R407C | p.5 | |
| 4.1 kg | refrigerant: R407A/R407C | p.5 | |
| 8.6 lb | refrigerant: R404A/R507 | p.6 | |
| 3.9 kg | refrigerant: R404A/R507 | p.6 | |
| 8.7 lb | refrigerant: R448A/R449A | p.5 | |
| 3.9 kg | refrigerant: R448A/R449A | p.5 | |
| awef rating | 9 ratio | refrigerant: R404A/R507 | p.33 ✓ |
| 9 ratio | refrigerant: R407A | p.33 | |
| 9 ratio | refrigerant: R448A/R449A | p.33 | |
| 9 ratio | refrigerant: R454A | p.33 | |
| 9 ratio | refrigerant: R454C | p.33 | |
| 9 ratio | refrigerant: R455A | p.33 | |
| 9 ratio | fpi: 6 | p.31 | |
| suction od | 1 5/8 inches | TMP + TMP-GEN-E p.35 ✓ | |
| distributor inlet | 1 1/8 inchessources differ | TMP p.35 | |
| 1 3/8 inchessources differ | TMP p.35 | ||
| 1 1/8 inchessources differ | TMP-GEN-E p.33 | ||
| 1 3/8 inchessources differ | TMP-GEN-E p.34 | ||
| hot gas connection | 0.875 inchessources differ | TMP p.35 | |
| 1 3/8 inchessources differ | TMP p.35 | ||
| shipping weight | 460 lb | TMP + TMP-GEN-E p.36 ✓ | |
| 209 kg | TMP + TMP-GEN-E p.36 ✓ | ||
| fpi | 6 | p.11 | |
| mca | 28.6 ampssources differ | TMP p.11 | |
| 16 ampssources differ | TMP-GEN-E p.12 | ||
| 29 ampssources differ | TMP-GEN-E p.12 | ||
| esp circuit 460 1 60 mop a | 30 | TMP + TMP-GEN-E p.11 ✓ | |
| voltage | 460 V | TMP + TMP-GEN-E p.? ✓ | |
| phase | 1 ph | TMP + TMP-GEN-E p.? ✓ | |
| frequency | 60 Hz | TMP + TMP-GEN-E p.? ✓ | |
| side port connection | 0.875 inches | p.34 | |
| drain pan loop conn od sweat | 1 3/8 | p.34 | |
| r454a sporlan sbqte b c | EBSTE-11-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| r448a r449a r407a r407c r454c r455a sporlan sbqve b c | EBSVE-11-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| r404a r507 sporlan sbqse b c | EBSSE-10-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| liquid line od | 0.625 inches | p.46 | |
| suction line od | 1 5/8 inches | p.46 | |
| maximum line length 10 ft minimum room area ft2 | 118 | p.46 | |
| maximum line length 25 ft | 144 | p.46 | |
| maximum line length 50 ft | 188 | p.46 | |
| maximum line length 100 ft | 275 | p.46 | |
| motor hp | 0.3333333333333333 hp | p.12 | |
| motor fla | 6.4 amps | p.12 | |
| motor watts | 840 watts | p.12 | |
| mop | 20 amps | p.12 | |
| total watts | 10600 watts | p.12 | |
| total amps | 23 amps | p.12 | |
| defrost heaters 460 1 60 mop a | 30 | p.12 | |
| esp circuit mca | 28.6 amps | p.17 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TMP495ME-S4E | 460/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 95 |
| capacity mbh | 95 |
| defrost | E |
| fan count | 4 |
| generation suffix | E |
| temp class | M |
| voltage | S4 |
Parts
7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | E12✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V55order as E3V55BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV13order as CSOV-13S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV19✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B10order as B10S2-5/8✓ | Solenoid valve; Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| TXV | EBSSE-10-C✓ | refrigerant: R404A/R507 | - | - | Check availability |
| TXV | EBSVE-11-C✓ | refrigerant: R407A/R407C/R448A/R449A | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KMP495ME-S4E | shared catalog stem ✓ |
| Bally | BMP495ME-S4E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TMP495ME-S4E?
TMP495ME-S4E has a rated capacity of 94800 btu_h. See the specifications table for rating conditions.
What voltage does TMP495ME-S4E require?
TMP495ME-S4E runs on 460 V supply power.
Related models in TMP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.