TMP457VE-T4E
Trenton Refrigeration TMP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 4 count | TMP + TMP-GEN-E p.5 ✓ | |
| capacity | 60600 btu_h | evap temp f: 0; refrigerant: R407A/R448A | p.5 |
| 58900 btu_h | evap temp f: 10; refrigerant: R407A/R448A | p.5 | |
| 57200 btu_h | evap temp f: 20; refrigerant: R407A/R448A | p.5 | |
| 52600 btu_h | evap temp f: 30; refrigerant: R407A/R448A | p.5 | |
| 48600 btu_h | evap temp f: 40; refrigerant: R407A/R448A | p.5 | |
| 49300 btu_h | evap temp f: 0; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 47900 btu_h | evap temp f: 10; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 46500 btu_h | evap temp f: 20; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 42800 btu_h | evap temp f: 30; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 39500 btu_h | evap temp f: 40; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 60600 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 58900 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 57200 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 52600 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 48600 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 60600 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | p.6 | |
| 58900 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | p.6 | |
| 57200 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | p.6 | |
| 52600 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | p.6 | |
| 48600 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | p.6 | |
| airflow | 12100 cfm | refrigerant: R407A/R448A | p.5 |
| 5710 l_s | refrigerant: R407A/R448A | p.5 | |
| 12100 cfm | refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 5710 l_s | refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 12100 cfm | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 5710 l_s | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 12100 cfm | refrigerant: R407A/R448A/R449A | p.6 | |
| 5710 l_s | refrigerant: R407A/R448A/R449A | p.6 | |
| refrigerant charge | 8.7 lbsources differ | refrigerant: R407A | TMP p.5 |
| 9 lbsources differ | refrigerant: R407A | TMP-GEN-E p.6 | |
| 4 kgsources differ | refrigerant: R407A | TMP p.5 | |
| 4.1 kgsources differ | refrigerant: R407A | TMP-GEN-E p.6 | |
| 8.1 lbsources differ | refrigerant: R404A | TMP p.5 | |
| 16.6 lbsources differ | refrigerant: R404A | TMP-GEN-E p.7 | |
| 3.7 kgsources differ | refrigerant: R404A | TMP p.5 | |
| 7.5 kgsources differ | refrigerant: R404A | TMP-GEN-E p.7 | |
| 7.8 lbsources differ | refrigerant: R454A/R454C/R455A | TMP p.5 | |
| 7.9 lbsources differ | refrigerant: R454A/R454C/R455A | TMP-GEN-E p.4 | |
| 3.5 kgsources differ | refrigerant: R454A/R454C/R455A | TMP p.5 | |
| 3.6 kgsources differ | refrigerant: R454A/R454C/R455A | TMP-GEN-E p.4 | |
| 8.4 lb | refrigerant: R448A | p.5 | |
| 3.8 kg | refrigerant: R448A | p.5 | |
| 8.6 lb | refrigerant: R448A/R449A | p.6 | |
| 3.9 kg | refrigerant: R448A/R449A | p.6 | |
| awef rating | 4.15 ratio | refrigerant: R404A/R507 | p.33 ✓ |
| 4.15 ratio | refrigerant: R407A | p.33 | |
| 4.15 ratio | refrigerant: R448A/R449A | p.33 | |
| 4.15 ratio | refrigerant: R454A | p.33 | |
| 4.15 ratio | refrigerant: R454C | p.33 | |
| 4.15 ratio | refrigerant: R455A | p.33 | |
| 4.15 ratio | fpi: 4 | p.31 | |
| hot gas connection | 4 inchessources differ | TMP p.35 | |
| 1 1/8 inchessources differ | TMP p.35 | ||
| 1 3/8 inchessources differ | TMP p.35 | ||
| suction od | 1 5/8 inches | TMP + TMP-GEN-E p.35 ✓ | |
| distributor inlet | 1 5/8 inchessources differ | TMP p.35 | |
| 1 3/8 inchessources differ | TMP p.35 | ||
| 1 5/8 inchessources differ | TMP-GEN-E p.33 | ||
| shipping weight | 425 lb | TMP + TMP-GEN-E p.36 ✓ | |
| 193 kg | TMP + TMP-GEN-E p.36 ✓ | ||
| mca | 19.5 ampssources differ | TMP p.11 | |
| 16 ampssources differ | TMP-GEN-E p.13 | ||
| 19 ampssources differ | TMP-GEN-E p.13 | ||
| esp circuit 460 3 60 mop a | 20 | TMP + TMP-GEN-E p.11 ✓ | |
| voltage | 460 V | TMP + TMP-GEN-E p.? ✓ | |
| phase | 3 ph | TMP + TMP-GEN-E p.? ✓ | |
| frequency | 60 Hz | TMP + TMP-GEN-E p.? ✓ | |
| side port connection | 1 1/8 inches | p.34 | |
| drain pan loop conn od sweat | 1 3/8 | p.34 | |
| r454a sporlan sbqte b zp | EBSTE-11-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| r448a r449a r407a r407c r454c r455a sporlan sbqve b zp | EBSVE-11-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| r404a r507 sporlan sbqse b zp | EBSSE-10-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| liquid line od | 0.875 inches | p.46 | |
| suction line od | 1 5/8 inches | p.46 | |
| maximum line length 10 ft minimum room area ft2 | 129 | p.46 | |
| maximum line length 25 ft | 176 | p.46 | |
| maximum line length 50 ft | 256 | p.46 | |
| maximum line length 100 ft | 415 | p.46 | |
| motor hp | 0.3333333333333333 hp | p.13 | |
| motor fla | 6.4 amps | p.13 | |
| motor watts | 840 watts | p.13 | |
| mop | 20 amps | p.13 | |
| total watts | 10600 watts | p.13 | |
| total amps | 15.6 amps | p.13 | |
| defrost heaters 460 3 60 mop a | 20 | p.13 | |
| esp circuit mca | 19.5 amps | p.17 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TMP457VE-T4E | 460/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 57 |
| capacity mbh | 57 |
| defrost | E |
| fan count | 4 |
| generation suffix | E |
| temp class | V |
| voltage | T4 |
Parts
7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | A12✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V45order as E3V45BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV13order as CSOV-13S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV19✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B9order as B9S2✓ | Solenoid valve; Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| TXV | EBSSE-10-ZP✓ | refrigerant: R404A/R507 | - | - | Check availability |
| TXV | EBSVE-11-ZPorder as EBSVE-11-ZP40✓ | refrigerant: R448A/R449A/R407A | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KMP457VE-T4E | shared catalog stem ✓ |
| Bally | BMP457VE-T4E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TMP457VE-T4E?
TMP457VE-T4E has a rated capacity of 60600 btu_h. See the specifications table for rating conditions.
What voltage does TMP457VE-T4E require?
TMP457VE-T4E runs on 460 V supply power.
Related models in TMP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.