TMP248ME-T4D

Trenton Refrigeration TMP medium profile evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
fan qty2 countp.3
capacity47500 btu_hp.3
47000 btu_hp.3
46600 btu_hp.3
38600 btu_hp.3
38210 btu_hp.3
37830 btu_hp.3
47500 btu_hp.3
47000 btu_hp.3
46600 btu_hp.3
airflow5730 cfmp.3
2700 l_sp.3
5730 cfmp.3
2704 l_sp.3
5730 cfmp.3
2700 l_sp.3
refrigerant charge5.4 lbp.3
2.5 kgp.3
5.1 lbp.3
2.3 kgp.3
2.2 lbp.3
1 kgp.3
5.2 lbp.3
2.4 kgp.3
awef rating9 ratiop.33
9 ratiop.33
9 ratiop.33
9 ratiop.33
9 ratiop.33
9 ratiop.33
suction od1 3/8 inchesp.35
distributor inlet1 1/8 inchessources differTMP p.35
0.875 inchessources differTMP p.35
hot gas connection0.625 inchessources differTMP p.35
0.875 inchessources differTMP p.35
shipping weight270 lbp.36
123 kgp.36
motor hp0.3333333333333333 hpp.8
motor fla3.2 ampsp.8
total watts420 wattssources differTMP p.8
6190 wattssources differTMP p.8
mca15 ampssources differTMP p.8
11 ampssources differTMP p.8
11.5 ampssources differTMP p.11
mop15 ampsp.8
total amps9.2 ampsp.8
defrost heaters mop a15p.8
esp circuit 460 3 60 mop a15p.11
voltage 208 230 1 60460/3/60p.66
1 x evaporator defrost kit dfk 10DFK-14p.66
1 x evaporator fuse package fp 015FP-041p.66
2 x evaporator defrost kit dfk 12DFK-18p.66
2 x evaporator fuse package fp 116FP-042p.66
voltage460 Vp.?
phase3 php.?
frequency60 Hzp.?

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TMP_1109295, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
TMP248ME-T4D460/3/60Check availability

Nomenclature

Position / meaningValue
capacity code48
capacity mbh48
defrostE
fan count2
generation suffixD
temp classM
voltageT4

Parts

7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.

PartPart numberQtyListAvailability
Distributor nozzleE4--Check availability
Electronic expansion valveE3V45order as E3V45BWRC1--Check availability
Safety check valveCSOV11order as CSOV-11S--Check availability
Safety shutoff solenoidSSOV10--Check availability
Solenoid valveB9order as B9S2--Check availability
TXVEBSPE-6-C--Check availability
TXVERVE-6-C--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKMP248ME-T4Dshared catalog stem
BallyBMP248ME-T4Dshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TMP248ME-T4D?

TMP248ME-T4D has a rated capacity of 47500 btu_h. See the specifications table for rating conditions.

What voltage does TMP248ME-T4D require?

TMP248ME-T4D runs on 460 V supply power.

Related models in TMP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.