TMP240ME-S4E

Trenton Refrigeration TMP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
fan qty2 countTMP + TMP-GEN-E p.3
capacity40000 btu_hp.3
39600 btu_hp.3
39200 btu_hp.3
32500 btu_hp.3
32180 btu_hp.3
31850 btu_hp.3
40000 btu_hTMP + TMP-GEN-E p.3
39600 btu_hTMP + TMP-GEN-E p.3
39200 btu_hTMP + TMP-GEN-E p.3
40000 btu_hp.5
39600 btu_hp.5
39200 btu_hp.5
32500 btu_hp.6
32180 btu_hp.6
31850 btu_hp.6
airflow6070 cfmp.3
2870 l_sp.3
6070 cfmp.3
2865 l_sp.3
6070 cfmTMP + TMP-GEN-E p.3
2870 l_sTMP + TMP-GEN-E p.3
6070 cfmp.5
2870 l_sp.5
6070 cfmp.6
2865 l_sp.6
refrigerant charge4.4 lbp.3
2 kgp.3
4.1 lbp.3
1.9 kgp.3
1.8 lbsources differTMP p.3
4 lbsources differTMP-GEN-E p.3
0.8 kgsources differTMP p.3
1.8 kgsources differTMP-GEN-E p.3
4.2 lbp.3
1.9 kgp.3
4.4 lbp.5
2 kgp.5
4.1 lbp.6
1.9 kgp.6
4.2 lbp.5
1.9 kgp.5
awef rating9 ratiop.33
9 ratiop.33
9 ratiop.33
9 ratiop.33
9 ratiop.33
9 ratiop.33
9 ratiop.31
suction od1 3/8 inchesTMP + TMP-GEN-E p.35
distributor inlet0.875 inchesTMP + TMP-GEN-E p.35
hot gas connection0.625 inchessources differTMP p.35
0.5 inchessources differTMP p.35
0.875 inchessources differTMP p.35
shipping weight257 lbTMP + TMP-GEN-E p.36
117 kgTMP + TMP-GEN-E p.36
mca16.8 ampssources differTMP p.11
15 ampssources differTMP-GEN-E p.12
17 ampssources differTMP-GEN-E p.12
esp circuit 460 1 60 mop a20TMP + TMP-GEN-E p.11
voltage460 VTMP + TMP-GEN-E p.?
phase1 phTMP + TMP-GEN-E p.?
frequency60 HzTMP + TMP-GEN-E p.?
side port connection0.625 inchesp.34
drain pan loop conn od sweat0.875p.34
r454a sporlan sbqte b cSBQTE-C-Cp.37
r448a r449a r407a r407c r454c r455a sporlan sbqve b cSBQVE-C-Cp.37
r404a r507 sporlan sbqse b cERPE-4-Cp.37
liquid line od0.5 inchesp.46
suction line od1 3/8 inchesp.46
maximum line length 10 ft minimum room area ft260p.46
maximum line length 25 ft77p.46
maximum line length 50 ft105p.46
maximum line length 100 ft160p.46
motor hp0.3333333333333333 hpp.12
motor fla3.2 ampsp.12
motor watts420 wattsp.12
mop15 ampsp.12
total watts6190 wattsp.12
total amps13.5 ampsp.12
defrost heaters 460 1 60 mop a20p.12
esp circuit mca16.8 ampsp.17

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TMP_1109295, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TMP-GEN-E_1112922, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
TMP240ME-S4E460/1/60Check availability

Nomenclature

Position / meaningValue
capacity code40
capacity mbh40
defrostE
fan count2
generation suffixE
temp classM
voltageS4

Parts

8 factory parts for this unit: 8from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.

PartPart numberQtyListAvailability
Distributor nozzleG3--Check availability
Distributor nozzleG4--Check availability
Electronic expansion valveE2V35order as E2V35FSMC0--Check availability
Safety check valveCSOV11order as CSOV-11S--Check availability
Safety shutoff solenoidSSOV6--Check availability
Solenoid valveB6order as B6S1--Check availability
TXVERPE-4-C--Check availability
TXVSBQVE-C-C--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKMP240ME-S4Eshared catalog stem
BallyBMP240ME-S4Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TMP240ME-S4E?

TMP240ME-S4E has a rated capacity of 40000 btu_h. See the specifications table for rating conditions.

What voltage does TMP240ME-S4E require?

TMP240ME-S4E runs on 460 V supply power.

Related models in TMP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.