TMP226VE-S2E
Trenton Refrigeration TMP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 2 count | TMP + TMP-GEN-E p.5 ✓ | |
| capacity | 27700 btu_h | evap temp f: 0; refrigerant: R407A/R448A | p.5 |
| 26900 btu_h | evap temp f: 10; refrigerant: R407A/R448A | p.5 | |
| 26100 btu_h | evap temp f: 20; refrigerant: R407A/R448A | p.5 | |
| 24000 btu_h | evap temp f: 30; refrigerant: R407A/R448A | p.5 | |
| 22200 btu_h | evap temp f: 40; refrigerant: R407A/R448A | p.5 | |
| 22600 btu_h | evap temp f: 0; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 21900 btu_h | evap temp f: 10; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 21300 btu_h | evap temp f: 20; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 19600 btu_h | evap temp f: 30; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 18100 btu_h | evap temp f: 40; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 27700 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 58900 btu_hsources differ | evap temp f: 10; refrigerant: R454A/R454C/R455A | TMP p.5 | |
| 26900 btu_hsources differ | evap temp f: 10; refrigerant: R454A/R454C/R455A | TMP-GEN-E p.4 | |
| 26100 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 24000 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 22200 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 27700 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | p.6 | |
| 26900 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | p.6 | |
| 26100 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | p.6 | |
| 24000 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | p.6 | |
| 22200 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | p.6 | |
| airflow | 6430 cfm | refrigerant: R407A/R448A | p.5 |
| 3030 l_s | refrigerant: R407A/R448A | p.5 | |
| 6430 cfm | refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 3030 l_s | refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 6430 cfm | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 3030 l_s | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 6430 cfm | refrigerant: R407A/R448A/R449A | p.6 | |
| 3030 l_s | refrigerant: R407A/R448A/R449A | p.6 | |
| refrigerant charge | 4.2 lb | refrigerant: R407A | TMP + TMP-GEN-E p.5 ✓ |
| 1.9 kg | refrigerant: R407A | TMP + TMP-GEN-E p.5 ✓ | |
| 3.9 lbsources differ | refrigerant: R404A | TMP p.5 | |
| 7.1 lbsources differ | refrigerant: R404A | TMP-GEN-E p.7 | |
| 1.8 kgsources differ | refrigerant: R404A | TMP p.5 | |
| 3.2 kgsources differ | refrigerant: R404A | TMP-GEN-E p.7 | |
| 3.6 lbsources differ | refrigerant: R454A/R454C/R455A | TMP p.5 | |
| 3.8 lbsources differ | refrigerant: R454A/R454C/R455A | TMP-GEN-E p.4 | |
| 1.6 kgsources differ | refrigerant: R454A/R454C/R455A | TMP p.5 | |
| 1.7 kgsources differ | refrigerant: R454A/R454C/R455A | TMP-GEN-E p.4 | |
| 4 lb | refrigerant: R448A | p.5 | |
| 1.8 kg | refrigerant: R448A | p.5 | |
| 4 lb | refrigerant: R448A/R449A | p.6 | |
| 1.8 kg | refrigerant: R448A/R449A | p.6 | |
| awef rating | 4.15 ratio | refrigerant: R404A/R507 | p.33 ✓ |
| 4.15 ratio | refrigerant: R407A | p.33 | |
| 4.15 ratio | refrigerant: R448A/R449A | p.33 | |
| 4.15 ratio | refrigerant: R454A | p.33 | |
| 4.15 ratio | refrigerant: R454C | p.33 | |
| 4.15 ratio | refrigerant: R455A | p.33 | |
| 4.15 ratio | fpi: 4 | p.31 | |
| suction od | 1 3/8 inches | TMP + TMP-GEN-E p.35 ✓ | |
| distributor inlet | 1 1/8 inchessources differ | TMP p.35 | |
| 0.875 inchessources differ | TMP p.35 | ||
| 1 1/8 inchessources differ | TMP-GEN-E p.34 | ||
| hot gas connection | 0.625 inchessources differ | TMP p.35 | |
| 0.875 inchessources differ | TMP p.35 | ||
| shipping weight | 250 lb | TMP + TMP-GEN-E p.36 ✓ | |
| 114 kg | TMP + TMP-GEN-E p.36 ✓ | ||
| mca | 33.6 ampssources differ | TMP p.10 | |
| 16 ampssources differ | TMP-GEN-E p.10 | ||
| 34 ampssources differ | TMP-GEN-E p.10 | ||
| esp circuit 1 208 230 1 60 mop a | 35 | p.10 | |
| voltage | 208 V | TMP + TMP-GEN-E p.? ✓ | |
| phase | 1 ph | TMP + TMP-GEN-E p.? ✓ | |
| frequency | 60 Hz | TMP + TMP-GEN-E p.? ✓ | |
| side port connection | 0.625 inches | p.34 | |
| drain pan loop conn od sweat | 0.875 | p.34 | |
| r454a sporlan sbqte b zp | SBQTE-C-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| r448a r449a r407a r407c r454c r455a sporlan sbqve b zp | SBQVE-C-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| r404a r507 sporlan sbqse b zp | SBQSE-C-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| liquid line od | 0.375 inches | p.46 | |
| suction line od | 1 3/8 inches | p.46 | |
| maximum line length 10 ft minimum room area ft2 | 53 | p.46 | |
| maximum line length 25 ft | 61 | p.46 | |
| maximum line length 50 ft | 76 | p.46 | |
| maximum line length 100 ft | 104 | p.46 | |
| motor hp | 0.25 hp | p.10 | |
| motor fla | 4.4 amps | p.10 | |
| motor watts | 420 watts | p.10 | |
| mop | 20 amps | p.10 | |
| total watts | 6190 watts | p.10 | |
| total amps | 26.9 amps | p.10 | |
| defrost heaters 208 230 1 60 mop a | 35 | p.10 | |
| esp circuit mca | 33.6 amps | p.16 | |
| esp circuit 208 230 1 60 mop a | 35 | p.16 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TMP226VE-S2E | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 26 |
| capacity mbh | 26 |
| defrost | E |
| fan count | 2 |
| generation suffix | E |
| temp class | V |
| voltage | S2 |
Parts
7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Nozzle / solenoid valve | E5order as E5S130✓ | Distributor nozzle; Solenoid valve; Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E2V24order as E2V24FWBC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV11order as CSOV-11S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV10✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B6order as B6S1✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| TXV | SBQSE-C-ZPorder as SBQSE-C-ZP40✓ | refrigerant: R404A/R507 | - | - | Check availability |
| TXV | SBQVE-C-ZPorder as SBQVE-C-ZP40✓ | refrigerant: R448A/R449A/R407A | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KMP226VE-S2E | shared catalog stem ✓ |
| Bally | BMP226VE-S2E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TMP226VE-S2E?
TMP226VE-S2E has a rated capacity of 27700 btu_h. See the specifications table for rating conditions.
What voltage does TMP226VE-S2E require?
TMP226VE-S2E runs on 208 V supply power.
Related models in TMP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.