TMP116LE-T3E
Trenton Refrigeration TMP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 1 count | TMP + TMP-GEN-E p.4 ✓ | |
| capacity | 16700 btu_h | evap temp f: 0; refrigerant: R407A/R448A | p.4 |
| 16300 btu_h | evap temp f: 10; refrigerant: R407A/R448A | p.4 | |
| 15800 btu_h | evap temp f: 20; refrigerant: R407A/R448A | p.4 | |
| 14500 btu_h | evap temp f: 30; refrigerant: R407A/R448A | p.4 | |
| 13400 btu_h | evap temp f: 40; refrigerant: R407A/R448A | p.4 | |
| 13600 btu_h | evap temp f: 0; refrigerant: R404A | TMP + TMP-GEN-E p.4 ✓ | |
| 13200 btu_h | evap temp f: 10; refrigerant: R404A | TMP + TMP-GEN-E p.4 ✓ | |
| 12800 btu_h | evap temp f: 20; refrigerant: R404A | TMP + TMP-GEN-E p.4 ✓ | |
| 11800 btu_h | evap temp f: 30; refrigerant: R404A | TMP + TMP-GEN-E p.4 ✓ | |
| 10900 btu_h | evap temp f: 40; refrigerant: R404A | TMP + TMP-GEN-E p.4 ✓ | |
| 16700 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.4 ✓ | |
| 16300 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.4 ✓ | |
| 15800 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.4 ✓ | |
| 14500 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.4 ✓ | |
| 13400 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.4 ✓ | |
| 16700 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | p.5 | |
| 16300 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | p.5 | |
| 15800 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | p.5 | |
| 14500 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | p.5 | |
| 13400 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | p.5 | |
| airflow | 3030 cfm | refrigerant: R407A/R448A | p.4 |
| 1430 l_s | refrigerant: R407A/R448A | p.4 | |
| 3030 cfm | refrigerant: R404A | TMP + TMP-GEN-E p.4 ✓ | |
| 1430 l_s | refrigerant: R404A | TMP + TMP-GEN-E p.4 ✓ | |
| 3030 cfm | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.4 ✓ | |
| 1430 l_s | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.4 ✓ | |
| 3030 cfm | refrigerant: R407A/R448A/R449A | p.5 | |
| 1430 l_s | refrigerant: R407A/R448A/R449A | p.5 | |
| refrigerant charge | 2.5 lb | refrigerant: R407A | TMP + TMP-GEN-E p.4 ✓ |
| 1.1 kg | refrigerant: R407A | TMP + TMP-GEN-E p.4 ✓ | |
| 2.3 lb | refrigerant: R404A | TMP + TMP-GEN-E p.4 ✓ | |
| 1 kg | refrigerant: R404A | TMP + TMP-GEN-E p.4 ✓ | |
| 1.3 lbsources differ | refrigerant: R454A/R454C/R455A | TMP p.4 | |
| 2.2 lbsources differ | refrigerant: R454A/R454C/R455A | TMP-GEN-E p.3 | |
| 0.6 kgsources differ | refrigerant: R454A/R454C/R455A | TMP p.4 | |
| 1 kgsources differ | refrigerant: R454A/R454C/R455A | TMP-GEN-E p.3 | |
| 2.4 lb | refrigerant: R448A | p.4 | |
| 1.1 kg | refrigerant: R448A | p.4 | |
| 2.4 lb | refrigerant: R448A/R449A | p.5 | |
| 1.1 kg | refrigerant: R448A/R449A | p.5 | |
| awef rating | 4.09 ratio | refrigerant: R404A/R507 | p.33 ✓ |
| 4.09 ratio | refrigerant: R407A | p.33 | |
| 4.09 ratio | refrigerant: R448A/R449A | p.33 | |
| 4.09 ratio | refrigerant: R454A | p.33 | |
| 4.09 ratio | refrigerant: R454C | p.33 | |
| 4.09 ratio | refrigerant: R455A | p.33 | |
| 4.09 ratio | fpi: 6 | p.31 | |
| hot gas connection | 1 inchessources differ | TMP p.35 | |
| 0.5 inchessources differ | TMP p.35 | ||
| 0.875 inchessources differ | TMP p.35 | ||
| suction od | 1 1/8 inches | TMP + TMP-GEN-E p.35 ✓ | |
| distributor inlet | 0.875 inches | TMP + TMP-GEN-E p.35 ✓ | |
| shipping weight | 164 lb | TMP + TMP-GEN-E p.36 ✓ | |
| 74 kg | TMP + TMP-GEN-E p.36 ✓ | ||
| fpi | 6 | TMP + TMP-GEN-E p.10 ✓ | |
| mca | 12.4 ampssources differ | TMP p.10 | |
| 15 ampssources differ | TMP-GEN-E p.11 | ||
| 12 ampssources differ | TMP-GEN-E p.11 | ||
| esp circuit 208 230 3 60 mop a | 15 | TMP + TMP-GEN-E p.10 ✓ | |
| voltage | 208 V | TMP + TMP-GEN-E p.? ✓ | |
| phase | 3 ph | TMP + TMP-GEN-E p.? ✓ | |
| frequency | 60 Hz | TMP + TMP-GEN-E p.? ✓ | |
| side port connection | 0.5 inches | p.34 | |
| drain pan loop conn od sweat | 0.875 | p.34 | |
| liquid line od | 0.375 inches | p.46 | |
| suction line od | 1 1/8 inches | p.46 | |
| maximum line length 10 ft minimum room area ft2 | 33 | p.46 | |
| maximum line length 25 ft | 42 | p.46 | |
| maximum line length 50 ft | 55 | p.46 | |
| maximum line length 100 ft | 82 | p.46 | |
| motor hp | 0.25 hp | p.11 | |
| motor fla | 2.2 amps | p.11 | |
| motor watts | 210 watts | p.11 | |
| mop | 15 amps | p.11 | |
| total watts | 3330 watts | p.11 | |
| total amps | 9.9 amps | p.11 | |
| defrost heaters 208 230 3 60 mop a | 15 | p.11 | |
| esp circuit mca | 12.4 amps | p.16 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TMP116LE-T3E | 208-230/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 16 |
| capacity mbh | 16 |
| defrost | E |
| fan count | 1 |
| generation suffix | E |
| temp class | L |
| voltage | T3 |
Parts
7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | G2-1/2✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E2V24order as E2V24FWBC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV9order as CSOV-9S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV6✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | E5order as E5S130✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| TXV | SBQSE-B-ZPorder as SBQSE-B-ZP40✓ | refrigerant: R404A/R507 | - | - | Check availability |
| TXV | SBQVE-B-ZPorder as SBQVE-B-ZP40✓ | refrigerant: R448A/R449A/R407A | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KMP116LE-T3E | shared catalog stem ✓ |
| Bally | BMP116LE-T3E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TMP116LE-T3E?
TMP116LE-T3E has a rated capacity of 16700 btu_h. See the specifications table for rating conditions.
What voltage does TMP116LE-T3E require?
TMP116LE-T3E runs on 208 V supply power.