| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 1 count | p.4 | |
| 1 count | p.4 | ||
| 1 count | p.4 | ||
| 1 count | p.35 | ||
| 1 count | p.7 | ||
| capacity | 16700 btu_h | evap temp f: 0 | p.4 |
| 16300 btu_h | evap temp f: 10 | p.4 | |
| 15800 btu_h | evap temp f: 20 | p.4 | |
| 14500 btu_h | evap temp f: 30 | p.4 | |
| 13400 btu_h | evap temp f: 40 | p.4 | |
| 13600 btu_h | evap temp f: 0 | p.4 | |
| 13200 btu_h | evap temp f: 10 | p.4 | |
| 12800 btu_h | evap temp f: 20 | p.4 | |
| 11800 btu_h | evap temp f: 30 | p.4 | |
| 10900 btu_h | evap temp f: 40 | p.4 | |
| 16700 btu_h | evap temp f: 0 | p.4 | |
| 16300 btu_h | evap temp f: 10 | p.4 | |
| 15800 btu_h | evap temp f: 20 | p.4 | |
| 14500 btu_h | evap temp f: 30 | p.4 | |
| 13400 btu_h | evap temp f: 40 | p.4 | |
| airflow | 3030 cfm | p.4 | |
| 1430 l_s | p.4 | ||
| 3030 cfm | p.4 | ||
| 1430 l_s | p.4 | ||
| 3030 cfm | p.4 | ||
| 1430 l_s | p.4 | ||
| refrigerant charge | 2.5 lb | p.4 | |
| 1.1 kg | p.4 | ||
| 2.3 lb | p.4 | ||
| 1 kg | p.4 | ||
| 1.3 lb | p.4 | ||
| 0.6 kg | p.4 | ||
| r404a r507 | 4.09 | p.33 | |
| awef rating | 4.09 ratio | refrigerant: R407A | p.33 |
| 4.09 ratio | refrigerant: R454A | p.33 | |
| 4.09 ratio | refrigerant: R454C | p.33 | |
| 4.09 ratio | refrigerant: R455A | p.33 | |
| r448a r449a | 4.09 | p.33 | |
| hot gas connection | 1 inches | p.35 | |
| 0.5 inches | p.35 | ||
| 0.5 inches | p.35 | ||
| 0.875 inches | p.35 | ||
| suction od | 1 1/8 inches | p.35 | |
| 1 1/8 inches | p.35 | ||
| distributor inlet | 0.875 inches | p.35 | |
| 0.875 inches | p.35 | ||
| 0.875 inches | p.35 | ||
| txv model | SBQSE-B-ZP part_number | refrigerant: R404A/R507 | p.37 |
| SBQVE-B-ZP part_number | refrigerant: R448A/R449A/R407A | p.37 | |
| shipping weight | 164 lb | p.36 | |
| 74 kg | p.36 | ||
| distributor nozzle | G2-1/2 part_id | p.38 | |
| G2-1/2 part_id | p.40 | ||
| G2-1/2 part_id | p.40 | ||
| electronic expansion valve | E2V24 part_number | p.40 | |
| E2V24 part_number | p.40 | ||
| solenoid valve | E5 part_number | p.40 | |
| E5 part_number | p.40 | ||
| safety solenoid valve | SSOV6 part_number | p.40 | |
| SSOV6 part_number | p.40 | ||
| safety check valve | CSOV9 part_number | p.40 | |
| CSOV9 part_number | p.40 | ||
| fpi | 6 | p.7 | |
| 6 | p.10 | ||
| motor hp | 0.25 hp | p.7 | |
| motor fla | 2.2 amps | p.7 | |
| total watts | 210 watts | p.7 | |
| 3330 watts | p.7 | ||
| mca | 15 amps | p.7 | |
| 12 amps | p.7 | ||
| 12.4 amps | p.10 | ||
| fan motors standard ec motors mop a | 20 | p.7 | |
| total amps | 9.9 amps | p.7 | |
| defrost heaters mop a | 15 | p.7 | |
| esp circuit 208 230 3 60 mop a | 15 | p.10 | |
| voltage 208 230 1 60 | 208-230/3/60 | p.66 | |
| 1 x evaporator defrost kit dfk 10 | DFK-14 | p.66 | |
| 1 x evaporator fuse package fp 015 | FP-110 | p.66 | |
| 2 x evaporator defrost kit dfk 12 | DFK-18 | p.66 | |
| 2 x evaporator fuse package fp 116 | FP-121 | p.66 | |
| voltage | 208 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: TMP_1109295 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TMP116LE-T3D | 208-230/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 16 |
| defrost | E |
| fan count | 1 |
| generation suffix | D |
| temp class | L |
| voltage | T3 |
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KMP116LE-T3D | shared catalog stem ✓ |
| Bally | BMP116LE-T3D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TMP116LE-T3D?
TMP116LE-T3D has a rated capacity of 16700 btu_h. See the specifications table for rating conditions.
What voltage does TMP116LE-T3D require?
TMP116LE-T3D runs on 208 V supply power.