TMP113VE-S4E
Trenton Refrigeration TMP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 1 count | TMP + TMP-GEN-E p.5 ✓ | |
| capacity | 13600 btu_h | evap temp f: 0; refrigerant: R407A/R448A | p.5 |
| 13200 btu_h | evap temp f: 10; refrigerant: R407A/R448A | p.5 | |
| 12800 btu_h | evap temp f: 20; refrigerant: R407A/R448A | p.5 | |
| 11800 btu_h | evap temp f: 30; refrigerant: R407A/R448A | p.5 | |
| 10900 btu_h | evap temp f: 40; refrigerant: R407A/R448A | p.5 | |
| 11000 btu_h | evap temp f: 0; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 10700 btu_h | evap temp f: 10; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 10400 btu_h | evap temp f: 20; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 9600 btu_h | evap temp f: 30; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 8800 btu_h | evap temp f: 40; refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 13600 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 34500 btu_hsources differ | evap temp f: 10; refrigerant: R454A/R454C/R455A | TMP p.5 | |
| 13200 btu_hsources differ | evap temp f: 10; refrigerant: R454A/R454C/R455A | TMP-GEN-E p.4 | |
| 12800 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 11800 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 10900 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 13600 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | p.6 | |
| 13200 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | p.6 | |
| 12800 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | p.6 | |
| 11800 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | p.6 | |
| 10900 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | p.6 | |
| airflow | 3220 cfm | refrigerant: R407A/R448A | p.5 |
| 1520 l_s | refrigerant: R407A/R448A | p.5 | |
| 3220 cfm | refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 1520 l_s | refrigerant: R404A | TMP + TMP-GEN-E p.5 ✓ | |
| 3220 cfm | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 1520 l_s | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 3220 cfm | refrigerant: R407A/R448A/R449A | p.6 | |
| 1520 l_s | refrigerant: R407A/R448A/R449A | p.6 | |
| refrigerant charge | 2.5 lb | refrigerant: R407A | TMP + TMP-GEN-E p.5 ✓ |
| 1.1 kg | refrigerant: R407A | TMP + TMP-GEN-E p.5 ✓ | |
| 2.3 lbsources differ | refrigerant: R404A | TMP p.5 | |
| 3.7 lbsources differ | refrigerant: R404A | TMP-GEN-E p.7 | |
| 1 kgsources differ | refrigerant: R404A | TMP p.5 | |
| 1.7 kgsources differ | refrigerant: R404A | TMP-GEN-E p.7 | |
| 2.2 lb | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 1 kg | refrigerant: R454A/R454C/R455A | TMP + TMP-GEN-E p.5 ✓ | |
| 2.4 lb | refrigerant: R448A | p.5 | |
| 1.1 kg | refrigerant: R448A | p.5 | |
| 2.4 lb | refrigerant: R448A/R449A | p.6 | |
| 1.1 kg | refrigerant: R448A/R449A | p.6 | |
| awef rating | 4.06 ratio | refrigerant: R404A/R507 | p.33 ✓ |
| 4.06 ratio | refrigerant: R407A | p.33 | |
| 4.06 ratio | refrigerant: R448A/R449A | p.33 | |
| 4.06 ratio | refrigerant: R454A | p.33 | |
| 4.06 ratio | refrigerant: R454C | p.33 | |
| 4.06 ratio | refrigerant: R455A | p.33 | |
| 4.06 ratio | fpi: 4 | p.31 | |
| hot gas connection | 1 inchessources differ | TMP p.35 | |
| 0.5 inchessources differ | TMP p.35 | ||
| 0.875 inchessources differ | TMP p.35 | ||
| suction od | 1 1/8 inches | TMP + TMP-GEN-E p.35 ✓ | |
| distributor inlet | 0.875 inches | TMP + TMP-GEN-E p.35 ✓ | |
| shipping weight | 160 lb | TMP + TMP-GEN-E p.36 ✓ | |
| 73 kg | TMP + TMP-GEN-E p.36 ✓ | ||
| mca | 9.1 ampssources differ | TMP p.11 | |
| 15 ampssources differ | TMP-GEN-E p.12 | ||
| 9 ampssources differ | TMP-GEN-E p.12 | ||
| esp circuit 460 1 60 mop a | 15 | TMP + TMP-GEN-E p.11 ✓ | |
| voltage | 460 V | TMP + TMP-GEN-E p.? ✓ | |
| phase | 1 ph | TMP + TMP-GEN-E p.? ✓ | |
| frequency | 60 Hz | TMP + TMP-GEN-E p.? ✓ | |
| side port connection | 0.5 inches | p.34 | |
| drain pan loop conn od sweat | 0.875 | p.34 | |
| r454a sporlan sbqte b zp | SBQTE-B-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| r448a r449a r407a r407c r454c r455a sporlan sbqve b zp | SBQVE-B-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| r404a r507 sporlan sbqse b zp | SBQSE-A-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.37 |
| liquid line od | 0.375 inches | p.46 | |
| suction line od | 1 1/8 inches | p.46 | |
| maximum line length 10 ft minimum room area ft2 | 33 | p.46 | |
| maximum line length 25 ft | 42 | p.46 | |
| maximum line length 50 ft | 55 | p.46 | |
| maximum line length 100 ft | 82 | p.46 | |
| fpi | 4 | p.12 | |
| motor hp | 0.3333333333333333 hp | p.12 | |
| motor fla | 1.6 amps | p.12 | |
| motor watts | 210 watts | p.12 | |
| mop | 15 amps | p.12 | |
| total watts | 3330 watts | p.12 | |
| total amps | 7.2 amps | p.12 | |
| defrost heaters 460 1 60 mop a | 15 | p.12 | |
| esp circuit mca | 9.1 amps | p.17 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TMP113VE-S4E | 460/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 13 |
| capacity mbh | 13 |
| defrost | E |
| fan count | 1 |
| generation suffix | E |
| temp class | V |
| voltage | S4 |
Parts
8 factory parts for this unit: 8from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | G2-1/2✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E2V24order as E2V24FWBC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV9order as CSOV-9S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV6✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B3✓ | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | - | - | Check availability |
| Solenoid valve | E5order as E5S130✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| TXV | SBQSE-A-ZPorder as SBQSE-A-ZP40✓ | refrigerant: R404A/R507 | - | - | Check availability |
| TXV | SBQVE-B-ZPorder as SBQVE-B-ZP40✓ | refrigerant: R448A/R449A/R407A | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KMP113VE-S4E | shared catalog stem ✓ |
| Bally | BMP113VE-S4E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TMP113VE-S4E?
TMP113VE-S4E has a rated capacity of 13600 btu_h. See the specifications table for rating conditions.
What voltage does TMP113VE-S4E require?
TMP113VE-S4E runs on 460 V supply power.
Related models in TMP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.