TLP627VE-S2D
Trenton Refrigeration TLP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 6 count | refrigerant: R454A/R454C/R455A | p.3 |
| 6 count | TLP + TLP-GEN-E p.6 ✓ | ||
| capacity | 28400 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | TLP + TLP-GEN-E p.3 ✓ |
| 27600 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | TLP + TLP-GEN-E p.3 ✓ | |
| 26800 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | TLP + TLP-GEN-E p.3 ✓ | |
| 24700 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | TLP + TLP-GEN-E p.3 ✓ | |
| 22800 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | TLP + TLP-GEN-E p.3 ✓ | |
| 28400 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | p.6 | |
| 27600 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | p.6 | |
| 26800 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | p.6 | |
| 24700 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | p.6 | |
| 22800 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | p.6 | |
| 26610 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.7 | |
| 25900 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.7 | |
| 25100 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.7 | |
| 23100 btu_h | evap temp f: 30; refrigerant: R404A/R507 | p.7 | |
| 21340 btu_h | evap temp f: 40; refrigerant: R404A/R507 | p.7 | |
| airflow | 4080 cfm | refrigerant: R454A/R454C/R455A | p.3 |
| 1930 l_s | refrigerant: R454A/R454C/R455A | p.3 | |
| 4080 cfm | p.4 | ||
| 1930 l_s | p.4 | ||
| refrigerant charge | 7.8 lbsources differ | refrigerant: R454A/R454C/R455A | TLP p.3 |
| 4.1 lbsources differ | refrigerant: R454A/R454C/R455A | TLP-GEN-E p.4 | |
| (3.5) kgsources differ | refrigerant: R454A/R454C/R455A | TLP p.3 | |
| (1.9) kgsources differ | refrigerant: R454A/R454C/R455A | TLP-GEN-E p.4 | |
| 4.5 lb | refrigerant: R407A/R448A/R449A | p.6 | |
| (2.0) kg | refrigerant: R407A/R448A/R449A | p.6 | |
| 4.2 lb | refrigerant: R404A/R507 | p.7 | |
| (1.9) kg | refrigerant: R404A/R507 | p.7 | |
| awef rating | 4.15 ratio | refrigerant: R454A | p.16 ✓ |
| 4.15 ratio | refrigerant: R454C | p.16 | |
| 4.15 ratio | refrigerant: R455A | p.16 | |
| 4.15 ratio | fpi: 4 | p.24 | |
| liquid line od | 0.5 inches | TLP + TLP-GEN-E p.25 ✓ | |
| 13 mm | TLP + TLP-GEN-E p.26 ✓ | ||
| suction od | 1 3/8 inches | TLP + TLP-GEN-E p.25 ✓ | |
| 35 mm | p.26 | ||
| maximum line length 10 ft minimum room area ft2 | 60 | p.25 | |
| maximum line length 25 ft | 76 | TLP + TLP-GEN-E p.25 ✓ | |
| maximum line length 50 ft | 102 | TLP + TLP-GEN-E p.25 ✓ | |
| maximum line length 100 ft | 154 | TLP + TLP-GEN-E p.25 ✓ | |
| maximum line length 3m minimum room area m2 | 6 | p.26 | |
| maximum line length 7 6m | 7 | TLP + TLP-GEN-E p.26 ✓ | |
| maximum line length 15 2m | 9 | TLP + TLP-GEN-E p.26 ✓ | |
| maximum line length 30 5m | 14 | TLP + TLP-GEN-E p.26 ✓ | |
| motor hp | 0.06666666666666667 hp | TLP + TLP-GEN-E p.6 ✓ | |
| motor fla | 3.6 amps | TLP + TLP-GEN-E p.6 ✓ | |
| total watts | 360 wattssources differ | TLP p.6 | |
| 5230 wattssources differ | TLP p.6 | ||
| 5230 wattssources differ | TLP-GEN-E p.10 | ||
| mca | 3.8 ampssources differ | TLP p.6 | |
| 28.4 ampssources differ | TLP p.6 | ||
| 18 ampssources differ | TLP p.6 | ||
| 3.8 ampssources differ | TLP-GEN-E p.10 | ||
| 28.4 ampssources differ | TLP-GEN-E p.10 | ||
| 18 ampssources differ | TLP-GEN-E p.10 | ||
| mop | 15 amps | TLP + TLP-GEN-E p.6 ✓ | |
| total amps | 22.7 ampssources differ | TLP p.6 | |
| 15 ampssources differ | TLP p.6 | ||
| 22.7 ampssources differ | TLP-GEN-E p.10 | ||
| 15 ampssources differ | TLP-GEN-E p.10 | ||
| defrost heaters 208 230 1 60 mop a | 30 | TLP + TLP-GEN-E p.6 ✓ | |
| defrost heaters 208 230 3 60 mop a | 20 | TLP + TLP-GEN-E p.6 ✓ | |
| snaf fo 1 | 6 | p.33 | |
| voltage 208 230 1 60 | 208-230/1/60 | p.33 | |
| 1 x evaporator defrost kit dfk 02 | DFK-02 | p.33 | |
| 1 x evaporator fuse package fp 004 | FP-020 | p.33 | |
| 2 x evaporator defrost kit dfk 06 | DFK-09 | p.33 | |
| 2 x evaporator fuse package fp 008 | FP-021 | p.33 | |
| voltage | 208 V | TLP + TLP-GEN-E p.? ✓ | |
| phase | 1 ph | TLP + TLP-GEN-E p.? ✓ | |
| frequency | 60 Hz | TLP + TLP-GEN-E p.? ✓ | |
| model tlp | TLP | p.26 | |
| TLP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.30 | |
| dimension unparsed | 110 1/4sources differ | TLP-GEN-E p.26 | |
| 2800sources differ | TLP-GEN-E p.26 | ||
| 48 5/8sources differ | TLP-GEN-E p.26 | ||
| 1235sources differ | TLP-GEN-E p.26 | ||
| 1 1/8sources differ | TLP-GEN-E p.26 | ||
| distributor inlet | 0.875 inches | p.26 | |
| hot gas connection | 0.625 inches | p.26 | |
| suction line od | 1 3/8 inches | p.39 | |
| 35 mm | p.40 | ||
| maximum line length 10 ft minimum room area ft | 60 | p.39 | |
| maximum line length 3m minimum room area ft | 6 | p.40 | |
| unclassified part | TLP part_number | p.32 | |
| motor watts | 360 watts | p.10 | |
| r454a sporlan ebqte aa zp | EBQTE-C-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.30 |
| r448a r449a r407a r407c r454c r455a sporlan ebqve aa zp | EBQVE-C-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.30 |
| r404a r507 sporlan ebqse aa zp | EBSSE-6-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.30 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TLP627VE-S2D | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 27 |
| capacity mbh | 27 |
| defrost | E |
| fan count | 6 |
| generation suffix | D |
| temp class | V |
| voltage | S2 |
Parts
7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | G5✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E2V35order as E2V35FSMC0✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Electronic expansion valve | RSV320✓ | Electronic expansion valve (EEV), KE2 Therm Solutions | - | - | Check availability |
| Safety check valve | CSOV11order as CSOV-11S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV6✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B6order as B6S1✓ | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | - | - | Check availability |
| Solenoid valve | E6order as E6S140✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KLP627VE-S2D | shared catalog stem ✓ |
| Bally | BLP627VE-S2D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TLP627VE-S2D?
TLP627VE-S2D has a rated capacity of 28400 btu_h. See the specifications table for rating conditions.
What voltage does TLP627VE-S2D require?
TLP627VE-S2D runs on 208 V supply power.
Related models in TLP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.