Trenton Refrigeration · TLP · Low Profile Evaporatorsavailable Options
TLP524VE-S2D
Trenton Refrigeration TLP low profile savailable option evaporator.
53 extracted specifications, each traceable to its source document and page.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 5 count | p.3 | |
| 5 count | p.6 | ||
| capacity | 25300 btu_h | evap temp f: 0 | p.3 |
| 24600 btu_h | evap temp f: 10 | p.3 | |
| 23900 btu_h | evap temp f: 20 | p.3 | |
| 22000 btu_h | evap temp f: 30 | p.3 | |
| 20300 btu_h | evap temp f: 40 | p.3 | |
| airflow | 3400 cfm | p.3 | |
| 1600 l_s | p.3 | ||
| refrigerant charge | 6.5 lb | p.3 | |
| (2.9) kg | p.3 | ||
| awef rating | 4.15 ratio | refrigerant: R454A | p.16 |
| 4.15 ratio | refrigerant: R454C | p.16 | |
| 4.15 ratio | refrigerant: R455A | p.16 | |
| liquid line od in | 0.5 | p.25 | |
| suction od | 1 3/8 inches | p.25 | |
| 35 inches | p.26 | ||
| maximum line length 10 ft minimum room area ft2 | 54 | p.25 | |
| maximum line length 25 ft | 69 | p.25 | |
| maximum line length 50 ft | 95 | p.25 | |
| maximum line length 100 ft | 147 | p.25 | |
| liquid line od mm | 13 | p.26 | |
| maximum line length 3m minimum room area m2 | 5 | p.26 | |
| maximum line length 7 6m | 6 | p.26 | |
| maximum line length 15 2m | 9 | p.26 | |
| maximum line length 30 5m | 14 | p.26 | |
| distributor nozzle | G4 part_id | p.19 | |
| electronic expansion valve | E2V35 part_number | p.19 | |
| RSV220 part_number | p.19 | ||
| solenoid valve | E6 part_number | p.19 | |
| safety solenoid valve | SSOV6 part_number | p.19 | |
| safety check valve | CSOV11 part_number | p.19 | |
| motor hp | 0.06666666666666667 hp | p.6 | |
| motor fla | 3 amps | p.6 | |
| total watts | 300 watts | p.6 | |
| 4400 watts | p.6 | ||
| mca | 3.2 amps | p.6 | |
| 23.9 amps | p.6 | ||
| 15 amps | p.6 | ||
| fan motors standard ec motors mop a | 15 | p.6 | |
| total amps | 19.1 amps | p.6 | |
| 12 amps | p.6 | ||
| defrost heaters 208 230 1 60 mop a | 25 | p.6 | |
| defrost heaters 208 230 3 60 mop a | 20 | p.6 | |
| snaf fo 1 | 5 | p.33 | |
| voltage 208 230 1 60 | 208-230/1/60 | p.33 | |
| 1 x evaporator defrost kit dfk 02 | DFK-02 | p.33 | |
| 1 x evaporator fuse package fp 004 | FP-007 | p.33 | |
| 2 x evaporator defrost kit dfk 06 | DFK-06 | p.33 | |
| 2 x evaporator fuse package fp 008 | FP-010 | p.33 | |
| voltage | 208 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: TLP_1112452 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TLP524VE-S2D | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 24 |
| defrost | E |
| fan count | 5 |
| generation suffix | D |
| temp class | V |
| voltage | S2 |
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KLP524VE-S2D | shared catalog stem ✓ |
| Bally | BLP524VE-S2D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TLP524VE-S2D?
TLP524VE-S2D has a rated capacity of 25300 btu_h. See the specifications table for rating conditions.
What voltage does TLP524VE-S2D require?
TLP524VE-S2D runs on 208 V supply power.
Related models in TLP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.