TLP429ME-T3E

Trenton Refrigeration TLP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
capacity29400 btu_hTLP + TLP-GEN-E p.3
29100 btu_hTLP + TLP-GEN-E p.3
28810 btu_hTLP + TLP-GEN-E p.3
29400 btu_hp.5
29100 btu_hp.5
28810 btu_hp.5
26400 btu_hp.6
26100 btu_hp.6
25870 btu_hp.6
airflow2720 cfmp.3
1280 l_sp.3
2720 cfmp.3
1280 l_sp.3
refrigerant charge3.1 lbTLP + TLP-GEN-E p.3
(1.4) kgTLP + TLP-GEN-E p.3
3.1 lbp.5
(1.4) kgp.5
3.1 lbp.6
(1.4) kgp.6
awef rating9 ratiop.16
9 ratiop.16
9 ratiop.16
9 ratiop.24
liquid line od0.5 inchesTLP + TLP-GEN-E p.25
13 mmTLP + TLP-GEN-E p.26
suction od1 1/8 inchesTLP + TLP-GEN-E p.25
29 mmp.26
maximum line length 10 ft minimum room area ft248p.25
maximum line length 25 ft64TLP + TLP-GEN-E p.25
maximum line length 50 ft90TLP + TLP-GEN-E p.25
maximum line length 100 ft143TLP + TLP-GEN-E p.25
maximum line length 3m minimum room area m24p.26
maximum line length 7 6m6TLP + TLP-GEN-E p.26
maximum line length 15 2m8TLP + TLP-GEN-E p.26
maximum line length 30 5m13TLP + TLP-GEN-E p.26
model tlp421LEsources differTLP p.18
421VEsources differTLP p.18
TLPsources differTLP-GEN-E p.26
TLPp.29
shipping weight145 lbTLP + TLP-GEN-E p.18
66 kgsources differTLP p.18
(66) kgsources differTLP-GEN-E p.27
fan qty4 countTLP + TLP-GEN-E p.6
motor hp0.06666666666666667 hpTLP + TLP-GEN-E p.6
motor fla2.4 ampsTLP + TLP-GEN-E p.6
total watts240 wattssources differTLP p.6
3560 wattssources differTLP p.6
3560 wattssources differTLP-GEN-E p.10
mca2.6 ampssources differTLP p.6
19.3 ampssources differTLP p.6
12 ampssources differTLP p.6
12.5 ampssources differTLP p.9
2.6 ampssources differTLP-GEN-E p.10
19.3 ampssources differTLP-GEN-E p.10
12 ampssources differTLP-GEN-E p.10
mop15 ampsTLP + TLP-GEN-E p.6
total amps15.5 ampssources differTLP p.6
10 ampssources differTLP p.6
15.5 ampssources differTLP-GEN-E p.10
10 ampssources differTLP-GEN-E p.10
defrost heaters 208 230 1 60 mop a20TLP + TLP-GEN-E p.6
defrost heaters 208 230 3 60 mop a15TLP + TLP-GEN-E p.6
esp circuit 208 230 3 60 mop a15p.9
voltage208 VTLP + TLP-GEN-E p.?
phase3 phTLP + TLP-GEN-E p.?
frequency60 HzTLP + TLP-GEN-E p.?
air flow 30 f 34 c2720p.6
air flow 40 f 40 c1280p.6
dimension unparsed78 1/4sources differTLP-GEN-E p.26
1988sources differTLP-GEN-E p.26
32 5/8sources differTLP-GEN-E p.26
829sources differTLP-GEN-E p.26
0.875sources differTLP-GEN-E p.26
distributor inlet0.5 inchesp.26
hot gas connection0.5 inchesp.26
r454a sporlan ebqte aaa cEBQTE-B-Cp.29
r448a r449a r407a r407c r454c r455a sporlan ebqve aaa cEBQVE-B-Cp.29
r404a r507 sporlan ebqse aa cEBQSE-C-Cp.29
unclassified partTLP part_numberp.31
suction line od1 1/8 inchesp.39
29 mmp.40
maximum line length 10 ft minimum room area ft48p.39
maximum line length 3m minimum room area ft4p.40
model 104le421LEp.27
model 103ve421VEp.27
motor watts240 wattsp.10
voltage 208 230 1 60208-230/3/60p.46

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TLP_1112452, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TLP-GEN-E_1112452, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase.

Nomenclature

Position / meaningValue
capacity code29
capacity mbh29
defrostE
fan count4
generation suffixE
temp classM
voltageT3

Parts

6 factory parts for this unit: 6from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.

PartPart numberQtyListAvailability
Distributor nozzleL2--Check availability
Electronic expansion valveE2V24order as E2V24FWBC1--Check availability
Electronic expansion valveRSV 320--Check availability
Safety check valveCSOV9order as CSOV-9S--Check availability
Safety shutoff solenoidSSOV6--Check availability
Solenoid valveE5order as E5S130--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

No sister-brand equivalents cataloged for this model.

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TLP429ME-T3E?

TLP429ME-T3E has a rated capacity of 29400 btu_h. See the specifications table for rating conditions.

What voltage does TLP429ME-T3E require?

TLP429ME-T3E runs on 208 V supply power.

Related models in TLP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.