Trenton Refrigeration · TLP · Low Profile Evaporatorsavailable Options
TLP429ME-S2E
Trenton Refrigeration TLP low profile savailable option evaporator.
50 extracted specifications, each traceable to its source document and page.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 29400 btu_h | evap temp f: 25 | p.3 |
| 29100 btu_h | evap temp f: 15 | p.3 | |
| 28810 btu_h | evap temp f: 10 | p.3 | |
| airflow | 2720 cfm | p.3 | |
| 1280 l_s | p.3 | ||
| refrigerant charge | 3.1 lb | p.3 | |
| (1.4) kg | p.3 | ||
| awef rating | 9 ratio | refrigerant: R454A | p.16 |
| 9 ratio | refrigerant: R454C | p.16 | |
| 9 ratio | refrigerant: R455A | p.16 | |
| distributor nozzle | L2 part_id | p.19 | |
| electronic expansion valve | RSV 320 part_number | p.19 | |
| E2V24 part_number | p.19 | ||
| solenoid valve | E5 part_number | p.19 | |
| safety solenoid valve | SSOV6 part_number | p.19 | |
| safety check valve | CSOV9 part_number | p.19 | |
| liquid line od in | 0.5 | p.25 | |
| suction od | 1 1/8 inches | p.25 | |
| 29 inches | p.26 | ||
| maximum line length 10 ft minimum room area ft2 | 48 | p.25 | |
| maximum line length 25 ft | 64 | p.25 | |
| maximum line length 50 ft | 90 | p.25 | |
| maximum line length 100 ft | 143 | p.25 | |
| liquid line od mm | 13 | p.26 | |
| maximum line length 3m minimum room area m2 | 4 | p.26 | |
| maximum line length 7 6m | 6 | p.26 | |
| maximum line length 15 2m | 8 | p.26 | |
| maximum line length 30 5m | 13 | p.26 | |
| model tlp | 421LE | p.18 | |
| 421VE | p.18 | ||
| shipping weight | 145 lb | p.18 | |
| 66 kg | p.18 | ||
| fan qty | 4 count | p.6 | |
| motor hp | 0.06666666666666667 hp | p.6 | |
| motor fla | 2.4 amps | p.6 | |
| total watts | 240 watts | p.6 | |
| 3560 watts | p.6 | ||
| mca | 2.6 amps | p.6 | |
| 19.3 amps | p.6 | ||
| 12 amps | p.6 | ||
| 19.3 amps | p.9 | ||
| fan motors standard ec motors mop a | 15 | p.6 | |
| total amps | 15.5 amps | p.6 | |
| 10 amps | p.6 | ||
| defrost heaters 208 230 1 60 mop a | 20 | p.6 | |
| defrost heaters 208 230 3 60 mop a | 15 | p.6 | |
| esp circuit 208 230 1 60 mop a | 20 | p.9 | |
| voltage | 208 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: TLP_1112452 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TLP429ME-S2E | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 29 |
| defrost | E |
| fan count | 4 |
| generation suffix | E |
| temp class | M |
| voltage | S2 |
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KLP429ME-S2E | shared catalog stem ✓ |
| Bally | BLP429ME-S2E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TLP429ME-S2E?
TLP429ME-S2E has a rated capacity of 29400 btu_h. See the specifications table for rating conditions.
What voltage does TLP429ME-S2E require?
TLP429ME-S2E runs on 208 V supply power.
Related models in TLP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.