TLP424ME-S2E

Trenton Refrigeration TLP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
fan qty4 countp.6
capacity24400 btu_hp.3
24200 btu_hp.3
23910 btu_hp.3
24400 btu_hp.5
24200 btu_hp.5
23910 btu_hp.5
21800 btu_hp.6
21600 btu_hp.6
21360 btu_hp.6
airflow2820 cfmp.3
1330 l_sp.3
refrigerant charge2.5 lbp.3
(1.1) kgp.3
2.5 lbp.5
(1.1) kgp.5
2.5 lbp.6
(1.2) kgp.6
air flow 30 f 34 c2820p.6
air flow 40 f 40 c1330p.6
awef rating9 ratiop.24
model tlpTLPp.26
TLPp.29
dimension unparsed78 1/4sources differTLP-GEN-E p.26
1988sources differTLP-GEN-E p.26
32 5/8sources differTLP-GEN-E p.26
829sources differTLP-GEN-E p.26
0.875sources differTLP-GEN-E p.26
suction od1 1/8 inchesp.26
distributor inlet0.5 inchesp.26
hot gas connection0.5 inchesp.26
r454a sporlan ebqte aaa cEBQTE-B-Cp.29
r448a r449a r407a r407c r454c r455a sporlan ebqve aaa cEBQVE-B-Cp.29
r404a r507 sporlan ebqse aa cEBQSE-C-Cp.29
unclassified partTLP part_numberp.31
liquid line od0.5 inchesp.39
13 mmp.40
suction line od1 1/8 inchesp.39
29 mmp.40
maximum line length 10 ft minimum room area ft41p.39
maximum line length 25 ft57p.39
maximum line length 50 ft83p.39
maximum line length 100 ft136p.39
maximum line length 3m minimum room area ft4p.40
maximum line length 7 6m5p.40
maximum line length 15 2m8p.40
maximum line length 30 5m13p.40
model 104le418LEp.27
model 103ve418VEp.27
shipping weight127 lbp.27
(58) kgp.27
motor hp0.06666666666666667 hpp.10
motor fla2.4 ampsp.10
motor watts240 wattsp.10
mca2.6 ampssources differTLP-GEN-E p.10
19.3 ampssources differTLP-GEN-E p.10
12 ampssources differTLP-GEN-E p.10
mop15 ampsp.10
total watts3560 wattsp.10
total amps15.5 ampssources differTLP-GEN-E p.10
10 ampssources differTLP-GEN-E p.10
defrost heaters 208 230 1 60 mop a20p.10
defrost heaters 208 230 3 60 mop a15p.10
esp circuit mca19.3 ampsp.13
esp 208 230 1 60 mop a20p.13
voltage 208 230 1 60208-230/1/60p.46
voltage208 Vp.?
phase1 php.?
frequency60 Hzp.?

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including TLP-GEN-E_1112452, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
TLP424ME-S2E208-230/1/60Check availability

Nomenclature

Position / meaningValue
capacity code24
capacity mbh24
defrostE
fan count4
generation suffixE
temp classM
voltageS2

Parts

6 factory parts for this unit: 6from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.

PartPart numberQtyListAvailability
Distributor nozzleL2--Check availability
Electronic expansion valveE2V24order as E2V24FWBC1--Check availability
Electronic expansion valveRSV 320--Check availability
Safety check valveCSOV9order as CSOV-9S--Check availability
Safety shutoff solenoidSSOV6--Check availability
Solenoid valveE5order as E5S130--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKLP424ME-S2Eshared catalog stem
BallyBLP424ME-S2Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TLP424ME-S2E?

TLP424ME-S2E has a rated capacity of 24400 btu_h. See the specifications table for rating conditions.

What voltage does TLP424ME-S2E require?

TLP424ME-S2E runs on 208 V supply power.

Related models in TLP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.