TLP421VE-T3D
Trenton Refrigeration TLP low profile evaporatorsavailable options evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 22300 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | p.3 |
| 21600 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.3 | |
| 21000 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | p.3 | |
| 19300 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | p.3 | |
| 17900 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | p.3 | |
| airflow | 2720 cfm | refrigerant: R454A/R454C/R455A | p.3 |
| 1280 l_s | refrigerant: R454A/R454C/R455A | p.3 | |
| refrigerant charge | 3.9 lb | refrigerant: R454A/R454C/R455A | p.3 |
| (1.8) kg | refrigerant: R454A/R454C/R455A | p.3 | |
| awef rating | 4.15 ratio | refrigerant: R454A | p.16 ✓ |
| 4.15 ratio | refrigerant: R454C | p.16 | |
| 4.15 ratio | refrigerant: R455A | p.16 | |
| liquid line od | 0.5 inches | p.25 | |
| 13 mm | p.26 | ||
| suction od | 1 1/8 inches | p.25 | |
| 29 mm | p.26 | ||
| maximum line length 10 ft minimum room area ft2 | 46 | p.25 | |
| maximum line length 25 ft | 61 | p.25 | |
| maximum line length 50 ft | 87 | p.25 | |
| maximum line length 100 ft | 137 | p.25 | |
| maximum line length 3m minimum room area m2 | 4 | p.26 | |
| maximum line length 7 6m | 6 | p.26 | |
| maximum line length 15 2m | 8 | p.26 | |
| maximum line length 30 5m | 13 | p.26 | |
| fan qty | 4 count | p.6 ✓ | |
| motor hp | 0.06666666666666667 hp | p.6 ✓ | |
| motor fla | 2.4 amps | p.6 | |
| total watts | 240 wattssources differ | TLP p.6 | |
| 3560 wattssources differ | TLP p.6 | ||
| mca | 2.6 ampssources differ | TLP p.6 | |
| 19.3 ampssources differ | TLP p.6 | ||
| 12 ampssources differ | TLP p.6 | ||
| mop | 15 amps | p.6 | |
| total amps | 15.5 ampssources differ | TLP p.6 | |
| 10 ampssources differ | TLP p.6 | ||
| defrost heaters 208 230 1 60 mop a | 20 | p.6 | |
| defrost heaters 208 230 3 60 mop a | 15 | p.6 | |
| voltage 208 230 1 60 | 208-230/3/60 | p.33 | |
| 1 x evaporator defrost kit dfk 02 | DFK-03 | p.33 | |
| 1 x evaporator fuse package fp 004 | FP-013 | p.33 | |
| 2 x evaporator defrost kit dfk 06 | DFK-07 | p.33 | |
| 2 x evaporator fuse package fp 008 | FP-018 | p.33 | |
| voltage | 208 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TLP421VE-T3D | 208-230/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 21 |
| capacity mbh | 21 |
| defrost | E |
| fan count | 4 |
| generation suffix | D |
| temp class | V |
| voltage | T3 |
Parts
6 factory parts for this unit: 6from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | G3✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E2V35order as E2V35FSMC0✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Electronic expansion valve | RSV220✓ | Electronic expansion valve (EEV), KE2 Therm Solutions | - | - | Check availability |
| Safety check valve | CSOV9order as CSOV-9S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV6✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | E5order as E5S130✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KLP421VE-T3D | shared catalog stem ✓ |
| Bally | BLP421VE-T3D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TLP421VE-T3D?
TLP421VE-T3D has a rated capacity of 22300 btu_h. See the specifications table for rating conditions.
What voltage does TLP421VE-T3D require?
TLP421VE-T3D runs on 208 V supply power.
Related models in TLP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.