TLP418VE-S2D
Trenton Refrigeration TLP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 4 count | refrigerant: R454A/R454C/R455A | p.3 |
| 4 count | TLP + TLP-GEN-E p.6 ✓ | ||
| capacity | 18800 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | TLP + TLP-GEN-E p.3 ✓ |
| 18200 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | TLP + TLP-GEN-E p.3 ✓ | |
| 17700 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | TLP + TLP-GEN-E p.3 ✓ | |
| 16300 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | TLP + TLP-GEN-E p.3 ✓ | |
| 15000 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | TLP + TLP-GEN-E p.3 ✓ | |
| 18800 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | p.6 | |
| 18200 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | p.6 | |
| 17700 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | p.6 | |
| 16300 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | p.6 | |
| 15000 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | p.6 | |
| 17600 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.7 | |
| 17100 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.7 | |
| 16600 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.7 | |
| 15300 btu_h | evap temp f: 30; refrigerant: R404A/R507 | p.7 | |
| 14110 btu_h | evap temp f: 40; refrigerant: R404A/R507 | p.7 | |
| airflow | 2820 cfm | refrigerant: R454A/R454C/R455A | p.3 |
| 1330 l_s | refrigerant: R454A/R454C/R455A | p.3 | |
| 2820 cfm | p.4 | ||
| 1330 l_s | p.4 | ||
| refrigerant charge | 3.3 lbsources differ | refrigerant: R454A/R454C/R455A | TLP p.3 |
| 2.4 lbsources differ | refrigerant: R454A/R454C/R455A | TLP-GEN-E p.4 | |
| (1.5) kgsources differ | refrigerant: R454A/R454C/R455A | TLP p.3 | |
| (1.1) kgsources differ | refrigerant: R454A/R454C/R455A | TLP-GEN-E p.4 | |
| 2.6 lb | refrigerant: R407A/R448A/R449A | p.6 | |
| (1.2) kg | refrigerant: R407A/R448A/R449A | p.6 | |
| 2.4 lb | refrigerant: R404A/R507 | p.7 | |
| (1.1) kg | refrigerant: R404A/R507 | p.7 | |
| awef rating | 4.13 ratio | refrigerant: R454A | p.16 ✓ |
| 4.13 ratio | refrigerant: R454C | p.16 | |
| 4.13 ratio | refrigerant: R455A | p.16 | |
| 4.13 ratio | fpi: 4 | p.24 | |
| liquid line od | 0.375 inches | TLP + TLP-GEN-E p.25 ✓ | |
| 10 mm | TLP + TLP-GEN-E p.26 ✓ | ||
| suction od | 1 1/8 inches | TLP + TLP-GEN-E p.25 ✓ | |
| 29 mm | p.26 | ||
| maximum line length 10 ft minimum room area ft2 | 34 | p.25 | |
| maximum line length 25 ft | 43 | TLP + TLP-GEN-E p.25 ✓ | |
| maximum line length 50 ft | 56 | TLP + TLP-GEN-E p.25 ✓ | |
| maximum line length 100 ft | 83 | TLP + TLP-GEN-E p.25 ✓ | |
| maximum line length 3m minimum room area m2 | 3 | p.26 | |
| maximum line length 7 6m | 4 | TLP + TLP-GEN-E p.26 ✓ | |
| maximum line length 15 2m | 5 | TLP + TLP-GEN-E p.26 ✓ | |
| maximum line length 30 5m | 8 | TLP + TLP-GEN-E p.26 ✓ | |
| motor hp | 0.06666666666666667 hp | TLP + TLP-GEN-E p.6 ✓ | |
| motor fla | 2.4 amps | TLP + TLP-GEN-E p.6 ✓ | |
| total watts | 240 wattssources differ | TLP p.6 | |
| 3560 wattssources differ | TLP p.6 | ||
| 3560 wattssources differ | TLP-GEN-E p.10 | ||
| mca | 2.6 ampssources differ | TLP p.6 | |
| 19.3 ampssources differ | TLP p.6 | ||
| 12 ampssources differ | TLP p.6 | ||
| 2.6 ampssources differ | TLP-GEN-E p.10 | ||
| 19.3 ampssources differ | TLP-GEN-E p.10 | ||
| 12 ampssources differ | TLP-GEN-E p.10 | ||
| mop | 15 amps | TLP + TLP-GEN-E p.6 ✓ | |
| total amps | 15.5 ampssources differ | TLP p.6 | |
| 10 ampssources differ | TLP p.6 | ||
| 15.5 ampssources differ | TLP-GEN-E p.10 | ||
| 10 ampssources differ | TLP-GEN-E p.10 | ||
| defrost heaters 208 230 1 60 mop a | 20 | TLP + TLP-GEN-E p.6 ✓ | |
| defrost heaters 208 230 3 60 mop a | 15 | TLP + TLP-GEN-E p.6 ✓ | |
| snaf fo 1 | 4 | p.33 | |
| voltage 208 230 1 60 | 208-230/1/60 | p.33 | |
| 1 x evaporator defrost kit dfk 02 | DFK-02 | p.33 | |
| 1 x evaporator fuse package fp 004 | FP-006 | p.33 | |
| 2 x evaporator defrost kit dfk 06 | DFK-06 | p.33 | |
| 2 x evaporator fuse package fp 008 | FP-015 | p.33 | |
| voltage | 208 V | TLP + TLP-GEN-E p.? ✓ | |
| phase | 1 ph | TLP + TLP-GEN-E p.? ✓ | |
| frequency | 60 Hz | TLP + TLP-GEN-E p.? ✓ | |
| model tlp | TLP | p.26 | |
| TLP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.30 | |
| dimension unparsed | 78 1/4sources differ | TLP-GEN-E p.26 | |
| 1988sources differ | TLP-GEN-E p.26 | ||
| 32 5/8sources differ | TLP-GEN-E p.26 | ||
| 829sources differ | TLP-GEN-E p.26 | ||
| 0.875sources differ | TLP-GEN-E p.26 | ||
| distributor inlet | 0.5 inches | p.26 | |
| hot gas connection | 0.5 inches | p.26 | |
| suction line od | 1 1/8 inches | p.39 | |
| 29 mm | p.40 | ||
| maximum line length 10 ft minimum room area ft | 34 | p.39 | |
| maximum line length 3m minimum room area ft | 3 | p.40 | |
| unclassified part | TLP part_number | p.32 | |
| motor watts | 240 watts | p.10 | |
| r454a sporlan ebqte aa zp | EBQTE-B-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.30 |
| r448a r449a r407a r407c r454c r455a sporlan ebqve aa zp | EBQVE-B-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.30 |
| r404a r507 sporlan ebqse aa zp | EBQSE-C-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.30 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TLP418VE-S2D | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 18 |
| capacity mbh | 18 |
| defrost | E |
| fan count | 4 |
| generation suffix | D |
| temp class | V |
| voltage | S2 |
Parts
6 factory parts for this unit: 6from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | J2-1/2✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E2V24order as E2V24FWBC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Electronic expansion valve | RSV220✓ | Electronic expansion valve (EEV), KE2 Therm Solutions | - | - | Check availability |
| Safety check valve | CSOV9order as CSOV-9S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV6✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | E5order as E5S130✓ | Solenoid valve; Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KLP418VE-S2D | shared catalog stem ✓ |
| Bally | BLP418VE-S2D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TLP418VE-S2D?
TLP418VE-S2D has a rated capacity of 18800 btu_h. See the specifications table for rating conditions.
What voltage does TLP418VE-S2D require?
TLP418VE-S2D runs on 208 V supply power.
Related models in TLP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.