Trenton Refrigeration · TLP · Low Profile Evaporatorsavailable Options
TLP318ME-T3D
Trenton Refrigeration TLP low profile savailable option evaporator.
54 extracted specifications, each traceable to its source document and page.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 3 count | p.3 | |
| 3 count | p.6 | ||
| capacity | 18400 btu_h | evap temp f: 25 | p.3 |
| 18200 btu_h | evap temp f: 15 | p.3 | |
| 18030 btu_h | evap temp f: 10 | p.3 | |
| airflow | 2115 cfm | p.3 | |
| 1000 l_s | p.3 | ||
| refrigerant charge | 2 lb | p.3 | |
| (0.9) kg | p.3 | ||
| awef rating | 9 ratio | refrigerant: R454A | p.16 |
| 9 ratio | refrigerant: R454C | p.16 | |
| 9 ratio | refrigerant: R455A | p.16 | |
| distributor nozzle | L1-1/2 part_id | p.19 | |
| electronic expansion valve | RSV 220 part_number | p.19 | |
| E2V24 part_number | p.19 | ||
| solenoid valve | E5 part_number | p.19 | |
| safety solenoid valve | SSOV6 part_number | p.19 | |
| safety check valve | CSOV7 part_number | p.19 | |
| liquid line od in | 0.375 | p.25 | |
| suction od | 0.875 inches | p.25 | |
| 22 inches | p.26 | ||
| maximum line length 10 ft minimum room area ft2 | 30 | p.25 | |
| maximum line length 25 ft | 38 | p.25 | |
| maximum line length 50 ft | 52 | p.25 | |
| maximum line length 100 ft | 80 | p.25 | |
| liquid line od mm | 10 | p.26 | |
| maximum line length 3m minimum room area m2 | 3 | p.26 | |
| maximum line length 7 6m | 4 | p.26 | |
| maximum line length 15 2m | 5 | p.26 | |
| maximum line length 30 5m | 7 | p.26 | |
| model tlp | 314LE | p.18 | |
| 313VE | p.18 | ||
| shipping weight | 109 lb | p.18 | |
| 49 kg | p.18 | ||
| motor hp | 0.06666666666666667 hp | p.6 | |
| motor fla | 1.8 amps | p.6 | |
| total watts | 180 watts | p.6 | |
| 2730 watts | p.6 | ||
| mca | 2 amps | p.6 | |
| 14.8 amps | p.6 | ||
| 10 amps | p.6 | ||
| fan motors standard ec motors mop a | 15 | p.6 | |
| total amps | 11.9 amps | p.6 | |
| 7.7 amps | p.6 | ||
| defrost heaters 208 230 1 60 mop a | 15 | p.6 | |
| defrost heaters 208 230 3 60 mop a | 15 | p.6 | |
| voltage 208 230 1 60 | 208-230/3/60 | p.32 | |
| 1 x evaporator defrost kit dfk 02 | DFK-03 | p.32 | |
| 1 x evaporator fuse package fp 004 | FP-013 | p.32 | |
| 2 x evaporator defrost kit dfk 06 | DFK-07 | p.32 | |
| 2 x evaporator fuse package fp 008 | FP-018 | p.32 | |
| voltage | 208 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: TLP_1112452 · extraction with per-cell provenance · verify before purchase.
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 18 |
| defrost | E |
| fan count | 3 |
| generation suffix | D |
| temp class | M |
| voltage | T3 |
Cross references
No sister-brand equivalents cataloged for this model.
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TLP318ME-T3D?
TLP318ME-T3D has a rated capacity of 18400 btu_h. See the specifications table for rating conditions.
What voltage does TLP318ME-T3D require?
TLP318ME-T3D runs on 208 V supply power.
Related models in TLP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.