Trenton Refrigeration · TLP · Low Profile Evaporatorsavailable Options

TLP316LE-S2D

Trenton Refrigeration TLP low profile savailable option evaporator.

51 extracted specifications, each traceable to its source document and page.

Specifications

SpecificationValueSource
capacity17170 btu_hp.3
16700 btu_hp.3
16200 btu_hp.3
14900 btu_hp.3
13800 btu_hp.3
airflow2040 cfmp.3
960 l_sp.3
refrigerant charge2.4 lbp.3
(1.1) kgp.3
awef rating4.1 ratiop.16
4.1 ratiop.16
4.1 ratiop.16
liquid line od in0.375p.25
suction od1 1/8 inchesp.25
29 inchesp.26
maximum line length 10 ft minimum room area ft235p.25
maximum line length 25 ft43p.25
maximum line length 50 ft56p.25
maximum line length 100 ft83p.25
liquid line od mm10p.26
maximum line length 3m minimum room area m23p.26
maximum line length 7 6m4p.26
maximum line length 15 2m5p.26
maximum line length 30 5m8p.26
distributor nozzleL3 part_idp.19
electronic expansion valveE2V24 part_numberp.19
RSV220 part_numberp.19
solenoid valveE5 part_numberp.19
safety solenoid valveSSOV6 part_numberp.19
safety check valveCSOV9 part_numberp.19
fan qty3 countp.6
motor hp0.06666666666666667 hpp.6
motor fla1.8 ampsp.6
total watts180 wattsp.6
2730 wattsp.6
mca2 ampsp.6
14.8 ampsp.6
10 ampsp.6
fan motors standard ec motors mop a15p.6
total amps11.9 ampsp.6
7.7 ampsp.6
defrost heaters 208 230 1 60 mop a15p.6
defrost heaters 208 230 3 60 mop a15p.6
voltage 208 230 1 60208-230/1/60p.32
1 x evaporator defrost kit dfk 02DFK-02p.32
1 x evaporator fuse package fp 004FP-004p.32
2 x evaporator defrost kit dfk 06 dfk 07DFK-06p.32
2 x evaporator fuse package fp 008FP-008p.32
voltage208 Vp.?
phase1 php.?
frequency60 Hzp.?

Sources: TLP_1112452 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot

Orderable variants (1)

VariantVoltageAvailability
TLP316LE-S2D208-230/1/60Check availability

Nomenclature

Position / meaningValue
capacity code16
defrostE
fan count3
generation suffixD
temp classL
voltageS2

Cross references

BrandEquivalent modelBasis
KeepRiteKLP316LE-S2Dshared catalog stem
BallyBLP316LE-S2Dshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TLP316LE-S2D?

TLP316LE-S2D has a rated capacity of 17170 btu_h. See the specifications table for rating conditions.

What voltage does TLP316LE-S2D require?

TLP316LE-S2D runs on 208 V supply power.

Related models in TLP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.