Trenton Refrigeration · TLP · Low Profile Evaporatorsavailable Options

TLP314LE-T3D

Trenton Refrigeration TLP low profile savailable option evaporator.

51 extracted specifications, each traceable to its source document and page.

Specifications

SpecificationValueSource
fan qty3 countp.3
3 countp.6
capacity14730 btu_hp.3
14300 btu_hp.3
13900 btu_hp.3
12800 btu_hp.3
11800 btu_hp.3
airflow2115 cfmp.3
1000 l_sp.3
refrigerant charge1.9 lbp.3
(0.9) kgp.3
awef rating4.07 ratiop.16
4.07 ratiop.16
4.07 ratiop.16
liquid line od in0.375p.25
suction od0.875 inchesp.25
22 inchesp.26
maximum line length 10 ft minimum room area ft229p.25
maximum line length 25 ft37p.25
maximum line length 50 ft50p.25
maximum line length 100 ft76p.25
liquid line od mm10p.26
maximum line length 3m minimum room area m23p.26
maximum line length 7 6m3p.26
maximum line length 15 2m5p.26
maximum line length 30 5m7p.26
distributor nozzleL2 part_idp.19
electronic expansion valveE2V24 part_numberp.19
RSV220 part_numberp.19
solenoid valveE5 part_numberp.19
safety solenoid valveSSOV6 part_numberp.19
safety check valveCSOV7 part_numberp.19
motor hp0.06666666666666667 hpp.6
motor fla1.8 ampsp.6
total watts180 wattsp.6
2730 wattsp.6
mca2 ampsp.6
14.8 ampsp.6
10 ampsp.6
fan motors standard ec motors mop a15p.6
total amps11.9 ampsp.6
7.7 ampsp.6
defrost heaters 208 230 1 60 mop a15p.6
defrost heaters 208 230 3 60 mop a15p.6
voltage 208 230 1 60208-230/3/60p.32
1 x evaporator defrost kit dfk 02DFK-03p.32
1 x evaporator fuse package fp 004FP-013p.32
2 x evaporator fuse package fp 008FP-018p.32
voltage208 Vp.?
phase3 php.?
frequency60 Hzp.?

Sources: TLP_1112452 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot

Orderable variants (1)

VariantVoltageAvailability
TLP314LE-T3D208-230/3/60Check availability

Nomenclature

Position / meaningValue
capacity code14
defrostE
fan count3
generation suffixD
temp classL
voltageT3

Cross references

BrandEquivalent modelBasis
KeepRiteKLP314LE-T3Dshared catalog stem
BallyBLP314LE-T3Dshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TLP314LE-T3D?

TLP314LE-T3D has a rated capacity of 14730 btu_h. See the specifications table for rating conditions.

What voltage does TLP314LE-T3D require?

TLP314LE-T3D runs on 208 V supply power.

Related models in TLP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.