Trenton Refrigeration · TLP · Low Profile Evaporatorsavailable Options

TLP211LE-S2E

Trenton Refrigeration TLP low profile savailable option evaporator.

48 extracted specifications, each traceable to its source document and page.

Specifications

SpecificationValueSource
capacity11980 btu_hp.3
11600 btu_hp.3
11300 btu_hp.3
10400 btu_hp.3
9610 btu_hp.3
airflow1360 cfmp.3
640 l_sp.3
refrigerant charge1.8 lbp.3
(0.8) kgp.3
awef rating4.04 ratiop.16
4.04 ratiop.16
4.04 ratiop.16
liquid line od in0.375p.25
suction od0.875 inchesp.25
22 inchesp.26
maximum line length 10 ft minimum room area ft227p.25
maximum line length 25 ft35p.25
maximum line length 50 ft48p.25
maximum line length 100 ft75p.25
liquid line od mm10p.26
maximum line length 3m minimum room area m23p.26
maximum line length 7 6m3p.26
maximum line length 15 2m4p.26
maximum line length 30 5m7p.26
distributor nozzleL2 part_idp.19
electronic expansion valveE2V24 part_numberp.19
RSV220 part_numberp.19
solenoid valveE3 part_numberp.19
safety solenoid valveSSOV3 part_numberp.19
safety check valveCSOV7 part_numberp.19
fan qty2 countp.6
motor hp0.06666666666666667 hpp.6
motor fla1.2 ampsp.6
total watts120 wattsp.6
1890 wattsp.6
mca1.4 ampsp.6
10.3 ampsp.6
6.7 ampsp.6
10.3 ampsp.9
fan motors standard ec motors mop a15p.6
total amps8.2 ampsp.6
5.3 ampsp.6
defrost heaters 208 230 1 60 mop a15p.6
defrost heaters 208 230 3 60 mop a15p.6
esp circuit 208 230 1 60 mop a15p.9
voltage208 Vp.?
phase1 php.?
frequency60 Hzp.?

Sources: TLP_1112452 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot

Orderable variants (1)

VariantVoltageAvailability
TLP211LE-S2E208-230/1/60Check availability

Nomenclature

Position / meaningValue
capacity code11
defrostE
fan count2
generation suffixE
temp classL
voltageS2

Cross references

BrandEquivalent modelBasis
KeepRiteKLP211LE-S2Eshared catalog stem
BallyBLP211LE-S2Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of TLP211LE-S2E?

TLP211LE-S2E has a rated capacity of 11980 btu_h. See the specifications table for rating conditions.

What voltage does TLP211LE-S2E require?

TLP211LE-S2E runs on 208 V supply power.

Related models in TLP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.