TLP108MA-S2E
Trenton Refrigeration TLP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 7600 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | p.3 |
| 7520 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | p.3 | |
| 7450 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.3 | |
| 7600 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 7520 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 7450 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 6830 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.6 | |
| 6760 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.6 | |
| 6690 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.6 | |
| airflow | 680 cfm | p.3 | |
| 320 l_s | p.3 | ||
| refrigerant charge | 1.3 lb | refrigerant: R454A/R454C/R455A | p.3 |
| (0.6) kg | refrigerant: R454A/R454C/R455A | p.3 | |
| 1.3 lb | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| (0.6) kg | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 1.3 lb | refrigerant: R404A/R507 | p.6 | |
| (0.6) kg | refrigerant: R404A/R507 | p.6 | |
| air flow 30 f 34 c | 680 | evap temp f: 30; refrigerant: R404A/R507 | p.6 |
| air flow 40 f 40 c | 320 | evap temp f: 40; refrigerant: R404A/R507 | p.6 |
| awef rating | 9 ratio | fpi: 6 | p.24 |
| model tlp | TLP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.29 |
| TLP | p.27 | ||
| r454a sporlan ebqte aaa c | EBQTE-AA-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.29 |
| r448a r449a r407a r407c r454c r455a sporlan ebqve aaa c | EBQVE-AA-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.29 |
| r404a r507 sporlan ebqse aa c | EBQSE-A-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.29 |
| unclassified part | TLP part_number | p.31 | |
| liquid line od | 0.375 inches | p.39 | |
| 10 mm | p.40 | ||
| suction line od | 0.625 inches | p.39 | |
| 16 mm | p.40 | ||
| maximum line length 10 ft minimum room area ft | 21 | p.39 | |
| maximum line length 25 ft | 29 | p.39 | |
| maximum line length 50 ft | 42 | p.39 | |
| maximum line length 100 ft | 68 | p.39 | |
| maximum line length 3m minimum room area ft | 2 | p.40 | |
| maximum line length 7 6m | 3 | p.40 | |
| maximum line length 15 2m | 4 | p.40 | |
| maximum line length 30 5m | 6 | p.40 | |
| model n a | N/A | p.27 | |
| shipping weight | 49 lb | p.27 | |
| (22) kg | p.27 | ||
| fan qty | 1 count | p.9 | |
| motor hp | 0.06666666666666667 hp | p.9 | |
| motor fla | 0.6 amps | p.9 | |
| motor watts | 60 watts | p.9 | |
| mca | 0.8 amps | p.9 | |
| mop | 15 amps | p.9 | |
| voltage | 208 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TLP108MA-S2E | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 08 |
| capacity mbh | 8 |
| defrost | A |
| fan count | 1 |
| generation suffix | E |
| temp class | M |
| voltage | S2 |
Parts
7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | L1/2✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E2V24order as E2V24FWBC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Electronic expansion valve | RSV 220✓ | Electronic expansion valve (EEV), KE2 Therm Solutions | - | - | Check availability |
| Safety check valve | CSOV5order as CSOV-5S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV3order as SSOV3S130✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B3✓ | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | - | - | Check availability |
| Solenoid valve | E3order as E3S130✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KLP108MA-S2E | shared catalog stem ✓ |
| Bally | BLP108MA-S2E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TLP108MA-S2E?
TLP108MA-S2E has a rated capacity of 7600 btu_h. See the specifications table for rating conditions.
What voltage does TLP108MA-S2E require?
TLP108MA-S2E runs on 208 V supply power.
Related models in TLP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.