TLP105MA-S2E
Trenton Refrigeration TLP evaporator.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 1 count | p.3 | |
| capacity | 4700 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | p.3 |
| 4650 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | p.3 | |
| 4610 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.3 | |
| 4700 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 4650 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 4610 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 4200 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.6 | |
| 4160 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.6 | |
| 4120 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.6 | |
| airflow | 750 cfm | p.3 | |
| 350 l_s | p.3 | ||
| refrigerant charge | 0.9 lb | refrigerant: R454A/R454C/R455A | p.3 |
| (0.4) kg | refrigerant: R454A/R454C/R455A | p.3 | |
| 0.9 lb | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| (0.4) kg | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 1 lb | refrigerant: R404A/R507 | p.6 | |
| (0.4) kg | refrigerant: R404A/R507 | p.6 | |
| air flow 30 f 34 c | 750 | evap temp f: 30; refrigerant: R404A/R507 | p.6 |
| air flow 40 f 40 c | 350 | evap temp f: 40; refrigerant: R404A/R507 | p.6 |
| awef rating | 9 ratio | fpi: 6 | p.24 |
| liquid line od | 0.375 inches | p.39 | |
| 10 mm | p.40 | ||
| suction line od | 0.625 inches | p.39 | |
| 16 mm | p.40 | ||
| maximum line length 10 ft minimum room area ft | 17 | p.39 | |
| maximum line length 25 ft | 25 | p.39 | |
| maximum line length 50 ft | 38 | p.39 | |
| maximum line length 100 ft | 64 | p.39 | |
| maximum line length 3m minimum room area ft | 2 | p.40 | |
| maximum line length 7 6m | 2 | p.40 | |
| maximum line length 15 2m | 4 | p.40 | |
| maximum line length 30 5m | 6 | p.40 | |
| fpi | 6 | p.9 | |
| motor hp | 0.06666666666666667 hp | p.9 | |
| motor fla | 0.6 amps | p.9 | |
| motor watts | 60 watts | p.9 | |
| mca | 0.8 amps | p.9 | |
| mop | 15 amps | p.9 | |
| voltage | 208 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TLP105MA-S2E | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 05 |
| capacity mbh | 5 |
| defrost | A |
| fan count | 1 |
| generation suffix | E |
| temp class | M |
| voltage | S2 |
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KLP105MA-S2E | shared catalog stem ✓ |
| Bally | BLP105MA-S2E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TLP105MA-S2E?
TLP105MA-S2E has a rated capacity of 4700 btu_h. See the specifications table for rating conditions.
What voltage does TLP105MA-S2E require?
TLP105MA-S2E runs on 208 V supply power.
Related models in TLP