Trenton Refrigeration · TLP · Low Profile Evaporatorsavailable Options
TLP105LE-T3D
Trenton Refrigeration TLP low profile savailable option evaporator.
50 extracted specifications, each traceable to its source document and page.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 5190 btu_h | evap temp f: 0 | p.3 |
| 5050 btu_h | evap temp f: 10 | p.3 | |
| 4900 btu_h | evap temp f: 20 | p.3 | |
| 4510 btu_h | evap temp f: 30 | p.3 | |
| 4170 btu_h | evap temp f: 40 | p.3 | |
| airflow | 705 cfm | p.3 | |
| 330 l_s | p.3 | ||
| refrigerant charge | 1.1 lb | p.3 | |
| (0.5) kg | p.3 | ||
| awef rating | 3.97 ratio | refrigerant: R454A | p.16 |
| 3.97 ratio | refrigerant: R454C | p.16 | |
| 3.97 ratio | refrigerant: R455A | p.16 | |
| liquid line od in | 0.375 | p.25 | |
| suction od | 0.625 inches | p.25 | |
| 16 inches | p.26 | ||
| maximum line length 10 ft minimum room area ft2 | 18 | p.25 | |
| maximum line length 25 ft | 26 | p.25 | |
| maximum line length 50 ft | 39 | p.25 | |
| maximum line length 100 ft | 65 | p.25 | |
| liquid line od mm | 10 | p.26 | |
| maximum line length 3m minimum room area m2 | 2 | p.26 | |
| maximum line length 7 6m | 2 | p.26 | |
| maximum line length 15 2m | 4 | p.26 | |
| maximum line length 30 5m | 6 | p.26 | |
| distributor nozzle | L3/4 part_id | p.19 | |
| electronic expansion valve | E2V24 part_number | p.19 | |
| RSV220 part_number | p.19 | ||
| solenoid valve | E3 part_number | p.19 | |
| safety solenoid valve | SSOV3 part_number | p.19 | |
| safety check valve | CSOV5 part_number | p.19 | |
| fan qty | 1 count | p.6 | |
| motor hp | 0.06666666666666667 hp | p.6 | |
| motor fla | 0.6 amps | p.6 | |
| total watts | 60 watts | p.6 | |
| 1060 watts | p.6 | ||
| mca | 0.8 amps | p.6 | |
| 5.8 amps | p.6 | ||
| 3.8 amps | p.6 | ||
| fan motors standard ec motors mop a | 15 | p.6 | |
| total amps | 4.6 amps | p.6 | |
| 3 amps | p.6 | ||
| defrost heaters 208 230 1 60 mop a | 15 | p.6 | |
| defrost heaters 208 230 3 60 mop a | 15 | p.6 | |
| voltage 208 230 1 60 | 208-230/3/60 | p.32 | |
| 1 x evaporator defrost kit dfk 02 | DFK-03 | p.32 | |
| 1 x evaporator fuse package fp 004 | FP-013 | p.32 | |
| 2 x evaporator fuse package fp 008 | FP-018 | p.32 | |
| voltage | 208 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: TLP_1112452 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| TLP105LE-T3D | 208-230/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 05 |
| defrost | E |
| fan count | 1 |
| generation suffix | D |
| temp class | L |
| voltage | T3 |
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KLP105LE-T3D | shared catalog stem ✓ |
| Bally | BLP105LE-T3D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of TLP105LE-T3D?
TLP105LE-T3D has a rated capacity of 5190 btu_h. See the specifications table for rating conditions.
What voltage does TLP105LE-T3D require?
TLP105LE-T3D runs on 208 V supply power.
Related models in TLP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.