THP250ME-T3D
Trenton Refrigeration THP high profile evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 250000 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | p.4 |
| 247500 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | p.4 | |
| 245000 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | p.4 | |
| 203000 btu_h | evap temp f: 25; refrigerant: R404A/R507 | p.4 | |
| 201000 btu_h | evap temp f: 15; refrigerant: R404A/R507 | p.4 | |
| 198900 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.4 | |
| 250000 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | p.4 | |
| 247500 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | p.4 | |
| 245000 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.4 | |
| airflow | 22700 cfm | p.4 | |
| 10710 l_s | p.4 | ||
| refrigerant charge | 58.3 lb | refrigerant: R407A/R407C | p.4 |
| 26.5 kg | refrigerant: R407A/R407C | p.4 | |
| 53.7 lb | refrigerant: R404A/R507 | p.4 | |
| 24.4 kg | refrigerant: R404A/R507 | p.4 | |
| 41.1 lb | refrigerant: R454A/R454C/R455A | p.4 | |
| 18.6 kg | refrigerant: R454A/R454C/R455A | p.4 | |
| 56 lb | refrigerant: R448A/R449A | p.4 | |
| 25.4 kg | refrigerant: R448A/R449A | p.4 | |
| awef rating | 9 ratio | refrigerant: R404A/R507 | p.28 ✓ |
| 9 ratio | refrigerant: R448A/R449A | p.28 | |
| 9 ratio | refrigerant: R407C/R407A | p.28 | |
| 9 ratio | refrigerant: R454A | p.28 | |
| 9 ratio | refrigerant: R454C | p.28 | |
| 9 ratio | refrigerant: R455A | p.28 | |
| suction od | 2-5/8 inches | p.31 | |
| distributor inlet | 1 5/8 inches | p.31 | |
| 1 5/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 | |
| side port connection | 1-5/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| hot gas connection | 1-5/8 inches | p.31 | |
| shipping weight | 1266 lb | p.32 | |
| 574 kg | p.32 | ||
| fan qty | 4 count | p.8 ✓ | |
| motor hp | 1 hp | p.8 | |
| motor fla | 20 amps | p.8 | |
| total watts | 2240 wattssources differ | THP p.8 | |
| 45500 wattssources differ | THP p.8 | ||
| mca | 25 ampssources differ | THP p.8 | |
| 53.9 ampssources differ | THP p.8 | ||
| 42.9 ampssources differ | THP p.8 | ||
| 150.7 ampssources differ | THP p.14 | ||
| mop | 30 amps | p.8 | |
| total amps | 43.1 ampssources differ | THP p.8 | |
| 34.3 ampssources differ | THP p.8 | ||
| defrost heaters 208 230 1 60 circuit 1 mop a | 60 | p.8 | |
| defrost heaters 208 230 3 60 circut 2 mop a | 60 | p.8 | |
| defrost heaters 208 230 3 60 circut 3 mop a | 45 | p.8 | |
| esp circuit 208 230 3 60 mop a | 175 | p.14 | |
| voltage | 208 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP250ME-T3D | 208-230/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 250 |
| capacity mbh | 250 |
| defrost | E |
| generation suffix | D |
| temp class | M |
| voltage | T3 |
Parts
7 factory parts for this unit: 7from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | A30✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V65order as E3V65BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV21order as CSOV-21S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV25✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B25order as B25S2✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Defrost and drain pan
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Defrost field kit | DFK-46✓ | Defrost kit (1-evap install), 208-230/3/60 | - | - | Check availability |
| Fuse package | FP-086✓ | Fuse package (1-evap install), 208-230/3/60 | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP250ME-T3D | shared catalog stem ✓ |
| Bally | BHP250ME-T3D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP250ME-T3D?
THP250ME-T3D has a rated capacity of 250000 btu_h. See the specifications table for rating conditions.
What voltage does THP250ME-T3D require?
THP250ME-T3D runs on 208 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.