THP242HA-S4E
Trenton Refrigeration THP evaporator.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 4 count | p.3 | |
| capacity | 241600 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | p.3 |
| 239200 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | p.3 | |
| 236800 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.3 | |
| 241600 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 239200 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 236800 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 196400 btu_h | evap temp f: 25; refrigerant: R404A/R507 | p.7 | |
| 194400 btu_h | evap temp f: 15; refrigerant: R404A/R507 | p.7 | |
| 192500 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.7 | |
| airflow | 23500 cfm | p.3 | |
| 11090 l_s | p.3 | ||
| refrigerant charge | 33.5 lb | refrigerant: R454A/R454C/R455A | p.3 |
| 15.2 kg | refrigerant: R454A/R454C/R455A | p.3 | |
| 46.7 lb | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 21.2 kg | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 34.8 lb | refrigerant: R404A/R507 | p.7 | |
| 15.8 kg | refrigerant: R404A/R507 | p.7 | |
| awef rating | 9 ratio | refrigerant: R404A/R507/R448A/R449A/R407C/R407A | p.31 |
| 9 ratio | refrigerant: R454A/R454C/R455A | p.31 | |
| r454a sporlan ebste 8 c | OTE-30-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.39 |
| r448a r449a r407a r407c r454c r455a sporlan ebsve 8 c | OVE-30-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.39 |
| r404a r507 sporlan ebsse 6 c | OSE-21-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.39 |
| liquid line od | 1 1/8 inches | p.49 | |
| 29 mm | p.50 | ||
| suction line od | 2 5/8 inches | p.49 | |
| 67 mm | p.50 | ||
| maximum line length a 10 ft minimum room area ft2 | 466 | p.49 | |
| maximum line length b 25 ft | 552* | p.49 | |
| maximum line length c 50 ft | 696* | p.49 | |
| maximum line length d 100 ft | 984* | p.49 | |
| maximum line length a 3m minimum room area m2 | 43 | p.50 | |
| maximum line length b 7 6m | 51* | p.50 | |
| maximum line length c 15 2m | 65* | p.50 | |
| maximum line length d 30 5m | 91* | p.50 | |
| suction od | 2 5/8 inches | p.34 | |
| distributor inlet | 1 5/8 inches | p.34 | |
| motor hp | 1 hp | p.9 | |
| motor fla | 10 amps | p.9 | |
| motor watts | 2080 watts | p.9 | |
| mca | 15 amps | p.9 | |
| mop | 20 amps | p.9 | |
| esp circuit mca | 15 amps | p.16 | |
| esp circuit 460 1 60 mop a | 20 | p.16 | |
| voltage | 460 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP242HA-S4E | 460/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 242 |
| capacity mbh | 242 |
| defrost | A |
| generation suffix | E |
| temp class | H |
| voltage | S4 |
Parts
1 factory parts for this unit: 1from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Solenoid valve | B19order as B19S2-7/8✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP242HA-S4E | shared catalog stem ✓ |
| Bally | BHP242HA-S4E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP242HA-S4E?
THP242HA-S4E has a rated capacity of 241600 btu_h. See the specifications table for rating conditions.
What voltage does THP242HA-S4E require?
THP242HA-S4E runs on 460 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.