THP227ME-T3E

Trenton Refrigeration THP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
fan qty4 countTHP + THP-GEN-E p.4
capacity227200 btu_hTHP + THP-GEN-E p.4
224900 btu_hTHP + THP-GEN-E p.4
222700 btu_hTHP + THP-GEN-E p.4
184700 btu_hTHP + THP-GEN-E p.4
182900 btu_hTHP + THP-GEN-E p.4
181000 btu_hTHP + THP-GEN-E p.4
227200 btu_hTHP + THP-GEN-E p.4
224900 btu_hTHP + THP-GEN-E p.4
222700 btu_hTHP + THP-GEN-E p.4
airflow23900 cfmTHP + THP-GEN-E p.4
11280 l_sTHP + THP-GEN-E p.4
refrigerant charge46.7 lbp.4
21.2 kgp.4
42.9 lbsources differTHP p.4
34.8 lbsources differTHP-GEN-E p.7
19.5 kgsources differTHP p.4
15.8 kgsources differTHP-GEN-E p.7
33.4 lbsources differTHP p.4
33.5 lbsources differTHP-GEN-E p.3
15.1 kgsources differTHP p.4
15.2 kgsources differTHP-GEN-E p.3
44.8 lbp.4
20.4 kgp.4
46.7 lbp.5
21.2 kgp.5
awef rating9 ratiop.28
9 ratiop.28
9 ratiop.28
9 ratiop.28
9 ratiop.28
9 ratiop.28
9 ratiop.31
9 ratiop.31
suction od2-5/8 inchessources differTHP p.31
3 1/8 inchessources differTHP-GEN-E p.34
distributor inlet1 5/8 inchesTHP + THP-GEN-E p.31
1 5/8 inchesp.31
side port connection1-5/8 inchesp.31
1-5/8 inchesp.36
hot gas connection1-5/8 inchesp.31
shipping weight1181 lbTHP + THP-GEN-E p.32
536 kgTHP + THP-GEN-E p.32
mca107.2 ampssources differTHP p.14
25 ampssources differTHP-GEN-E p.10
53.6 ampssources differTHP-GEN-E p.10
- ampssources differTHP-GEN-E p.10
esp circuit 208 230 3 60 mop a125THP + THP-GEN-E p.14
voltage208 VTHP + THP-GEN-E p.?
phase3 phTHP + THP-GEN-E p.?
frequency60 HzTHP + THP-GEN-E p.?
drain pan loop conn od sweat 1 3 81-5/8p.36
r454a sporlan ebste 8 cOTE-30-Cp.39
r448a r449a r407a r407c r454c r455a sporlan ebsve 8 cOVE-30-Cp.39
r404a r507 sporlan ebsse 6 cOSE-21-Cp.39
liquid line od1 1/8 inchesp.49
29 mmp.50
suction line od2 5/8 inchesp.49
67 mmp.50
maximum line length a 10 ft minimum room area ft2466p.49
maximum line length b 25 ft552*p.49
maximum line length c 50 ft696*p.49
maximum line length d 100 ft984*p.49
maximum line length a 3m minimum room area m243p.50
maximum line length b 7 6m51*p.50
maximum line length c 15 2m65*p.50
maximum line length d 30 5m91*p.50
motor hp1 hpp.10
motor fla20 ampsp.10
motor watts2240 wattsp.10
mop30 ampsp.10
total watts31850 wattsp.10
total amps42.9 ampssources differTHP-GEN-E p.10
- ampssources differTHP-GEN-E p.10
defrost heaters circuit 1 208 230 3 60 mop a60p.10
defrost heaters circuit 2 208 230 3 60 mop a60p.10
defrost heaters circuit 3 208 230 3 60 mop a-p.10
esp circuit mca107.2 ampsp.16
of fans 14p.56

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including THP_1111525, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including THP-GEN-E_1112936, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
THP227ME-T3E208-230/3/60Check availability

Nomenclature

Position / meaningValue
capacity code227
capacity mbh227
defrostE
generation suffixE
temp classM
voltageT3

Parts

5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

PartPart numberQtyListAvailability
Distributor nozzleA25--Check availability
Electronic expansion valveE3V65order as E3V65BWRC1--Check availability
Safety check valveCSOV21order as CSOV-21S--Check availability
Safety shutoff solenoidSSOV25--Check availability
Solenoid valveB19order as B19S2-7/8--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKHP227ME-T3Eshared catalog stem
BallyBHP227ME-T3Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of THP227ME-T3E?

THP227ME-T3E has a rated capacity of 227200 btu_h. See the specifications table for rating conditions.

What voltage does THP227ME-T3E require?

THP227ME-T3E runs on 208 V supply power.

Related models in THP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.