THP211LH-S2D
Trenton Refrigeration THP high profile evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 223700 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | p.5 |
| 217300 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | p.5 | |
| 211000 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | p.5 | |
| 192000 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | p.5 | |
| 179400 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | p.5 | |
| 182000 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.5 | |
| 176900 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.5 | |
| 171700 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.5 | |
| 156200 btu_h | evap temp f: 30; refrigerant: R404A/R507 | p.5 ✓ | |
| 145900 btu_h | evap temp f: 40; refrigerant: R404A/R507 | p.5 | |
| 223700 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | p.5 | |
| 217300 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.5 | |
| 211000 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | p.5 | |
| 192000 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | p.5 | |
| 179400 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | p.5 | |
| airflow | 22700 cfm | p.5 | |
| 10710 l_s | p.5 | ||
| refrigerant charge | 62.4 lb | refrigerant: R407A | p.5 |
| 28.3 kg | refrigerant: R407A | p.5 | |
| 57.4 lb | refrigerant: R404A/R507 | p.5 | |
| 26.1 kg | refrigerant: R404A/R507 | p.5 | |
| 40.1 lb | refrigerant: R454A/R454C/R455A | p.5 | |
| 18.2 kg | refrigerant: R454A/R454C/R455A | p.5 | |
| 59.9 lb | refrigerant: R448A/R449A | p.5 | |
| 27.2 kg | refrigerant: R448A/R449A | p.5 | |
| awef rating | 4.15 ratio | refrigerant: R404A/R507 | p.28 ✓ |
| 4.15 ratio | refrigerant: R448A/R449A | p.28 | |
| 4.15 ratio | refrigerant: R407C/R407A | p.28 | |
| 4.15 ratio | refrigerant: R454A | p.28 | |
| 4.15 ratio | refrigerant: R454C | p.28 | |
| 4.15 ratio | refrigerant: R455A | p.28 | |
| suction od | 3-1/8 inches | p.31 | |
| distributor inlet | 1 5/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| side port connection | 1-5/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| hot gas connection | 1-5/8 inchessources differ | THP p.31 | |
| 211LR inchessources differ | THP p.32 | ||
| 623 inchessources differ | THP p.32 | ||
| 1372 lb | p.32 | ||
| motor hp | 211LG hpsources differ | THP p.32 | |
| 211LT hpsources differ | THP p.32 | ||
| 1 hpsources differ | THP p.12 | ||
| shipping weight | 1279 lb | p.32 | |
| 580 kg | p.32 | ||
| fan qty | 4 count | p.12 ✓ | |
| motor fla | 20 amps | p.12 | |
| total watts | 2240 watts | p.12 | |
| mca | 25 amps | p.12 | |
| mop | 30 amps | p.12 | |
| voltage | 208 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP211LH-S2D | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 211 |
| capacity mbh | 211 |
| defrost | H |
| generation suffix | D |
| temp class | L |
| voltage | S2 |
Parts
5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | A50✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V65order as E3V65BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV25✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV25✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B19order as B19S2-7/8✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP211LH-S2D | shared catalog stem ✓ |
| Bally | BHP211LH-S2D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP211LH-S2D?
THP211LH-S2D has a rated capacity of 223700 btu_h. See the specifications table for rating conditions.
What voltage does THP211LH-S2D require?
THP211LH-S2D runs on 208 V supply power.
Related models in THP