THP190VH-S4D
Trenton Refrigeration THP high profile evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 201400 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | p.6 |
| 195700 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | p.6 | |
| 190000 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | p.6 | |
| 172900 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | p.6 | |
| 161500 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | p.6 | |
| 163800 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.6 | |
| 159100 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.6 | |
| 154500 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.6 ✓ | |
| 140600 btu_h | evap temp f: 30; refrigerant: R404A/R507 | p.6 | |
| 131300 btu_h | evap temp f: 40; refrigerant: R404A/R507 | p.6 ✓ | |
| 201400 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | p.6 | |
| 195700 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.6 | |
| 190000 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | p.6 | |
| 172900 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | p.6 | |
| 161500 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | p.6 | |
| airflow | 23500 cfm | p.6 | |
| 11090 l_s | p.6 | ||
| refrigerant charge | 62.4 lb | refrigerant: R407A | p.6 |
| 28.3 kg | refrigerant: R407A | p.6 | |
| 57.4 lb | refrigerant: R404A/R507 | p.6 | |
| 26.1 kg | refrigerant: R404A/R507 | p.6 | |
| 40.1 lb | refrigerant: R454A/R454C/R455A | p.6 | |
| 18.2 kg | refrigerant: R454A/R454C/R455A | p.6 | |
| 59.9 lb | refrigerant: R448A/R449A | p.6 | |
| 27.2 kg | refrigerant: R448A/R449A | p.6 | |
| awef rating | 4.15 ratio | refrigerant: R404A/R507 | p.28 ✓ |
| 4.15 ratio | refrigerant: R448A/R449A | p.28 | |
| 4.15 ratio | refrigerant: R407C/R407A | p.28 | |
| 4.15 ratio | refrigerant: R454A | p.28 | |
| 4.15 ratio | refrigerant: R454C | p.28 | |
| 4.15 ratio | refrigerant: R455A | p.28 | |
| suction od | 3-1/8 inches | p.31 | |
| distributor inlet | 1 5/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| side port connection | 1-5/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| hot gas connection | 1-5/8 inchessources differ | THP p.31 | |
| 190VR inchessources differ | THP p.32 | ||
| 594 inchessources differ | THP p.32 | ||
| 1310 lb | p.32 | ||
| motor hp | 190VG hpsources differ | THP p.32 | |
| 190VT hpsources differ | THP p.32 | ||
| 1 hpsources differ | THP p.12 | ||
| shipping weight | 1310 lb | p.32 | |
| 594 kg | p.32 | ||
| fan qty | 4 count | p.12 ✓ | |
| motor fla | 10 amps | p.12 | |
| total watts | 2080 watts | p.12 | |
| mca | 15 amps | p.12 | |
| mop | 20 amps | p.12 | |
| voltage | 460 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP190VH-S4D | 460/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 190 |
| capacity mbh | 190 |
| defrost | H |
| generation suffix | D |
| temp class | V |
| voltage | S4 |
Parts
5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | A40✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V65order as E3V65BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV25✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV25✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B19order as B19S2-7/8✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP190VH-S4D | shared catalog stem ✓ |
| Bally | BHP190VH-S4D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP190VH-S4D?
THP190VH-S4D has a rated capacity of 201400 btu_h. See the specifications table for rating conditions.
What voltage does THP190VH-S4D require?
THP190VH-S4D runs on 460 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.