THP186ME-T4D
Trenton Refrigeration THP high profile evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 186200 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | p.4 |
| 184300 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | p.4 | |
| 182500 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | p.4 | |
| 151400 btu_h | evap temp f: 25; refrigerant: R404A/R507 | p.4 | |
| 149900 btu_h | evap temp f: 15; refrigerant: R404A/R507 | p.4 | |
| 148400 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.4 | |
| 186200 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | p.4 | |
| 184300 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | p.4 | |
| 182500 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.4 | |
| airflow | 17000 cfm | p.4 | |
| 8020 l_s | p.4 | ||
| refrigerant charge | 44 lb | refrigerant: R407A/R407C | p.4 |
| 20 kg | refrigerant: R407A/R407C | p.4 | |
| 40.5 lb | refrigerant: R404A/R507 | p.4 | |
| 18.4 kg | refrigerant: R404A/R507 | p.4 | |
| 31 lb | refrigerant: R454A/R454C/R455A | p.4 | |
| 14 kg | refrigerant: R454A/R454C/R455A | p.4 | |
| 42.2 lb | refrigerant: R448A/R449A | p.4 | |
| 19.2 kg | refrigerant: R448A/R449A | p.4 | |
| awef rating | 9 ratio | refrigerant: R404A/R507 | p.28 ✓ |
| 9 ratio | refrigerant: R448A/R449A | p.28 | |
| 9 ratio | refrigerant: R407C/R407A | p.28 | |
| 9 ratio | refrigerant: R454A | p.28 | |
| 9 ratio | refrigerant: R454C | p.28 | |
| 9 ratio | refrigerant: R455A | p.28 | |
| suction od | 2-1/8 inches | p.31 | |
| distributor inlet | 1 5/8 inches | p.31 | |
| 1 5/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 | |
| side port connection | 1-3/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| hot gas connection | 1-5/8 inches | p.31 | |
| shipping weight | 973 lb | p.32 | |
| 441 kg | p.32 | ||
| fan qty | 3 count | p.9 ✓ | |
| motor hp | 1 hp | p.9 | |
| motor fla | 7.5 amps | p.9 | |
| total watts | 1560 wattssources differ | THP p.9 | |
| 35000 wattssources differ | THP p.9 | ||
| mca | 15 ampssources differ | THP p.9 | |
| 57.9 ampssources differ | THP p.9 | ||
| - ampssources differ | THP p.9 | ||
| mop | 20 amps | p.9 | |
| total amps | 46.3 ampssources differ | THP p.9 | |
| - ampssources differ | THP p.9 | ||
| defrost heaters 460 3 60 circuit 1 mop a | 60 | p.9 | |
| defrost heaters 460 3 60 circut 2 mop a | - | p.9 | |
| esp circuit 460 3 60 mop a | 60 | p.14 | |
| voltage | 460 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP186ME-T4D | 460/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 186 |
| capacity mbh | 186 |
| defrost | E |
| generation suffix | D |
| temp class | M |
| voltage | T4 |
Parts
9 factory parts for this unit: 9from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | A20✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V65order as E3V65BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV17order as CSOV-17S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV19✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B19order as B19S2-7/8✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Defrost and drain pan
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Defrost field kit | DFK-22✓ | Defrost kit (1-evap install), 460/3/60 | - | - | Check availability |
| Defrost field kit | DFK-33✓ | Defrost kit (2-evap install), 460/3/60 | - | - | Check availability |
| Fuse package | FP-025✓ | Fuse package (2-evap install), 460/3/60 | - | - | Check availability |
| Fuse package | FP-074✓ | Fuse package (1-evap install), 460/3/60 | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP186ME-T4D | shared catalog stem ✓ |
| Bally | BHP186ME-T4D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP186ME-T4D?
THP186ME-T4D has a rated capacity of 186200 btu_h. See the specifications table for rating conditions.
What voltage does THP186ME-T4D require?
THP186ME-T4D runs on 460 V supply power.
Related models in THP