THP168ME-T4E
Trenton Refrigeration THP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 168300 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | THP + THP-GEN-E p.4 ✓ |
| 166600 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | THP + THP-GEN-E p.4 ✓ | |
| 164900 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | THP + THP-GEN-E p.4 ✓ | |
| 136800 btu_h | evap temp f: 25; refrigerant: R404A/R507 | THP + THP-GEN-E p.4 ✓ | |
| 135400 btu_h | evap temp f: 15; refrigerant: R404A/R507 | THP + THP-GEN-E p.4 ✓ | |
| 134100 btu_h | evap temp f: 10; refrigerant: R404A/R507 | THP + THP-GEN-E p.4 ✓ | |
| 168300 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | THP + THP-GEN-E p.4 ✓ | |
| 166600 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | THP + THP-GEN-E p.4 ✓ | |
| 164900 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | THP + THP-GEN-E p.4 ✓ | |
| airflow | 18000 cfm | THP + THP-GEN-E p.4 ✓ | |
| 8500 l_s | THP + THP-GEN-E p.4 ✓ | ||
| refrigerant charge | 35.2 lb | refrigerant: R407A/R407C | p.4 |
| 16 kg | refrigerant: R407A/R407C | p.4 | |
| 32.3 lbsources differ | refrigerant: R404A/R507 | THP p.4 | |
| 26.1 lbsources differ | refrigerant: R404A/R507 | THP-GEN-E p.7 | |
| 14.7 kgsources differ | refrigerant: R404A/R507 | THP p.4 | |
| 11.9 kgsources differ | refrigerant: R404A/R507 | THP-GEN-E p.7 | |
| 25.1 lb | refrigerant: R454A/R454C/R455A | THP + THP-GEN-E p.4 ✓ | |
| 11.4 kg | refrigerant: R454A/R454C/R455A | THP + THP-GEN-E p.4 ✓ | |
| 33.8 lb | refrigerant: R448A/R449A | p.4 | |
| 15.4 kg | refrigerant: R448A/R449A | p.4 | |
| 35.2 lb | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 16 kg | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| awef rating | 9 ratio | refrigerant: R404A/R507 | p.28 ✓ |
| 9 ratio | refrigerant: R448A/R449A | p.28 | |
| 9 ratio | refrigerant: R407C/R407A | p.28 | |
| 9 ratio | refrigerant: R454A | p.28 | |
| 9 ratio | refrigerant: R454C | p.28 | |
| 9 ratio | refrigerant: R455A | p.28 | |
| 9 ratio | refrigerant: R404A/R507/R448A/R449A/R407C/R407A | p.31 | |
| 9 ratio | refrigerant: R454A/R454C/R455A | p.31 | |
| suction od | 2-1/8 inchessources differ | THP p.31 | |
| 2 5/8 inchessources differ | THP-GEN-E p.34 | ||
| distributor inlet | 1 5/8 inches | THP + THP-GEN-E p.31 ✓ | |
| 1 5/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 | |
| side port connection | 1-3/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| 1-3/8 inches | p.36 | ||
| hot gas connection | 1-5/8 inches | p.31 | |
| shipping weight | 909 lb | THP + THP-GEN-E p.32 ✓ | |
| 412 kg | THP + THP-GEN-E p.32 ✓ | ||
| mca | 41.5 ampssources differ | THP p.14 | |
| 15 ampssources differ | THP-GEN-E p.11 | ||
| 41.5 ampssources differ | THP-GEN-E p.11 | ||
| - ampssources differ | THP-GEN-E p.11 | ||
| esp circuit 460 3 60 mop a | 45 | THP + THP-GEN-E p.14 ✓ | |
| voltage | 460 V | THP + THP-GEN-E p.? ✓ | |
| phase | 3 ph | THP + THP-GEN-E p.? ✓ | |
| frequency | 60 Hz | THP + THP-GEN-E p.? ✓ | |
| fan qty | 3 count | p.34 | |
| drain pan loop conn od sweat 1 3 8 | 1-5/8 | p.36 | |
| r454a sporlan ebste 8 c | OTE-20-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.39 |
| r448a r449a r407a r407c r454c r455a sporlan ebsve 8 c | OVE-20-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.39 |
| r404a r507 sporlan ebsse 6 c | OSE-21-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.39 |
| liquid line od | 0.875 inches | p.49 | |
| 22 mm | p.50 | ||
| suction line od | 2 1/8 inches | p.49 | |
| 54 mm | p.50 | ||
| maximum line length a 10 ft minimum room area ft2 | 341 | p.49 | |
| maximum line length b 25 ft | 392 | p.49 | |
| maximum line length c 50 ft | 477 | p.49 | |
| maximum line length d 100 ft | 648* | p.49 | |
| maximum line length a 3m minimum room area m2 | 32 | p.50 | |
| maximum line length b 7 6m | 36 | p.50 | |
| maximum line length c 15 2m | 44 | p.50 | |
| maximum line length d 30 5m | 60* | p.50 | |
| motor hp | 1 hp | p.11 | |
| motor fla | 7.5 amps | p.11 | |
| motor watts | 1560 watts | p.11 | |
| mop | 20 amps | p.11 | |
| total watts | 24500 watts | p.11 | |
| total amps | 33.2 ampssources differ | THP-GEN-E p.11 | |
| - ampssources differ | THP-GEN-E p.11 | ||
| defrost heaters circuit 1 460 3 60 mop a | 45 | p.11 | |
| defrost heaters circuit 2 460 3 60 mop a | - | p.11 | |
| esp circuit mca | 41.5 amps | p.16 | |
| of fans 1 | 3 | p.56 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP168ME-T4E | 460/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 168 |
| capacity mbh | 168 |
| defrost | E |
| generation suffix | E |
| temp class | M |
| voltage | T4 |
Parts
5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | A20✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V65order as E3V65BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV17order as CSOV-17S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV19✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B19order as B19S2-7/8✓ | Solenoid valve; Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP168ME-T4E | shared catalog stem ✓ |
| Bally | BHP168ME-T4E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP168ME-T4E?
THP168ME-T4E has a rated capacity of 168300 btu_h. See the specifications table for rating conditions.
What voltage does THP168ME-T4E require?
THP168ME-T4E runs on 460 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.