THP165DE-T4D
Trenton Refrigeration THP high profile evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 142100 btu_h | evap temp f: 0; refrigerant: CO2 | p.36 |
| 138100 btu_h | evap temp f: 10; refrigerant: CO2 | p.36 | |
| 134100 btu_h | evap temp f: 20; refrigerant: CO2 | p.36 | |
| 122000 btu_h | evap temp f: 30; refrigerant: CO2 | p.36 ✓ | |
| 114000 btu_h | evap temp f: 40; refrigerant: CO2 | p.36 | |
| airflow | 17000 cfm | p.36 | |
| 8020 l_s | p.36 | ||
| refrigerant charge | 37 lb | refrigerant: CO2 | p.36 |
| 16.8 kg | refrigerant: CO2 | p.36 | |
| awef rating | 4.15 ratio | refrigerant: CO2 | p.41 ✓ |
| suction od | 1 1/8 inches | p.45 | |
| distributor inlet | 1 1/8 inches | defrost piping: reverse_cycle | p.45 |
| 1 1/8 inches | p.44 | ||
| liquid line od | 0.875 inches | defrost piping: reverse_cycle | p.45 |
| 0.875 inches | p.44 | ||
| side port connection | 0.625 inches | p.45 | |
| hot gas connection | 1 1/8 inches | p.45 | |
| shipping weight | 973 lb | p.46 | |
| 441 kg | p.46 | ||
| fan qty | 3 count | p.38 ✓ | |
| motor hp | 1 hp | p.38 | |
| motor fla | 7.5 amps | p.38 | |
| total watts | 1560 wattssources differ | THP p.38 | |
| 35000 wattssources differ | THP p.38 | ||
| mca | 15 ampssources differ | THP p.38 | |
| 57.9 ampssources differ | THP p.38 | ||
| - ampssources differ | THP p.38 | ||
| mop | 20 amps | p.38 | |
| total amps | 46.3 ampssources differ | THP p.38 | |
| - ampssources differ | THP p.38 | ||
| defrost heaters 460 3 60 circuit 1 mop a | 60 | p.38 | |
| defrost heaters 460 3 60 circut 2 mop a | - | p.38 | |
| voltage | 460 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP165DE-T4D | 460/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 165 |
| capacity mbh | 165 |
| defrost | E |
| generation suffix | D |
| temp class | D |
| voltage | T4 |
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP165DE-T4D | shared catalog stem ✓ |
| Bally | BHP165DE-T4D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP165DE-T4D?
THP165DE-T4D has a rated capacity of 142100 btu_h. See the specifications table for rating conditions.
What voltage does THP165DE-T4D require?
THP165DE-T4D runs on 460 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.