Trenton Refrigeration · THP · High Profile Evaporators
THP147VE-T4E
Trenton Refrigeration THP high profile evaporator.
52 extracted specifications, each traceable to its source document and page.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 155900 btu_h | evap temp f: 0 | p.6 |
| 151500 btu_h | evap temp f: 10 | p.6 | |
| 147100 btu_h | evap temp f: 20 | p.6 | |
| 133900 btu_h | evap temp f: 30 | p.6 | |
| 125000 btu_h | evap temp f: 40 | p.6 | |
| 126800 btu_h | evap temp f: 0 | p.6 | |
| 123200 btu_h | evap temp f: 10 | p.6 | |
| 119600 btu_h | evap temp f: 20 | p.6 | |
| 108800 btu_h | evap temp f: 30 | p.6 | |
| 101700 btu_h | evap temp f: 40 | p.6 | |
| 155900 btu_h | evap temp f: 0 | p.6 | |
| 151500 btu_h | evap temp f: 10 | p.6 | |
| 147100 btu_h | evap temp f: 20 | p.6 | |
| 133900 btu_h | evap temp f: 30 | p.6 | |
| 125000 btu_h | evap temp f: 40 | p.6 | |
| airflow | 17600 cfm | p.6 | |
| 8310 l_s | p.6 | ||
| 17600 cfm | p.6 | ||
| 8310 l_s | p.6 | ||
| 17600 cfm | p.6 | ||
| 8310 l_s | p.6 | ||
| refrigerant charge | 47 lb | p.6 | |
| 21.4 kg | p.6 | ||
| 43.2 lb | p.6 | ||
| 19.6 kg | p.6 | ||
| 30.3 lb | p.6 | ||
| 13.7 kg | p.6 | ||
| r404a r507 | 4.15 | p.28 | |
| r448a r449a | 4.15 | p.28 | |
| r407c r407a | 4.15 | p.28 | |
| awef rating | 4.15 ratio | refrigerant: R454A | p.28 |
| 4.15 ratio | refrigerant: R454C | p.28 | |
| 4.15 ratio | refrigerant: R455A | p.28 | |
| suction od | 2-5/8 inches | p.31 | |
| 2-5/8 inches | p.31 | ||
| distributor inlet | 1 5/8 inches | p.31 | |
| 1 5/8 inches | p.31 | ||
| reverse cycle 3 pipe defrost side port connection od sweat | 1-3/8 | p.31 | |
| hot gas connection | 1-5/8 inches | p.31 | |
| distributor nozzle | A30 part_id | p.33 | |
| A30 part_id | p.35 | ||
| electronic expansion valve | E3V65 part_number | p.35 | |
| solenoid valve | B19 part_number | p.35 | |
| safety solenoid valve | SSOV19 part_number | p.35 | |
| safety check valve | CSOV21 part_number | p.35 | |
| shipping weight | 926 lb | p.32 | |
| 420 kg | p.32 | ||
| mca | 57.9 amps | p.14 | |
| esp circuit 460 3 60 mop a | 60 | p.14 | |
| voltage | 460 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: THP_1111525 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP147VE-T4E | 460/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 47 |
| defrost | E |
| fan count | 1 |
| generation suffix | E |
| temp class | V |
| voltage | T4 |
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP147VE-T4E | shared catalog stem ✓ |
| Bally | BHP147VE-T4E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP147VE-T4E?
THP147VE-T4E has a rated capacity of 155900 btu_h. See the specifications table for rating conditions.
What voltage does THP147VE-T4E require?
THP147VE-T4E runs on 460 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.