THP147VE-T3E

Trenton Refrigeration THP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
capacity155900 btu_hTHP + THP-GEN-E p.6
151500 btu_hTHP + THP-GEN-E p.6
147100 btu_hTHP + THP-GEN-E p.6
133900 btu_hTHP + THP-GEN-E p.6
125000 btu_hTHP + THP-GEN-E p.6
126800 btu_hp.6
123200 btu_hp.6
119600 btu_hp.6
108800 btu_hp.6
101700 btu_hp.6
155900 btu_hTHP + THP-GEN-E p.6
151500 btu_hTHP + THP-GEN-E p.6
147100 btu_hTHP + THP-GEN-E p.6
133900 btu_hTHP + THP-GEN-E p.6
125000 btu_hTHP + THP-GEN-E p.6
126800 btu_hp.8
123200 btu_hp.8
119600 btu_hp.8
108800 btu_hp.8
101700 btu_hp.8
airflow17600 cfmTHP + THP-GEN-E p.6
8310 l_sTHP + THP-GEN-E p.6
refrigerant charge47 lbp.6
21.4 kgp.6
43.2 lbp.6
19.6 kgp.6
30.3 lbTHP + THP-GEN-E p.6
13.7 kgsources differTHP p.6
13.8 kgsources differTHP-GEN-E p.4
45.1 lbp.6
20.5 kgp.6
47 lbp.6
21.4 kgp.6
43.2 lbp.8
19.6 kgp.8
awef rating4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.31
4.15 ratiop.31
suction od2-5/8 inchessources differTHP p.31
3 1/8 inchessources differTHP-GEN-E p.36
distributor inlet1 5/8 inchesp.31
1 5/8 inchesTHP + THP-GEN-E p.31
side port connection1-3/8 inchesp.31
1-3/8 inchesp.36
hot gas connection1-5/8 inchesp.31
shipping weight926 lbp.32
420 kgp.32
mca115.8 ampssources differTHP p.14
20 ampssources differTHP-GEN-E p.10
57.9 ampssources differTHP-GEN-E p.10
- ampssources differTHP-GEN-E p.10
esp circuit 208 230 3 60 mop a125THP + THP-GEN-E p.14
voltage208 VTHP + THP-GEN-E p.?
phase3 phTHP + THP-GEN-E p.?
frequency60 HzTHP + THP-GEN-E p.?
fan qty3 countp.36
drain pan loop conn od sweat 1 3 81-5/8p.36
r454a sporlan ebste 8 zpOTE-40-ZPp.40
r448a r449a r407a r407c r454c r455a sporlan ebsve 8 zpOVE-40-ZPp.40
r404a r507 sporlan ebsse 7 1 2 zpOSE-30-ZPp.40
liquid line od1 1/8 inchesp.49
29 mmp.50
suction line od2 5/8 inchesp.49
67 mmp.50
maximum line length a 10 ft minimum room area ft2424p.49
maximum line length b 25 ft507p.49
maximum line length c 50 ft644*p.49
maximum line length d 100 ft919*p.49
maximum line length a 3m minimum room area m239p.50
maximum line length b 7 6m47p.50
maximum line length c 15 2m60*p.50
maximum line length d 30 5m85*p.50
motor hp1 hpp.10
motor fla15 ampsp.10
motor watts1680 wattsp.10
mop25 ampsp.10
total watts35000 wattsp.10
total amps46.3 ampssources differTHP-GEN-E p.10
- ampssources differTHP-GEN-E p.10
defrost heaters circuit 1 208 230 3 60 mop a60p.10
defrost heaters circuit 2 208 230 3 60 mop a60p.10
defrost heaters circuit 3 208 230 3 60 mop a-p.10
esp circuit mca115.8 ampsp.16
of fans 13p.58

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including THP_1111525, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including THP-GEN-E_1112936, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
THP147VE-T3E208-230/3/60Check availability

Nomenclature

Position / meaningValue
capacity code147
capacity mbh147
defrostE
generation suffixE
temp classV
voltageT3

Parts

5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

PartPart numberQtyListAvailability
Distributor nozzleA30--Check availability
Electronic expansion valveE3V65order as E3V65BWRC1--Check availability
Safety check valveCSOV21order as CSOV-21S--Check availability
Safety shutoff solenoidSSOV19--Check availability
Solenoid valveB19order as B19S2-7/8--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKHP147VE-T3Eshared catalog stem
BallyBHP147VE-T3Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of THP147VE-T3E?

THP147VE-T3E has a rated capacity of 155900 btu_h. See the specifications table for rating conditions.

What voltage does THP147VE-T3E require?

THP147VE-T3E runs on 208 V supply power.

Related models in THP