THP131HA-S4E
Trenton Refrigeration THP evaporator.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 131100 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | p.3 |
| 129800 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | p.3 | |
| 128500 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.3 | |
| 131100 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 129800 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 128500 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 106600 btu_h | evap temp f: 25; refrigerant: R404A/R507 | p.7 | |
| 105500 btu_h | evap temp f: 15; refrigerant: R404A/R507 | p.7 | |
| 104500 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.7 | |
| airflow | 11100 cfm | p.7 | |
| 5240 l_s | p.7 | ||
| refrigerant charge | 21.4 lb | refrigerant: R454A/R454C/R455A | p.3 |
| 9.7 kg | refrigerant: R454A/R454C/R455A | p.3 | |
| 29 lb | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 13.2 kg | refrigerant: R407A/R407C/R448A/R449A | p.5 | |
| 22.2 lb | refrigerant: R404A/R507 | p.7 | |
| 10.1 kg | refrigerant: R404A/R507 | p.7 | |
| awef rating | 9 ratio | refrigerant: R404A/R507/R448A/R449A/R407C/R407A | p.31 |
| 9 ratio | refrigerant: R454A/R454C/R455A | p.31 | |
| r454a sporlan ebste 8 c | OTE-15-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.39 |
| r448a r449a r407a r407c r454c r455a sporlan ebsve 8 c | OVE-15-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.39 |
| r404a r507 sporlan ebsse 6 c | OSE-12-C | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.39 |
| liquid line od | 0.875 inches | p.49 | |
| 22 mm | p.50 | ||
| suction line od | 2 1/8 inches | p.49 | |
| 54 mm | p.50 | ||
| maximum line length a 10 ft minimum room area ft2 | 295 | p.49 | |
| maximum line length b 25 ft | 346 | p.49 | |
| maximum line length c 50 ft | 432 | p.49 | |
| maximum line length d 100 ft | 603* | p.49 | |
| maximum line length a 3m minimum room area m2 | 27 | p.50 | |
| maximum line length b 7 6m | 32 | p.50 | |
| maximum line length c 15 2m | 40 | p.50 | |
| maximum line length d 30 5m | 56* | p.50 | |
| fan qty | 2 count | p.34 | |
| suction od | 2 1/8 inches | p.34 | |
| distributor inlet | 1 3/8 inches | p.34 | |
| shipping weight | 695 lb | p.37 | |
| 315 kg | p.37 | ||
| motor hp | 1 hp | p.9 | |
| motor fla | 5 amps | p.9 | |
| motor watts | 1040 watts | p.9 | |
| mca | 15 amps | p.9 | |
| mop | 20 amps | p.9 | |
| esp circuit mca | 15 amps | p.16 | |
| esp circuit 460 1 60 mop a | 20 | p.16 | |
| voltage | 460 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP131HA-S4E | 460/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 131 |
| capacity mbh | 131 |
| defrost | A |
| generation suffix | E |
| temp class | H |
| voltage | S4 |
Parts
1 factory parts for this unit: 1from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Solenoid valve | B14order as B14S2-5/8ODF✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP131HA-S4E | shared catalog stem ✓ |
| Bally | BHP131HA-S4E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP131HA-S4E?
THP131HA-S4E has a rated capacity of 131100 btu_h. See the specifications table for rating conditions.
What voltage does THP131HA-S4E require?
THP131HA-S4E runs on 460 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.