THP130VH-S4D
Trenton Refrigeration THP high profile evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 138300 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | p.6 |
| 134400 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | p.6 | |
| 130500 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | p.6 | |
| 118800 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | p.6 | |
| 110900 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | p.6 | |
| 112500 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.6 | |
| 109300 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.6 | |
| 106100 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.6 ✓ | |
| 96600 btu_h | evap temp f: 30; refrigerant: R404A/R507 | p.6 | |
| 90200 btu_h | evap temp f: 40; refrigerant: R404A/R507 | p.6 ✓ | |
| 138300 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | p.6 | |
| 134400 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.6 | |
| 130500 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | p.6 | |
| 118800 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | p.6 | |
| 110900 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | p.6 | |
| airflow | 18600 cfm | p.6 | |
| 8780 l_s | p.6 | ||
| refrigerant charge | 37.6 lb | refrigerant: R407A | p.6 |
| 17.1 kg | refrigerant: R407A | p.6 | |
| 34.6 lb | refrigerant: R404A/R507 | p.6 | |
| 15.7 kg | refrigerant: R404A/R507 | p.6 | |
| 24.6 lb | refrigerant: R454A/R454C/R455A | p.6 | |
| 11.2 kg | refrigerant: R454A/R454C/R455A | p.6 | |
| 36.1 lb | refrigerant: R448A/R449A | p.6 | |
| 16.4 kg | refrigerant: R448A/R449A | p.6 | |
| awef rating | 4.15 ratio | refrigerant: R404A/R507 | p.28 ✓ |
| 4.15 ratio | refrigerant: R448A/R449A | p.28 | |
| 4.15 ratio | refrigerant: R407C/R407A | p.28 | |
| 4.15 ratio | refrigerant: R454A | p.28 | |
| 4.15 ratio | refrigerant: R454C | p.28 | |
| 4.15 ratio | refrigerant: R455A | p.28 | |
| suction od | 2-5/8 inches | p.31 | |
| distributor inlet | 1 5/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| side port connection | 1-3/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| hot gas connection | 1-5/8 inchessources differ | THP p.31 | |
| 130VR inchessources differ | THP p.32 | ||
| 429 inchessources differ | THP p.32 | ||
| 946 lb | p.32 | ||
| motor hp | 130VG hpsources differ | THP p.32 | |
| 130VT hpsources differ | THP p.32 | ||
| 1 hpsources differ | THP p.12 | ||
| shipping weight | 946 lb | p.32 | |
| 429 kg | p.32 | ||
| fan qty | 3 count | p.12 ✓ | |
| motor fla | 7.5 amps | p.12 | |
| total watts | 1560 watts | p.12 | |
| mca | 15 amps | p.12 | |
| mop | 20 amps | p.12 | |
| voltage | 460 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP130VH-S4D | 460/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 130 |
| capacity mbh | 130 |
| defrost | H |
| generation suffix | D |
| temp class | V |
| voltage | S4 |
Parts
5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | A25✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V65order as E3V65BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV21order as CSOV-21S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV19✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B14order as B14S2-5/8ODF✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP130VH-S4D | shared catalog stem ✓ |
| Bally | BHP130VH-S4D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP130VH-S4D?
THP130VH-S4D has a rated capacity of 138300 btu_h. See the specifications table for rating conditions.
What voltage does THP130VH-S4D require?
THP130VH-S4D runs on 460 V supply power.
Related models in THP