THP110LE-T3E
Trenton Refrigeration THP evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 116600 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | THP + THP-GEN-E p.5 ✓ |
| 113300 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | THP + THP-GEN-E p.5 ✓ | |
| 110000 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | THP + THP-GEN-E p.5 ✓ | |
| 100100 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | THP + THP-GEN-E p.5 ✓ | |
| 93500 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | THP + THP-GEN-E p.5 ✓ | |
| 94400 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.5 | |
| 91800 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.5 | |
| 89100 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.5 | |
| 81100 btu_h | evap temp f: 30; refrigerant: R404A/R507 | p.5 ✓ | |
| 75700 btu_h | evap temp f: 40; refrigerant: R404A/R507 | p.5 | |
| 116600 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | THP + THP-GEN-E p.5 ✓ | |
| 113300 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | THP + THP-GEN-E p.5 ✓ | |
| 110000 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | THP + THP-GEN-E p.5 ✓ | |
| 100100 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | THP + THP-GEN-E p.5 ✓ | |
| 93500 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | THP + THP-GEN-E p.5 ✓ | |
| 94400 btu_h | evap temp f: 0; refrigerant: R404A | p.8 | |
| 91800 btu_h | evap temp f: 10; refrigerant: R404A | p.8 | |
| 89100 btu_h | evap temp f: 20; refrigerant: R404A | p.8 | |
| 81100 btu_h | evap temp f: 30; refrigerant: R404A | p.8 | |
| 75700 btu_h | evap temp f: 40; refrigerant: R404A | p.8 | |
| airflow | 11300 cfm | THP + THP-GEN-E p.5 ✓ | |
| 5330 l_s | THP + THP-GEN-E p.5 ✓ | ||
| refrigerant charge | 31.7 lb | refrigerant: R407A | p.5 |
| 14.4 kg | refrigerant: R407A | p.5 | |
| 29.2 lb | refrigerant: R404A/R507 | p.5 | |
| 13.3 kg | refrigerant: R404A/R507 | p.5 | |
| 21 lbsources differ | refrigerant: R454A/R454C/R455A | THP p.5 | |
| 21.1 lbsources differ | refrigerant: R454A/R454C/R455A | THP-GEN-E p.4 | |
| 9.5 kgsources differ | refrigerant: R454A/R454C/R455A | THP p.5 | |
| 9.6 kgsources differ | refrigerant: R454A/R454C/R455A | THP-GEN-E p.4 | |
| 30.4 lb | refrigerant: R448A/R449A | p.5 | |
| 13.8 kg | refrigerant: R448A/R449A | p.5 | |
| 31.7 lb | refrigerant: R407A/R448A/R449A | p.6 | |
| 14.4 kg | refrigerant: R407A/R448A/R449A | p.6 | |
| 29.2 lb | refrigerant: R404A | p.8 | |
| 13.3 kg | refrigerant: R404A | p.8 | |
| awef rating | 4.15 ratio | refrigerant: R404A/R507 | p.28 ✓ |
| 4.15 ratio | refrigerant: R448A/R449A | p.28 | |
| 4.15 ratio | refrigerant: R407C/R407A | p.28 | |
| 4.15 ratio | refrigerant: R454A | p.28 | |
| 4.15 ratio | refrigerant: R454C | p.28 | |
| 4.15 ratio | refrigerant: R455A | p.28 | |
| 4.15 ratio | refrigerant: R404A/R507/R448A/R449A/R407C/R407A | p.31 | |
| 4.15 ratio | refrigerant: R454A/R454C/R455A | p.31 | |
| suction od | 2-5/8 inchessources differ | THP p.31 | |
| 3 1/8 inchessources differ | THP-GEN-E p.36 | ||
| distributor inlet | 1 5/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| 1 5/8 inches | THP + THP-GEN-E p.31 ✓ | ||
| side port connection | 1-1/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| 1-1/8 inches | p.36 | ||
| hot gas connection | 1-3/8 inches | p.31 | |
| shipping weight | 679 lb | THP + THP-GEN-E p.32 ✓ | |
| 308 kg | THP + THP-GEN-E p.32 ✓ | ||
| mca | 81 ampssources differ | THP p.14 | |
| 15 ampssources differ | THP-GEN-E p.10 | ||
| 40.5 ampssources differ | THP-GEN-E p.10 | ||
| - ampssources differ | THP-GEN-E p.10 | ||
| esp circuit 208 230 3 60 mop a | 90 | THP + THP-GEN-E p.14 ✓ | |
| voltage | 208 V | THP + THP-GEN-E p.? ✓ | |
| phase | 3 ph | THP + THP-GEN-E p.? ✓ | |
| frequency | 60 Hz | THP + THP-GEN-E p.? ✓ | |
| fan qty | 2 count | p.36 | |
| drain pan loop conn od sweat 1 3 8 | 1-3/8 | p.36 | |
| r454a sporlan ebste 8 zp | OTE-20-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.40 |
| r448a r449a r407a r407c r454c r455a sporlan ebsve 8 zp | OVE-20-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.40 |
| r404a r507 sporlan ebsse 7 1 2 zp | OSE-21-ZP | refrigerant: R404A/R407A/R407C/R448A/R449A/R454A/R454C/R455A/R507 | p.40 |
| liquid line od | 0.875 inches | p.49 | |
| 22 mm | p.50 | ||
| suction line od | 2 5/8 inches | p.49 | |
| 67 mm | p.50 | ||
| maximum line length a 10 ft minimum room area ft2 | 290 | p.49 | |
| maximum line length b 25 ft | 340 | p.49 | |
| maximum line length c 50 ft | 423 | p.49 | |
| maximum line length d 100 ft | 590* | p.49 | |
| maximum line length a 3m minimum room area m2 | 27 | p.50 | |
| maximum line length b 7 6m | 32 | p.50 | |
| maximum line length c 15 2m | 39 | p.50 | |
| maximum line length d 30 5m | 55* | p.50 | |
| motor hp | 1 hp | p.10 | |
| motor fla | 10 amps | p.10 | |
| motor watts | 1120 watts | p.10 | |
| mop | 20 amps | p.10 | |
| total watts | 24500 watts | p.10 | |
| total amps | 32.4 ampssources differ | THP-GEN-E p.10 | |
| - ampssources differ | THP-GEN-E p.10 | ||
| defrost heaters circuit 1 208 230 3 60 mop a | 45 | p.10 | |
| defrost heaters circuit 2 208 230 3 60 mop a | 45 | p.10 | |
| defrost heaters circuit 3 208 230 3 60 mop a | - | p.10 | |
| esp circuit mca | 81 amps | p.16 | |
| of fans 1 | 2 | p.57 |
Sources: , . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP110LE-T3E | 208-230/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 110 |
| capacity mbh | 110 |
| defrost | E |
| generation suffix | E |
| temp class | L |
| voltage | T3 |
Parts
5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | A25✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V55order as E3V55BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV21order as CSOV-21S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV19✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B14order as B14S2-5/8ODF✓ | Solenoid valve; Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP110LE-T3E | shared catalog stem ✓ |
| Bally | BHP110LE-T3E | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP110LE-T3E?
THP110LE-T3E has a rated capacity of 116600 btu_h. See the specifications table for rating conditions.
What voltage does THP110LE-T3E require?
THP110LE-T3E runs on 208 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.