Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
fan qty3 countTHP + THP-GEN-E p.6
capacity113700 btu_hTHP + THP-GEN-E p.6
110500 btu_hTHP + THP-GEN-E p.6
107300 btu_hTHP + THP-GEN-E p.6
97600 btu_hTHP + THP-GEN-E p.6
91200 btu_hTHP + THP-GEN-E p.6
92400 btu_hp.6
89800 btu_hp.6
87200 btu_hp.6
79400 btu_hp.6
74100 btu_hp.6
113700 btu_hTHP + THP-GEN-E p.6
110500 btu_hTHP + THP-GEN-E p.6
107300 btu_hTHP + THP-GEN-E p.6
97600 btu_hTHP + THP-GEN-E p.6
91200 btu_hTHP + THP-GEN-E p.6
92400 btu_hp.8
89800 btu_hp.8
87200 btu_hp.8
79400 btu_hp.8
74100 btu_hp.8
airflow19200 cfmTHP + THP-GEN-E p.6
9060 l_sTHP + THP-GEN-E p.6
refrigerant charge28.2 lbp.6
12.8 kgp.6
25.9 lbp.6
11.8 kgp.6
19.1 lbTHP + THP-GEN-E p.6
8.6 kgsources differTHP p.6
8.7 kgsources differTHP-GEN-E p.4
27.1 lbp.6
12.3 kgp.6
28.2 lbp.6
12.8 kgp.6
25.9 lbp.8
11.8 kgp.8
awef rating4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.31
4.15 ratiop.31
suction od2-5/8 inchessources differTHP p.31
3 1/8 inchessources differTHP-GEN-E p.36
distributor inlet1 5/8 inchesp.31
1 5/8 inchesTHP + THP-GEN-E p.31
side port connection1-3/8 inchesp.31
1-3/8 inchesp.36
hot gas connection1-5/8 inchesp.31
shipping weight576 lbp.32
261 kgp.32
mca41.5 ampssources differTHP p.14
15 ampssources differTHP-GEN-E p.11
41.5 ampssources differTHP-GEN-E p.11
- ampssources differTHP-GEN-E p.11
esp circuit 460 3 60 mop a45THP + THP-GEN-E p.14
voltage460 VTHP + THP-GEN-E p.?
phase3 phTHP + THP-GEN-E p.?
frequency60 HzTHP + THP-GEN-E p.?
drain pan loop conn od sweat 1 3 81-5/8p.36
r454a sporlan ebste 8 zpOTE-30-ZPp.40
r448a r449a r407a r407c r454c r455a sporlan ebsve 8 zpOVE-30-ZPp.40
r404a r507 sporlan ebsse 7 1 2 zpOSE-21-ZPp.40
liquid line od0.875 inchesp.49
22 mmp.50
suction line od2 5/8 inchesp.49
67 mmp.50
maximum line length a 10 ft minimum room area ft2266p.49
maximum line length b 25 ft316p.49
maximum line length c 50 ft399p.49
maximum line length d 100 ft566*p.49
maximum line length a 3m minimum room area m225p.50
maximum line length b 7 6m29p.50
maximum line length c 15 2m37p.50
maximum line length d 30 5m53*p.50
motor hp1 hpp.11
motor fla7.5 ampsp.11
motor watts1560 wattsp.11
mop20 ampsp.11
total watts24500 wattsp.11
total amps33.2 ampssources differTHP-GEN-E p.11
- ampssources differTHP-GEN-E p.11
defrost heaters circuit 1 460 3 60 mop a45p.11
defrost heaters circuit 2 460 3 60 mop a-p.11
esp circuit mca41.5 ampsp.16
of fans 13p.58

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including THP_1111525, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including THP-GEN-E_1112936, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
THP107VE-T4E460/3/60Check availability

Nomenclature

Position / meaningValue
capacity code107
capacity mbh107
defrostE
generation suffixE
temp classV
voltageT4

Parts

5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

PartPart numberQtyListAvailability
Distributor nozzleA20--Check availability
Electronic expansion valveE3V65order as E3V65BWRC1--Check availability
Safety check valveCSOV21order as CSOV-21S--Check availability
Safety shutoff solenoidSSOV19--Check availability
Solenoid valveB14order as B14S2-5/8ODF--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKHP107VE-T4Eshared catalog stem
BallyBHP107VE-T4Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of THP107VE-T4E?

THP107VE-T4E has a rated capacity of 113700 btu_h. See the specifications table for rating conditions.

What voltage does THP107VE-T4E require?

THP107VE-T4E runs on 460 V supply power.

Related models in THP