THP103HA-T3D
Trenton Refrigeration THP high profile evaporator.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 2 count | p.3 ✓ | |
| capacity | 103300 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | p.3 |
| 102300 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | p.3 | |
| 101200 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | p.3 | |
| 84000 btu_h | evap temp f: 25; refrigerant: R404A/R507 | p.3 | |
| 83200 btu_h | evap temp f: 15; refrigerant: R404A/R507 | p.3 | |
| 82300 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.3 | |
| 103300 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | p.3 | |
| 102300 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | p.3 | |
| 101200 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.3 | |
| airflow | 12200 cfm | p.3 | |
| 5760 l_s | p.3 | ||
| refrigerant charge | 17.8 lb | refrigerant: R407A/R407C | p.3 |
| 8.1 kg | refrigerant: R407A/R407C | p.3 | |
| 16.4 lb | refrigerant: R404A/R507 | p.3 | |
| 7.4 kg | refrigerant: R404A/R507 | p.3 | |
| 13 lb | refrigerant: R454A/R454C/R455A | p.3 | |
| 5.9 kg | refrigerant: R454A/R454C/R455A | p.3 | |
| 17.1 lb | refrigerant: R448A/R449A | p.3 | |
| 7.8 kg | refrigerant: R448A/R449A | p.3 | |
| awef rating | 9 ratio | refrigerant: R404A/R507 | p.28 ✓ |
| 9 ratio | refrigerant: R448A/R449A | p.28 | |
| 9 ratio | refrigerant: R407C/R407A | p.28 | |
| 9 ratio | refrigerant: R454A | p.28 | |
| 9 ratio | refrigerant: R454C | p.28 | |
| 9 ratio | refrigerant: R455A | p.28 | |
| suction od | 1-5/8 inches | p.31 | |
| distributor inlet | 1 3/8 inches | p.31 | |
| shipping weight | 603 lb | p.32 | |
| 274 kg | p.32 | ||
| mca | 15 amps | p.13 | |
| esp circuit 208 230 3 60 mop a | 20 | p.13 | |
| voltage | 208 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase.
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 103 |
| capacity mbh | 103 |
| defrost | A |
| generation suffix | D |
| temp class | H |
| voltage | T3 |
Parts
5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | C12✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V55order as E3V55BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV13order as CSOV-13S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV19✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B10order as B10S2-5/8✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
No sister-brand equivalents cataloged for this model.
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP103HA-T3D?
THP103HA-T3D has a rated capacity of 103300 btu_h. See the specifications table for rating conditions.
What voltage does THP103HA-T3D require?
THP103HA-T3D runs on 208 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.