THP098VE-T3E

Trenton Refrigeration THP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
capacity103700 btu_hTHP + THP-GEN-E p.6
100700 btu_hTHP + THP-GEN-E p.6
97800 btu_hTHP + THP-GEN-E p.6
89000 btu_hTHP + THP-GEN-E p.6
83100 btu_hTHP + THP-GEN-E p.6
84300 btu_hp.6
81900 btu_hp.6
79500 btu_hp.6
72300 btu_hp.6
67600 btu_hp.6
103700 btu_hTHP + THP-GEN-E p.6
100700 btu_hTHP + THP-GEN-E p.6
97800 btu_hTHP + THP-GEN-E p.6
89000 btu_hTHP + THP-GEN-E p.6
83100 btu_hTHP + THP-GEN-E p.6
84300 btu_hp.8
81900 btu_hp.8
79500 btu_hp.8
72300 btu_hp.8
67600 btu_hp.8
airflow11800 cfmTHP + THP-GEN-E p.6
5570 l_sTHP + THP-GEN-E p.6
refrigerant charge31.7 lbp.6
14.4 kgp.6
29.2 lbp.6
13.3 kgp.6
21 lbsources differTHP p.6
21.1 lbsources differTHP-GEN-E p.4
9.5 kgsources differTHP p.6
9.6 kgsources differTHP-GEN-E p.4
30.4 lbp.6
13.8 kgp.6
31.7 lbp.6
14.4 kgp.6
29.2 lbp.8
13.3 kgp.8
awef rating4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.31
4.15 ratiop.31
suction od2-5/8 inchessources differTHP p.31
3 1/8 inchessources differTHP-GEN-E p.36
distributor inlet1 5/8 inchesp.31
1 5/8 inchesTHP + THP-GEN-E p.31
side port connection1-1/8 inchesp.31
1-1/8 inchesp.36
hot gas connection1-3/8 inchesp.31
shipping weight648 lbp.32
294 kgp.32
mca81 ampssources differTHP p.14
15 ampssources differTHP-GEN-E p.10
40.5 ampssources differTHP-GEN-E p.10
- ampssources differTHP-GEN-E p.10
esp circuit 208 230 3 60 mop a90THP + THP-GEN-E p.14
voltage208 VTHP + THP-GEN-E p.?
phase3 phTHP + THP-GEN-E p.?
frequency60 HzTHP + THP-GEN-E p.?
fan qty2 countp.36
drain pan loop conn od sweat 1 3 81-3/8p.36
r454a sporlan ebste 8 zpOTE-20-ZPp.40
r448a r449a r407a r407c r454c r455a sporlan ebsve 8 zpOVE-20-ZPp.40
r404a r507 sporlan ebsse 7 1 2 zpOSE-21-ZPp.40
liquid line od0.875 inchesp.49
22 mmp.50
suction line od2 5/8 inchesp.49
67 mmp.50
maximum line length a 10 ft minimum room area ft2290p.49
maximum line length b 25 ft340p.49
maximum line length c 50 ft423p.49
maximum line length d 100 ft590*p.49
maximum line length a 3m minimum room area m227p.50
maximum line length b 7 6m32p.50
maximum line length c 15 2m39p.50
maximum line length d 30 5m55*p.50
motor hp1 hpp.10
motor fla10 ampsp.10
motor watts1120 wattsp.10
mop20 ampsp.10
total watts24500 wattsp.10
total amps32.4 ampssources differTHP-GEN-E p.10
- ampssources differTHP-GEN-E p.10
defrost heaters circuit 1 208 230 3 60 mop a45p.10
defrost heaters circuit 2 208 230 3 60 mop a45p.10
defrost heaters circuit 3 208 230 3 60 mop a-p.10
esp circuit mca81 ampsp.16
of fans 12p.58

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including THP_1111525, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including THP-GEN-E_1112936, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
THP098VE-T3E208-230/3/60Check availability

Nomenclature

Position / meaningValue
capacity code098
capacity mbh98
defrostE
generation suffixE
temp classV
voltageT3

Parts

5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

PartPart numberQtyListAvailability
Distributor nozzleA20--Check availability
Electronic expansion valveE3V55order as E3V55BWRC1--Check availability
Safety check valveCSOV21order as CSOV-21S--Check availability
Safety shutoff solenoidSSOV19--Check availability
Solenoid valveB14order as B14S2-5/8ODF--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKHP098VE-T3Eshared catalog stem
BallyBHP098VE-T3Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of THP098VE-T3E?

THP098VE-T3E has a rated capacity of 103700 btu_h. See the specifications table for rating conditions.

What voltage does THP098VE-T3E require?

THP098VE-T3E runs on 208 V supply power.

Related models in THP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.