SpecificationValueSource
capacity103700 btu_hp.6
100700 btu_hp.6
97800 btu_hp.6
89000 btu_hp.6
83100 btu_hp.6
84300 btu_hp.6
81900 btu_hp.6
79500 btu_hp.6
72300 btu_hp.6
67600 btu_hp.6
103700 btu_hp.6
100700 btu_hp.6
97800 btu_hp.6
89000 btu_hp.6
83100 btu_hp.6
airflow11800 cfmp.6
5570 l_sp.6
11800 cfmp.6
5570 l_sp.6
11800 cfmp.6
5570 l_sp.6
refrigerant charge31.7 lbp.6
14.4 kgp.6
29.2 lbp.6
13.3 kgp.6
21 lbp.6
9.5 kgp.6
r404a r5074.15p.28
r448a r449a4.15p.28
r407c r407a4.15p.28
awef rating4.15 ratiop.28
4.15 ratiop.28
4.15 ratiop.28
suction od2-5/8 inchesp.31
2-5/8 inchesp.31
distributor inlet1 5/8 inchesp.31
1 5/8 inchesp.31
reverse cycle 3 pipe defrost side port connection od sweat1-1/8p.31
hot gas connection1-3/8 inchesp.31
distributor nozzleA20 part_idp.33
A20 part_idp.35
electronic expansion valveE3V55 part_numberp.35
solenoid valveB14 part_numberp.35
safety solenoid valveSSOV19 part_numberp.35
safety check valveCSOV21 part_numberp.35
shipping weight648 lbp.32
294 kgp.32
fan qty2 countp.8
motor hp1 hpp.8
motor fla10 ampsp.8
total watts1120 wattsp.8
24500 wattsp.8
mca15 ampsp.8
40.5 ampsp.8
40.5 ampsp.8
- ampsp.8
81 ampsp.14
fan motors standard ec motors mop a20p.8
total amps32.4 ampsp.8
32.4 ampsp.8
- ampsp.8
defrost heaters 208 230 1 60 circuit 1 mop a45p.8
defrost heaters 208 230 3 60 circut 2 mop a45p.8
defrost heaters 208 230 3 60 circut 3 mop a-p.8
esp circuit 208 230 3 60 mop a90p.14
voltage208 Vp.?
phase3 php.?
frequency60 Hzp.?

Sources: THP_1111525 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot

Orderable variants (1)

VariantVoltageAvailability
THP098VE-T3D208-230/3/60Check availability

Nomenclature

Position / meaningValue
capacity code98
defrostE
fan count0
generation suffixD
temp classV
voltageT3

Cross references

BrandEquivalent modelBasis
KeepRiteKHP098VE-T3Dshared catalog stem
BallyBHP098VE-T3Dshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of THP098VE-T3D?

THP098VE-T3D has a rated capacity of 103700 btu_h. See the specifications table for rating conditions.

What voltage does THP098VE-T3D require?

THP098VE-T3D runs on 208 V supply power.

Related models in THP