THP095ME-T3E

Trenton Refrigeration THP evaporator.

Specifications

Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.

SpecificationValueSource
fan qty2 countTHP + THP-GEN-E p.4
capacity95300 btu_hTHP + THP-GEN-E p.4
94300 btu_hTHP + THP-GEN-E p.4
93400 btu_hTHP + THP-GEN-E p.4
77500 btu_hTHP + THP-GEN-E p.4
76700 btu_hTHP + THP-GEN-E p.4
76000 btu_hTHP + THP-GEN-E p.4
95300 btu_hTHP + THP-GEN-E p.4
94300 btu_hTHP + THP-GEN-E p.4
93400 btu_hTHP + THP-GEN-E p.4
airflow12400 cfmTHP + THP-GEN-E p.4
5850 l_sTHP + THP-GEN-E p.4
refrigerant charge17.8 lbp.4
8.1 kgp.4
16.4 lbsources differTHP p.4
13.6 lbsources differTHP-GEN-E p.7
7.4 kgsources differTHP p.4
6.2 kgsources differTHP-GEN-E p.7
13 lbsources differTHP p.4
13.1 lbsources differTHP-GEN-E p.3
5.9 kgTHP + THP-GEN-E p.4
17.1 lbp.4
7.8 kgp.4
17.8 lbp.5
8.1 kgp.5
awef rating9 ratiop.28
9 ratiop.28
9 ratiop.28
9 ratiop.28
9 ratiop.28
9 ratiop.28
9 ratiop.31
9 ratiop.31
suction od1-5/8 inchessources differTHP p.31
1 7/8 inchessources differTHP-GEN-E p.34
distributor inlet1 3/8 inchesTHP + THP-GEN-E p.31
1 3/8 inchesp.31
side port connection1-1/8 inchesp.31
1-1/8 inchesp.36
hot gas connection1-3/8 inchesp.31
shipping weight594 lbTHP + THP-GEN-E p.32
270 kgTHP + THP-GEN-E p.32
mca57.7 ampssources differTHP p.14
15 ampssources differTHP-GEN-E p.10
57.7 ampssources differTHP-GEN-E p.10
- ampssources differTHP-GEN-E p.10
esp circuit 208 230 3 60 mop a60THP + THP-GEN-E p.14
voltage208 VTHP + THP-GEN-E p.?
phase3 phTHP + THP-GEN-E p.?
frequency60 HzTHP + THP-GEN-E p.?
drain pan loop conn od sweat 1 3 81-3/8p.36
r454a sporlan ebste 8 cOTE-15-Cp.39
r448a r449a r407a r407c r454c r455a sporlan ebsve 8 cOVE-15-Cp.39
r404a r507 sporlan ebsse 6 cOSE-12-Cp.39
liquid line od0.875 inchesp.49
22 mmp.50
suction line od1 5/8 inchesp.49
41 mmp.50
maximum line length a 10 ft minimum room area ft2192p.49
maximum line length b 25 ft242p.49
maximum line length c 50 ft324p.49
maximum line length d 100 ft488p.49
maximum line length a 3m minimum room area m218p.50
maximum line length b 7 6m22p.50
maximum line length c 15 2m30p.50
maximum line length d 30 5m45p.50
motor hp1 hpp.10
motor fla10 ampsp.10
motor watts1120 wattsp.10
mop20 ampsp.10
total watts17150 wattsp.10
total amps46.2 ampssources differTHP-GEN-E p.10
- ampssources differTHP-GEN-E p.10
defrost heaters circuit 1 208 230 3 60 mop a60p.10
defrost heaters circuit 2 208 230 3 60 mop a-p.10
defrost heaters circuit 3 208 230 3 60 mop a-p.10
esp circuit mca57.7 ampsp.16
of fans 12p.56

Sources:

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including THP_1111525, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

,

Source documents

Every value on this page is cited to a manufacturer document. Direct links to the documents, including THP-GEN-E_1112936, are a free member benefit. Accounts are coming; leave an email and we'll be in touch when source access goes live.

. Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.

Orderable variants (1)

VariantVoltageAvailability
THP095ME-T3E208-230/3/60Check availability

Nomenclature

Position / meaningValue
capacity code095
capacity mbh95
defrostE
generation suffixE
temp classM
voltageT3

Parts

5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.

Expansion and refrigerant circuit

PartPart numberQtyListAvailability
Distributor nozzleC12--Check availability
Electronic expansion valveE3V55order as E3V55BWRC1--Check availability
Safety check valveCSOV13order as CSOV-13S--Check availability
Safety shutoff solenoidSSOV19--Check availability
Solenoid valveB10order as B10S2-5/8--Check availability

Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.

Cross references

BrandEquivalent modelBasis
KeepRiteKHP095ME-T3Eshared catalog stem
BallyBHP095ME-T3Eshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of THP095ME-T3E?

THP095ME-T3E has a rated capacity of 95300 btu_h. See the specifications table for rating conditions.

What voltage does THP095ME-T3E require?

THP095ME-T3E runs on 208 V supply power.

Related models in THP