Trenton Refrigeration · THP · High Profile Evaporators

THP062ME-T4D

Trenton Refrigeration THP high profile evaporator.

59 extracted specifications, each traceable to its source document and page.

Specifications

SpecificationValueSource
capacity62000 btu_hp.4
61400 btu_hp.4
60800 btu_hp.4
50400 btu_hp.4
49900 btu_hp.4
49400 btu_hp.4
62000 btu_hp.4
61400 btu_hp.4
60800 btu_hp.4
airflow5700 cfmp.4
2690 l_sp.4
5700 cfmp.4
2690 l_sp.4
5700 cfmp.4
2690 l_sp.4
refrigerant charge15 lbp.4
6.8 kgp.4
13.8 lbp.4
6.3 kgp.4
11.1 lbp.4
5 kgp.4
r404a r5079p.28
r448a r449a9p.28
r407c r407a9p.28
awef rating9 ratiop.28
9 ratiop.28
9 ratiop.28
suction od1-3/8 inchesp.31
1-3/8 inchesp.31
distributor inlet1 1/8 inchesp.31
1 1/8 inchesp.31
reverse cycle 3 pipe defrost side port connection od sweat0.875p.31
hot gas connection1-3/8 inchesp.31
distributor nozzleE6 part_idp.33
E6 part_idp.34
electronic expansion valveE3V45 part_numberp.34
solenoid valveB9 part_numberp.34
safety solenoid valveSSOV10 part_numberp.34
safety check valveCSOV11 part_numberp.34
shipping weight386 lbp.32
175 kgp.32
fan qty1 countp.9
motor hp1 hpp.9
motor fla2.5 ampsp.9
total watts520 wattsp.9
12600 wattsp.9
mca15 ampsp.9
20.8 ampsp.9
- ampsp.9
20.8 ampsp.14
fan motors standard ec motors mop a20p.9
total amps16.6 ampsp.9
- ampsp.9
defrost heaters 460 3 60 circuit 1 mop a25p.9
defrost heaters 460 3 60 circut 2 mop a-p.9
esp circuit 460 3 60 mop a25p.14
voltage460 Vp.?
phase3 php.?
frequency60 Hzp.?

Sources: THP_1111525 · extraction with per-cell provenance · verify before purchase. · variants from distributor API snapshot

Orderable variants (1)

VariantVoltageAvailability
THP062ME-T4D460/3/60Check availability

Nomenclature

Position / meaningValue
capacity code62
defrostE
fan count0
generation suffixD
temp classM
voltageT4

Cross references

BrandEquivalent modelBasis
KeepRiteKHP062ME-T4Dshared catalog stem
BallyBHP062ME-T4Dshared catalog stem

In progress: cross-brand replacements by specification matching.

Frequently asked questions

What is the capacity of THP062ME-T4D?

THP062ME-T4D has a rated capacity of 62000 btu_h. See the specifications table for rating conditions.

What voltage does THP062ME-T4D require?

THP062ME-T4D runs on 460 V supply power.

Related models in THP

Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.