THP056ME-T3D
Trenton Refrigeration THP high profile evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 56300 btu_h | evap temp f: 25; refrigerant: R407A/R407C/R448A/R449A | p.4 |
| 55700 btu_h | evap temp f: 15; refrigerant: R407A/R407C/R448A/R449A | p.4 | |
| 55200 btu_h | evap temp f: 10; refrigerant: R407A/R407C/R448A/R449A | p.4 | |
| 45800 btu_h | evap temp f: 25; refrigerant: R404A/R507 | p.4 | |
| 45300 btu_h | evap temp f: 15; refrigerant: R404A/R507 | p.4 | |
| 44900 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.4 | |
| 56300 btu_h | evap temp f: 25; refrigerant: R454A/R454C/R455A | p.4 | |
| 55700 btu_h | evap temp f: 15; refrigerant: R454A/R454C/R455A | p.4 | |
| 55200 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.4 | |
| airflow | 6000 cfm | p.4 | |
| 2830 l_s | p.4 | ||
| refrigerant charge | 12.3 lb | refrigerant: R407A/R407C | p.4 |
| 5.6 kg | refrigerant: R407A/R407C | p.4 | |
| 11.3 lb | refrigerant: R404A/R507 | p.4 | |
| 5.1 kg | refrigerant: R404A/R507 | p.4 | |
| 9.1 lb | refrigerant: R454A/R454C/R455A | p.4 | |
| 4.1 kg | refrigerant: R454A/R454C/R455A | p.4 | |
| 11.8 lb | refrigerant: R448A/R449A | p.4 | |
| 5.4 kg | refrigerant: R448A/R449A | p.4 | |
| awef rating | 9 ratio | refrigerant: R404A/R507 | p.28 ✓ |
| 9 ratio | refrigerant: R448A/R449A | p.28 | |
| 9 ratio | refrigerant: R407C/R407A | p.28 | |
| 9 ratio | refrigerant: R454A | p.28 | |
| 9 ratio | refrigerant: R454C | p.28 | |
| 9 ratio | refrigerant: R455A | p.28 | |
| suction od | 1-3/8 inchessources differ | THP p.31 | |
| 39450 inchessources differ | THP p.31 | ||
| distributor inlet | 1 1/8 inches | p.31 | |
| 1 1/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 | |
| side port connection | 0.875 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| hot gas connection | 1-3/8 inches | p.31 | |
| shipping weight | 364 lb | p.32 | |
| 165 kg | p.32 | ||
| fan qty | 1 count | p.8 ✓ | |
| motor hp | 1 hp | p.8 | |
| motor fla | 5 amps | p.8 | |
| total watts | 560 wattssources differ | THP p.8 | |
| 8820 wattssources differ | THP p.8 | ||
| mca | 15 ampssources differ | THP p.8 | |
| 29.6 ampssources differ | THP p.8 | ||
| - ampssources differ | THP p.8 | ||
| mop | 20 amps | p.8 | |
| total amps | 23.7 ampssources differ | THP p.8 | |
| - ampssources differ | THP p.8 | ||
| defrost heaters 208 230 1 60 circuit 1 mop a | 30 | p.8 | |
| defrost heaters 208 230 3 60 circut 2 mop a | - | p.8 | |
| defrost heaters 208 230 3 60 circut 3 mop a | - | p.8 | |
| esp circuit 208 230 3 60 mop a | 30 | p.14 | |
| voltage | 208 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP056ME-T3D | 208-230/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 056 |
| capacity mbh | 56 |
| defrost | E |
| generation suffix | D |
| temp class | M |
| voltage | T3 |
Parts
9 factory parts for this unit: 9from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | E6order as E6S140✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V45order as E3V45BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV11order as CSOV-11S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV10✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B9order as B9S2✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Defrost and drain pan
Where several valves of one kind are listed, they are the manufacturer's selection options: which one a unit carries depends on the operating conditions shown. The service parts rows show what a documented build was actually fitted with.
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Defrost field kit | DFK-22✓ | Defrost kit (1-evap install), 208-230/3/60 | - | - | Check availability |
| Defrost field kit | DFK-33✓ | Defrost kit (2-evap install), 208-230/3/60 | - | - | Check availability |
| Fuse package | FP-143✓ | Fuse package (2-evap install), 208-230/3/60 | - | - | Check availability |
| Fuse package | FP-145✓ | Fuse package (1-evap install), 208-230/3/60 | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP056ME-T3D | shared catalog stem ✓ |
| Bally | BHP056ME-T3D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP056ME-T3D?
THP056ME-T3D has a rated capacity of 56300 btu_h. See the specifications table for rating conditions.
What voltage does THP056ME-T3D require?
THP056ME-T3D runs on 208 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.