THP049DE-T3D
Trenton Refrigeration THP high profile evaporator.
Specifications
Note:for some values below, the manufacturer's own documents disagree. Both figures are shown with their source. CrossRefHVAC is confirming the correct values with the manufacturer.
| Specification | Value | Conditions | Source |
|---|---|---|---|
| capacity | 42100 btu_h | evap temp f: 0; refrigerant: CO2 | p.36 |
| 40900 btu_h | evap temp f: 10; refrigerant: CO2 | p.36 | |
| 39700 btu_h | evap temp f: 20; refrigerant: CO2 | p.36 | |
| 36100 btu_h | evap temp f: 30; refrigerant: CO2 | p.36 ✓ | |
| 33700 btu_h | evap temp f: 40; refrigerant: CO2 | p.36 | |
| airflow | 6000 cfm | p.36 | |
| 2830 l_s | p.36 | ||
| refrigerant charge | 10.4 lb | refrigerant: CO2 | p.36 |
| 4.7 kg | refrigerant: CO2 | p.36 | |
| awef rating | 4.15 ratio | refrigerant: CO2 | p.41 ✓ |
| suction od | 0.625 inches | p.45 | |
| distributor inlet | 0.625 inches | defrost piping: reverse_cycle | p.45 |
| 0.625 inches | p.44 | ||
| liquid line od | 0.5 inches | defrost piping: reverse_cycle | p.45 |
| 0.5 inches | p.44 | ||
| side port connection | 0.5 inches | p.45 | |
| hot gas connection | 0.625 inches | p.45 | |
| shipping weight | 364 lb | p.46 | |
| 165 kg | p.46 | ||
| fan qty | 1 count | p.37 ✓ | |
| motor hp | 1 hp | p.37 | |
| motor fla | 5 amps | p.37 | |
| total watts | 560 wattssources differ | THP p.37 | |
| 8820 wattssources differ | THP p.37 | ||
| mca | 15 ampssources differ | THP p.37 | |
| 29.6 ampssources differ | THP p.37 | ||
| - ampssources differ | THP p.37 | ||
| mop | 20 amps | p.37 | |
| total amps | 23.7 ampssources differ | THP p.37 | |
| - ampssources differ | THP p.37 | ||
| defrost heaters 208 230 3 60 circuit 1 mop a | 30 | p.37 | |
| defrost heaters 208 230 3 60 circut 2 mop a | - | p.37 | |
| defrost heaters 208 230 3 60 circut 3 mop a | - | p.37 | |
| voltage | 208 V | p.? | |
| phase | 3 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP049DE-T3D | 208-230/3/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 049 |
| capacity mbh | 49 |
| defrost | E |
| generation suffix | D |
| temp class | D |
| voltage | T3 |
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP049DE-T3D | shared catalog stem ✓ |
| Bally | BHP049DE-T3D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP049DE-T3D?
THP049DE-T3D has a rated capacity of 42100 btu_h. See the specifications table for rating conditions.
What voltage does THP049DE-T3D require?
THP049DE-T3D runs on 208 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.