THP041LR-S2D
Trenton Refrigeration THP high profile evaporator.
Specifications
| Specification | Value | Conditions | Source |
|---|---|---|---|
| fan qty | 1 count | p.5 ✓ | |
| capacity | 43200 btu_h | evap temp f: 0; refrigerant: R407A/R448A/R449A | p.5 |
| 42000 btu_h | evap temp f: 10; refrigerant: R407A/R448A/R449A | p.5 | |
| 40800 btu_h | evap temp f: 20; refrigerant: R407A/R448A/R449A | p.5 | |
| 37100 btu_h | evap temp f: 30; refrigerant: R407A/R448A/R449A | p.5 | |
| 34700 btu_h | evap temp f: 40; refrigerant: R407A/R448A/R449A | p.5 | |
| 35200 btu_h | evap temp f: 0; refrigerant: R404A/R507 | p.5 | |
| 34200 btu_h | evap temp f: 10; refrigerant: R404A/R507 | p.5 | |
| 33200 btu_h | evap temp f: 20; refrigerant: R404A/R507 | p.5 | |
| 30200 btu_h | evap temp f: 30; refrigerant: R404A/R507 | p.5 | |
| 28200 btu_h | evap temp f: 40; refrigerant: R404A/R507 | p.5 ✓ | |
| 43200 btu_h | evap temp f: 0; refrigerant: R454A/R454C/R455A | p.5 | |
| 42000 btu_h | evap temp f: 10; refrigerant: R454A/R454C/R455A | p.5 | |
| 40800 btu_h | evap temp f: 20; refrigerant: R454A/R454C/R455A | p.5 | |
| 37100 btu_h | evap temp f: 30; refrigerant: R454A/R454C/R455A | p.5 | |
| 34700 btu_h | evap temp f: 40; refrigerant: R454A/R454C/R455A | p.5 | |
| airflow | 6200 cfm | p.5 | |
| 2930 l_s | p.5 | ||
| refrigerant charge | 9.5 lb | refrigerant: R407A | p.5 |
| 4.3 kg | refrigerant: R407A | p.5 | |
| 8.7 lb | refrigerant: R404A/R507 | p.5 | |
| 4 kg | refrigerant: R404A/R507 | p.5 | |
| 7 lb | refrigerant: R454A/R454C/R455A | p.5 | |
| 3.1 kg | refrigerant: R454A/R454C/R455A | p.5 | |
| 9.1 lb | refrigerant: R448A/R449A | p.5 | |
| 4.1 kg | refrigerant: R448A/R449A | p.5 | |
| awef rating | 4.15 ratio | refrigerant: R404A/R507 | p.28 ✓ |
| 4.15 ratio | refrigerant: R448A/R449A | p.28 | |
| 4.15 ratio | refrigerant: R407C/R407A | p.28 | |
| 4.15 ratio | refrigerant: R454A | p.28 | |
| 4.15 ratio | refrigerant: R454C | p.28 | |
| 4.15 ratio | refrigerant: R455A | p.28 | |
| suction od | 1-5/8 inches | p.31 | |
| distributor inlet | 1 1/8 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| side port connection | 0.875 inches | defrost piping: reverse_cycle_3_pipe | p.31 |
| hot gas connection | 1-3/8 inches | p.31 | |
| fpi | 6 | p.12 | |
| motor hp | 1 hp | p.12 | |
| motor fla | 5 amps | p.12 | |
| total watts | 560 watts | p.12 | |
| mca | 15 amps | p.12 | |
| mop | 20 amps | p.12 | |
| voltage | 208 V | p.? | |
| phase | 1 ph | p.? | |
| frequency | 60 Hz | p.? |
Sources: . Extraction with per-cell provenance. Verify before purchase. Variants from distributor API snapshot.
Orderable variants (1)
| Variant | Voltage | Availability |
|---|---|---|
| THP041LR-S2D | 208-230/1/60 | Check availability |
Nomenclature
| Position / meaning | Value |
|---|---|
| capacity code | 041 |
| capacity mbh | 41 |
| defrost | R |
| generation suffix | D |
| temp class | L |
| voltage | S2 |
Parts
5 factory parts for this unit: 5from the manufacturer's selection documents, 0 from Trenton service parts records. Prices are manufacturer list.
Expansion and refrigerant circuit
| Part | Part number | Description | Qty | List | Availability |
|---|---|---|---|---|---|
| Distributor nozzle | E8✓ | Distributor nozzle, Sporlan (Parker Hannifin) | - | - | Check availability |
| Electronic expansion valve | E3V45order as E3V45BWRC1✓ | Electronic expansion valve (EEV), Carel | - | - | Check availability |
| Safety check valve | CSOV13order as CSOV-13S✓ | Safety check valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Safety shutoff solenoid | SSOV10✓ | Safety shutoff solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
| Solenoid valve | B6order as B6S1✓ | Solenoid valve, Sporlan (Parker Hannifin) | - | - | Check availability |
Sources: manufacturer selection documents (page-cited) and Trenton service parts records. NLA: no longer available from the manufacturer. Verify before purchase.
Cross references
| Brand | Equivalent model | Basis |
|---|---|---|
| KeepRite | KHP041LR-S2D | shared catalog stem ✓ |
| Bally | BHP041LR-S2D | shared catalog stem ✓ |
In progress: cross-brand replacements by specification matching.
Frequently asked questions
What is the capacity of THP041LR-S2D?
THP041LR-S2D has a rated capacity of 43200 btu_h. See the specifications table for rating conditions.
What voltage does THP041LR-S2D require?
THP041LR-S2D runs on 208 V supply power.
Related models in THP
Independent reference. Not affiliated with any manufacturer. Verify specifications against manufacturer documentation before purchase.